MONTHYEARML23320A2472023-11-17017 November 2023 Constellation - Summary of November 14, 2023, Public Pre-Application Meeting with Constellation Energy Generation, LLC on Adoption of TSTF-591 ML23271A2682023-10-0505 October 2023 September 25, 2023, Summary of with Constellation Energy Generation, LLC on Proposed Changes to Emergency Plans ML23263B1062023-09-22022 September 2023 R. E. Ginna Nuclear Power Plant - Constellation - Pre-Application Amse 9/18/2023 Meeting Summary ML23179A0012023-06-28028 June 2023 6/7/2023 - Annual Assessment Meeting for Pa/Md/Ny/Nj Nuclear Power Plants - Meeting Summary ML23055A0352023-03-24024 March 2023 Summary of February 23, 2023, with Constellation Energy Generation, LLC on Proposed Changes to Emergency Plans to Revise Emergency Action Levels ML22187A1462022-07-0606 July 2022 Joint Annual Assessment Meeting for Pa/Md/Nj/Ny Nuclear Power Plants - Meeting Summary ML21333A1532021-11-30030 November 2021 Summary of November 16, 2021, Meeting with Exelon Generation Company, LLC Regarding a Planned Request for an Alternative to Extend the Inservice Inspection Interval ML21237A0412021-08-30030 August 2021 Summary of the July 27, 2021, Meeting with Exelon Generation Company, LLC Regarding a Planned Request to Use Case OMN-28, ML21176A0822021-07-0606 July 2021 June 15, 2021, Summary of Meeting with Exelon Generation Company, LLC Vessel Nozzle Repair Related to a Planned Request for an Alternative Related to Reactor Pressure ML21139A1852021-06-22022 June 2021 Summary of Meeting with Exelon Generation Company, LLC Regarding Its Requested Alternative to Eliminate Certain Documentation Requirements for the Replacement of Pressure Retaining Bolting ML21011A2822021-01-21021 January 2021 Summary of January 6, 2021, Presubmittal Meeting Between the NRC and Exelon Generation Company, LLC Regarding Licensing Activities to Support the Planned Early Closures of Byron, Unit Nos. 1 and 2 and Dresden, Units 2 and 3 ML20351A2832020-12-18018 December 2020 Summary of Meeting with Exelon Generation Company, LLC Regarding a Planned Request for an Exemption to Reduce the Frequency of Updates to Its Inservice Testing and Inspection Programs ML20342A3522020-12-10010 December 2020 Summary of November 13, 2020, Meeting with Exelon Generation Company, LLC Regarding a Planned Request for an Alterantive to Certain Documentation Requirements for the Replacement of Pressure Retaining Bolting (EPID-L-2020-LRM-0102) ML20323A0332020-12-0101 December 2020 Summary of November 4, 2020, Meeting with Exelon Generation Company, LLC Regarding a Planned Request for an Alternative to Reduce the Frequency of Updates to Its Inservice Testing and Inspection Programs ML20205L3712020-07-23023 July 2020 and R.E. Ginna Nuclear Power Plant Summary of Meeting ML20163A1722020-06-12012 June 2020 Summary of June 9, 2020, Pre-Submittal Meeting with Exelon Generation Company, LLC, Regarding Planned License Amendment Request to Modify Surveillance Requirement 3.6.1.3 ML19326C3582019-12-0303 December 2019 Summary of November 20, 2019, Meeting with Exelon Generation Company, LLC Regarding a Planned Request to Revise the Quality Assurance Program ML19326A3152019-12-0303 December 2019 Summary of November 18, 2019, Meeting with Exelon Generation Company, LLC Regarding a Planned Request for an Alternative to Supplemental Valve Position Indication Testing Requirements ML19302F8772019-11-0404 November 2019 Summary of the October 28, 2019, Meeting with Exelon Generation Company, LLC, Regarding a Planned Supplement to a License Amendment Request Regarding Revising the Allowable Value for Reactor Water Cleanup System Isolation ML19291A0022019-11-0101 November 2019 10/03-10/08/2019 Summary of Meetings with Exelon Generation Company, LLC, on Emergency Amendment Request Regarding One-Time Extension to Technical Specifications 3.8.1 Action A.3 Completion Time for Inoperable Offsite Source (EPID L-2019-LL ML19302D3152019-10-28028 October 2019 Annual Assessment Meeting for James A. Fitzpatrick Nuclear Power Plant and Nine Mile Point Nuclear Generating Station - Meeting Summary ML19176A0042019-07-15015 July 2019 Summary of Meeting with Exelon Generation Company, LLC, on a Planned License Amendment Request Regarding the Relaxation of Containment Differential Pressure Requirements ML19183A1282019-07-15015 July 2019 Summary of June 20, 2019, Meeting with Exelon Generation Company, LLC, on a Planned License Amendment Request Regarding Main Steam Isolation Valve Leak Rate Increase Utilizing ML19162A0272019-06-21021 June 2019 Summary of June 4, 2019, Meeting with Exelon Generation Company, LLC Regarding a Planned Request to Extend the Test Interval for Safety Relief Valves ML19036A8832019-02-0707 February 2019 Summary of Meeting with Exelon Generation Company, LLC Regarding a Planned Request to Use ASME Code Case N-879 ML18354B1712019-01-0202 January 2019 Summary of December 19, 2018, Meeting with Exelon Generation Company, LLC Regarding the Use of Boiling Water Reactor Vessel and Internals Project Guidelines ML18347B4932019-01-0202 January 2019 Summary of Pre-Application Meeting with Exelon Generation Co., LLC (Exelon) Forthcoming License Amendment Requests to Revise Technical Specification Requirements for Main Steam Isolation Valve Leak Rate Tests ML18325A1712018-11-28028 November 2018 Summary of Meeting with Exelon Generation Company, LLC Regarding Planned Fleet License Amendment Request to Revise Technical Specifications for High Radiation Areas ML18304A1662018-11-0606 November 2018 Summary of October 23, 2018, Teleconference with Exelon Generation Co., LLC to Discuss Potential License Amendment Request Ultimate Heat Sink Bar Rack Bar Heaters ML18297A1722018-10-26026 October 2018 Summary of Meeting with Exelon Generation Company, LLC Regarding Planned License Amendment Request to Adopt TSTF-427 ML18262A3662018-09-18018 September 2018 August 21, 2018, James A. Fitzpatrick Nuclear Power Plant (Fitzpatrick) and Nine Mile Point Nuclear Generating Station (Nine Mile Point) Summary of Public Meeting ML18163A2682018-06-19019 June 2018 Summary of June 5, 2018, Teleconference with Exelon Generation Company, LLC to Discuss Emergency Plan Changes at James A. Fitzpatrick Nuclear Power Plant and Nine Mile Point Nuclear Station ML18120A1772018-05-0101 May 2018 Summary of Meeting with Exelon Generation Company, LLC Regarding Draft Guidance for Emergency Response Organization Staffing ML18107A4972018-04-27027 April 2018 April 10, 2017, Summary of Public Meeting with Entergy Nuclear Operations, Inc. Regarding Upcoming License Amendment Request to Add Setpoint Verification Requirement to Technical Specification Surveillance Requirements ML17256A7482017-09-28028 September 2017 Summary of September 5, 2017, Meeting with Exelon Generation Co., LLC to Discuss Potential License Amendment Request Technical Specifications Task Force Traveler TSTF-542, Revision 2, for James A. Fitzpatrick Nuclear Power Plant ML17216A1732017-09-0707 September 2017 Notice of Meeting with Florida Power & Light Company and NextEra Energy to Discuss Closing Out Generic Safety Issue-191 and Generic Letter 2004-02 ML17144A2852017-06-0202 June 2017 Summary Teleconference with Exelon Generation Company, LLC, on Planned Submittals of License Amendment Requests to Change Emergency Action Levels Associated with Lake Ontario Water Level ML17143A3582017-05-23023 May 2017 Summary of Public Meeting for James A. Fitzpatrick and Nine Mile Point ML17143A1902017-05-23023 May 2017 Public Meeting Handouts and Sign in Sheet ML17031A2802017-02-0808 February 2017 Summary of Teleconference with Entergy Nuclear Operations, Inc. Regarding Verbal Authorization for Relief Request RR-21 for the James A. Fitzpatrick Nuclear Power Plant ML16229A4542016-08-16016 August 2016 Summary of Annual Assessment Meeting for James A. Fitzpatrick Nuclear Power Plant ML15197A3332015-07-24024 July 2015 June 29, 2015 Summary of Meeting with Beyond Nuclear, Et. Al., Regarding Its 10 CFR 2.206 Petition Requesting Enforcement Action Against the James A. FitzPatrick Nuclear Power Plant ML15120A0212015-04-28028 April 2015 April 23, 2015, Summary of Annual Assessment Meeting for James A. FitzPatrick Nuclear Power Plant on 4/23/2015 ML14197A5832014-09-18018 September 2014 Summary of the June 19, 2014, Category 1 Public Meeting with Entergy to Discuss Seismic Hazard Reevaluations Associated with Implementation of Japan Lessons-Learned Near-Tear Task Force Recommendation 2.1 ML14086A1532014-03-26026 March 2014 Summary of Annual Assessment Meeting for Nine Mile Point Nuclear Station and James A. FitzPatrick Nuclear Power Plant on 3/18/2014 ML13100A1172013-04-10010 April 2013 Summary of Public Meeting Regarding Nine Mile Point Nuclear Station and James A. Fitzpatrick Nuclear Power Plant ML13162A5812012-07-19019 July 2012 PRB Closed Meeting Notes - 07/19/12 Gunter Et Al. 2.206 Requesting Enforcement Action Against James A. Fitzpatrick Plant ML13162A5802012-05-29029 May 2012 PRB Closed Meeting Notes - 05/29/12 Gunter Et Al. 2.206 Requesting Enforcement Action Against James A. Fitzpatrick Plant ML12102A1752012-04-11011 April 2012 and James A. FitzPatrick Nuclear Power Plant - Summary of Public Meeting on March 22, 2012 ML13162A6282012-03-20020 March 2012 by Larry Doerflein: PRB Notes Attached-Dial-In Provided 2023-09-22
[Table view] Category:Memoranda
MONTHYEARML21277A2472021-11-0505 November 2021 Notification of Significant Licensing Action - Proposed Issuance of Order Approving the Transfer of Licenses for Which a Hearing Has Been Requested - Exelon Generation Company, LLC; Et. Al ML21285A1492021-10-22022 October 2021 Audit Plan in Support of Review of License Amendment Requests Regarding 50.69/TSFT-505 ML21056A5452021-03-30030 March 2021 Memorandum to File: Final Environmental Assessment and Finding of No Significant Impact for Initial and Updated Decommissioning Funding Plans for FitzPatrick ISFSI ML20038A2692020-02-11011 February 2020 Sensitive Unclassified Non-Safeguards Information Review of 2019 Final Safety Analysis Report Change Pages ML19099A2672019-04-16016 April 2019 Use of Encryption Software for Electronic Transmission of Safeguards Information ML17142A2382017-05-25025 May 2017 OEDO-17-00280 - Briefing Package for Drop-In Visit on June 9, 2017, by Senior Management of Exelon Generation Company, LLC with Chairman Svinicki, Commissioner Baran, and Commissioner Burns ML16336A4992017-01-18018 January 2017 Notice of Significant Licensing Action ML16088A2052016-03-28028 March 2016 Enclosure 1 - (72.30 DFP Reviews to Be Completed 2015) - Memo T Bowers from s Ruffin, Technial Assistance Requests - Review 2015 Tri-Annual Decommissioning Funding Plans for Multiple Independent Spent Fuel Storage Installations ML16088A2042016-03-28028 March 2016 Memo T Bowers from s Ruffin, Technical Assistance Requests - Review 2015 Tri-Annual Decommissioning Funding Plans for Multiple Independent Spent Fuel Storage Installations W/ Encl 2 (Template) ML15197A3272015-07-24024 July 2015 Audio Recording of June 29, 2015 Public Meeting with Paul Gunter Et. Al., Regarding Their 10 CFR 2.206 Petition Requesting Enforcement Action ML13309A0802013-12-11011 December 2013 Memorandum to File: Transcript for 10 CFR 2.206 Petition from Beyond Nuclear (Et Al) Regarding General Electric Mark I and Mark II Boiling-Water Reactors ML13108A3282013-04-22022 April 2013 Notice of Forthcoming Meeting with Petitioners Requesting Action Against Entergy Nuclear Operations, Inc., Regarding Operations at FitzPatrick, Pilgrim, and Vermont Yankee Nuclear Power Stations (TAC Nos. MF1092, MF1093, and MF1094) ML12290A2872012-11-0808 November 2012 Final Fitzpatrick Rotating Quadrants TIA Response ML13022A3542012-04-0505 April 2012 from Bhalchandra Vaida to George Wilson: G20120172/EDATS: OEDO-2012-0147 - Forthcoming Meeting with Petitioners, Beyond Nuclear Et Al, Requesting Action Under 10 CFR 2.206 ML12095A1712012-04-0505 April 2012 G20120172/EDATS-OEDO-2012-0147-ME8189-Meeting Notice-1st Meeting with Petitioners ML13017A3572012-04-0505 April 2012 from R1DRPMail Resource to Sam Mccarver: FW Fitzpatrick G20120172/EDATS ML11250A1712011-09-14014 September 2011 Notice of Forthcoming Meeting with Petitioner Requesting Action Under 10 CFR 2.206 Regarding Immediate Suspension of the Operating Licenses of General Electric (GE) Mark 1 Boiling Water Reactors (Bwrs) ML1115704052011-06-0606 June 2011 Notice of Meeting with Entergy Operations, Inc., to Discuss Implementation of Quality Oversight and Verification Programs at Entergy Sites Including Actions Being Taken to Enhance Effectiveness ML11126A0962011-05-12012 May 2011 Notice of Meeting with Petitioner Requesting Action Under 10CFR2.206 Regarding Immediate Suspension of Operating Licenses of General Electric Mark 1 Boiling Water Reactors ML1107504052011-03-21021 March 2011 Notice of Meeting with Entergy Operations, Inc., to Discuss Fleetwide Submittal for Proposed Technical Specification and Quality Assurance Program Manual Changes Related to Unit Staff Qualification Requirements ML0927301372009-10-0909 October 2009 Safety Evaluation by the Office of Nuclear Reactor Regulation Corporate Restructuring Conversion of Companies and Stock Split-Off by Entergy Nuclear Operations, Inc and Subsidiaries ML0917301322009-06-25025 June 2009 06/07-11/2009-Report on Trip to the Institute of Electrical and Electronics Engineers Stationary Battery Committee Meeting in Rohnert Park, CA ML0913405542009-05-14014 May 2009 Summary of Annual Assessment Open-House Public Meeting with Nine Mile Point and FitzPatrick ML0808000342008-03-24024 March 2008 Docketing of Slides Presentations to ACRS Full Committee Meeting Pertaining to License Renewal Application of the James A. Fitzpatrick Nuclear Power Plant ML0807400842008-03-14014 March 2008 Draft Regulatory Guide for Comment ML0806700322008-02-19019 February 2008 Status Report and Proposed Schedule for FitzPatrick License Renewal at Full Committee Meeting on March 6, 2008 ML0803601492008-02-14014 February 2008 Advisory Committee for Reactor Safeguards Review of the James A. FitzPatrick Nuclear Power Plant, License Renewal Application - Safety Evaluation Report ML0801402662008-02-0808 February 2008 Audit Q&A Database for FitzPatrick Nuclear Plant Aging Mgmt Programs, Aging Mgmt Reviews, and Time-Limited Aging Analyses - Audit Team'S Evaluation of the Applicant'S Responses ML0801505342008-01-24024 January 2008 01/11/2008 Summary of a Telephone Conference Call Between the NRC and Entergy Nuclear Operations, Inc., Concerning the 115kV AC Power Supply Connection Pertaining to the James A. FitzPatrick Nuclear Power Plant License Renewal Application ML0720000582007-07-26026 July 2007 7/18/07 Public Meeting Summary on the Reactor Oversight Process ML0717803562007-07-12012 July 2007 Summary of Telephone Conference Call Held on June 7, 2007, (FitzPatrick) ML0711504622007-05-0707 May 2007 Trip Report Summarizing March 27, 2007 Visit to James A. FitzPatrick Nuclear Power Plant Regarding the License Renewal Environmental Review ML0706702272007-03-15015 March 2007 Summary of Telephone Conference Calls Held on January 31, 2007 and February 13, 2007, Between the U.S. NRC and Entergy Nuclear Operations, Inc., Pertaining to the James A. Fitzpatrick Nuclear Power Plant, LRA ML0706702662007-03-14014 March 2007 Summary of Telephone Conference Call Held on March 5, 2007, Between the NRC and Entergy Nuclear Operations, Inc., Concerning Draft Request for Additional Information Pertaining to the James A. Fitzpatrick Nuclear Power Plant, LRA ML0634502502006-12-19019 December 2006 November 2006 Report on the Status of Public Petitions Under Title 10 of the Code of Federal Regulations, Section 2.206 ML0627801872006-10-23023 October 2006 Memorandum - Audit and Review Plan for Plant Aging Management Reviews and Programs, and Time-Limited Aging Analyses for the James A. Fitzpatrick Power Plant ML0626803552006-09-25025 September 2006 10/12/2006 Notice of Forthcoming Meeting to Discuss the License Renewal Process and Environmental Scoping for James A. Fitzpatrick Nuclear Power Plant, License Renewal Application Review ML0615806052006-06-0707 June 2006 06/26/2006 Forthcoming Pre-application Meeting with Entergy Nuclear Operations, Inc. on the License Renewal Application for James A. Fitzpatrick Nuclear Power Plant ML0600300802006-02-17017 February 2006 Transmittal of Final ASP Analyses (August 14, 2003 Grid Disturbance Events) ML0601201072006-01-27027 January 2006 Final Response to Task Interface Agreement 2005-10 Related to Operability Determination on Through-Wall Cracking of a Torus ML0506104872005-03-23023 March 2005 Draft Information Memo - May 1, 2005 Thru May 27, 2005 ML0433603982005-01-0404 January 2005 November 2004, Memo., from Brian W. Sheron, Nrr/Adpt to Luis A. Reyes, Nrc/Edo, Report on the Status of Public Petitions Under Title 10 of the Code of Federal Regulations, Section 2.206 ML0410507202004-03-31031 March 2004 Memo from D. Burch to File: RI-97-A-0126, Regarding FitzPatrick ML0405806902004-02-27027 February 2004 Transmittal of Preliminary ASP Analyses for Peer Review (August 14, 2003 Grid Event) ML0215803662002-06-0606 June 2002 Memo to R. Bellamy, RGN-I from: M. Tokar Subject: Region I Independent Spent Fuel Storage Installation Inspection Plans Attachment: Sfpo Comments to Region I Integrated Inspection Plans ML0207804562002-03-20020 March 2002 Memo, Draft Information for March 1 to March 15, 2002 ML0207704622002-03-20020 March 2002 Attachment Draft Information for March 1 to March 15, 2002 Requests for Additional Lnformation ML0200301552002-01-25025 January 2002 Memo to W.D. Beckner Closure of FitzPatrick Beyond Scope Issues (Bsis) BSI-F12 (Tac No. MB2710) NRC Generic Letter 1989-111989-06-30030 June 1989 NRC Generic Letter 1989-011: Resolution of Generic Issue 101 Boiling Water Reactor Water Level Redundancy 2021-03-30
[Table view] |
Text
January 24, 2008 LICENSEE: Entergy Nuclear Operations, Inc.
FACILITY: James A. FitzPatrick Nuclear Power Plant
SUBJECT:
SUMMARY
OF A TELEPHONE CONFERENCE CALL HELD ON JANUARY 11, 2008, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND ENTERGY NUCLEAR OPERATIONS, INC., CONCERNING THE 115KV AC POWER SUPPLY CONNECTION PERTAINING TO THE JAMES A.
FITZPATRICK NUCLEAR POWER PLANT LICENSE RENEWAL APPLICATION The U.S. Nuclear Regulatory Commission (NRC or the staff) and representatives of Entergy Nuclear Operations, Inc., held a telephone conference call on January 11, 2008, to discuss a concern regarding a cross-connect for the 115kV AC power supply sources and license renewal scoping for the James A. FitzPatrick Nuclear Power Plants license renewal application. provides a listing of the participants, and Enclosure 2 contains a brief description of the conference call.
The applicant had an opportunity to comment on this summary.
/RA/
N.B. (Tommy) Le, Sr. Project Manager Projects Branch 2 Division of License Renewal Office of Nuclear Reactor Regulation Docket No. 50-333
Enclosures:
As stated cc w/encls: See next page
ML080150534 OFFICE LA:DLR PM:RLRB:DLR BC:RLRB:DLR NAME IKing TLe RFranovich DATE 01/16/08 01/17/08 01/24/08
LIST OF PARTICIPANTS FROM THE TELEPHONE CONFERENCE CALLS JAMES A. FITZPATRICK NUCLEAR POWER PLANT LICENSE RENEWAL APPLICATION JANUARY 11, 2008 PARTICIPANTS AFFILIATIONS Tommy Le U.S. Nuclear Regulatory Commission (NRC)
Rani Franovich NRC Roy Mathew NRC Raj Auluck NRC Duc Nguyen NRC George Wilson NRC Sheila Ray NRC Rick Plasse Entergy Nuclear Operations, Inc. (ENO)
Mike Stroud ENO Dan Ruddy ENO Larry Leiter ENO Alan Cox ENO Enclosure 1
JAMES A. FITZPATRICK NUCLEAR POWER PLANT LICENSE RENEWAL APPLICATION (Brief description of the conference call)
The U.S. Nuclear Regulatory Commission (NRC or the staff) and representatives of Entergy Nuclear Operations, Inc. (Entergy), held a telephone conference call on January 11, 2008, to discuss a concern regarding the scoping of the station black-out (SBO) recovery paths, specifically, the offsite 115kV AC power supply sources, concerning the James A. FitzPatrick Nuclear Power Plants (JAFNPP) license renewal application (LRA).
Discussion: During the teleconference call, the staff requested the applicant to discuss the offsite 115kV AC power supply sources in regards to the scoping of the SBO recovery paths.
The NRC staff specifically asked if the disconnect switch 10017 is within the JAFNPP license renewal scoping.
The applicant indicated that based on the scoping and screening method used by Entergy, as described in the JAFNPP LRA, Section 2.5, the SBO recovery path would include in the review everything from the identified switchyard breakers (10022 and 10012) to the identified reserve transformers (T2 and T3) unless they are specifically stated as screened out.
The applicant stated that it understood the staffs specific question as to whether (1) the South 115kV bus and North 115kV bus cross-connect and (2) the normally closed electrically operated disconnect switch (10017) were included in the scope. The applicant stated that the cross-connect, which is part of the switchyard bus, and the electrically operated disconnect switch, both of which are located between the switchyard breakers 10022 and 10012 and the transformers T2 and T3, are in the scope of the JAFNPP license renewal. The applicant reiterated, during the conference phone call, that LRA Table 2.5-1 states that switchyard bus is subject to aging management review; and LRA Table 3.6.2-1 includes the commodity type Switchyard bus (switchyard bus for SBO), connections. And as such, no changes are required for the JAFNPP LRA Sections 2.5, 3.6 or Appendix B.
Enclosure 2
Letter to Entergy Nuclear Operations from Tommy Le, dated January 24, 2008 DISTRIBUTION:
SUBJECT:
SUMMARY
OF TELEPHONE CONFERENCE CALLS HELD ON JANUARY 11, 2008, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND ENTERGY NUCLEAR OPERATIONS, INC., CONCERNING THE 115KV AC POWER SUPPLY CONNECTION PERTAINING TO THE JAMES A.
FITZPATRICK NUCLEAR POWER PLANT LICENSE RENEWAL APPLICATION HARD COPY:
DLR RF E-MAIL:
PUBLIC SSmith (srs3)
SDuraiswamy RidsNrrDlr RidsNrrDlrRlra RidsNrrDlrRlrb RidsNrrDlrRlrc RidsNrrDlrReba RidsNrrDlrRebb RidsNrrDciCvib RidsNrrDciCpnb RidsNrrDraAfpb RidsNrrDeEmcb RidsNrrDeEeeb RidsNrrDssSrxb RidsNrrDssSbpb RidsNrrDssScvb RidsOgcMailCenter
GHunegs, SRI ECobey RLaufer JBoska
FitzPatrick Nuclear Power Plant cc:
Mr. Michael R. Kansler Mr. John A. Ventosa President & CEO / CNO GM, Engineering Entergy Nuclear Operations, Inc. Entergy Nuclear Operations, Inc.
1340 Echelon Parkway 440 Hamilton Avenue Jackson, MS 39213 White Plains, NY 10601 Mr. John T. Herron Mr. John F. McCann Sr. Vice President Director, Nuclear Safety & Licensing Entergy Nuclear Operations, Inc. Entergy Nuclear Operations, Inc.
1340 Echelon Parkway 440 Hamilton Avenue Jackson, MS 39213 White Plains, NY 10601 Sr. Vice President Ms. Charlene D. Faison Engineering & Technical Services Manager, Licensing Entergy Nuclear Operations, Inc. Entergy Nuclear Operations, Inc.
1340 Echelon Parkway 440 Hamilton Avenue Jackson, MS 39213 White Plains, NY 10601 Mr. Peter T. Dietrich Mr. Ernest J. Harkness Site Vice President Director, Oversight Entergy Nuclear Operations, Inc. Entergy Nuclear Operations, Inc.
James A. FitzPatrick Nuclear Power Plant 1340 Echelon Parkway P.O. Box 110 Jackson, MS 39213 Lycoming, NY 13093 Mr. Michael J. Colomb Mr. Kevin J. Mulligan Director of Oversight General Manager, Plant Operations Entergy Nuclear Operations, Inc.
Entergy Nuclear Operations, Inc. 440 Hamilton Avenue James A. FitzPatrick Nuclear Power Plant White Plains, NY 10601 P.O. Box 110 Lycoming, NY 13093 Director, Nuclear Safety Assurance Entergy Nuclear Operations, Inc.
Mr. Oscar Limpias James A. FitzPatrick Nuclear Power Plant Vice President Engineering P.O. Box 110 Entergy Nuclear Operations, Inc. Lycoming, NY 13093 1340 Echelon Parkway Jackson, MS 39213 Mr. James Costedio Manager, Licensing Mr. Joseph P. DeRoy Entergy Nuclear Operations, Inc.
Vice President, Operations Support James A. FitzPatrick Nuclear Power Plant Entergy Nuclear Operations, Inc. P.O. Box 110 1340 Echelon Parkway Lycoming, NY 13093 Jackson, MS 39213
FitzPatrick Nuclear Power Plant cc:
Mr. William C. Dennis Supervisor Assistant General Counsel Town of Scriba Entergy Nuclear Operations, Inc. Route 8, Box 382 440 Hamilton Avenue Oswego, NY 3126 White Plains, NY 10601 Mr. James H. Sniezek Regional Administrator, Region I BWR SRC Consultant U.S. Nuclear Regulatory Commission 5486 Nithsdale Drive 475 Allendale Road Salisbury, MD 21801-2490 King of Prussia, PA 19406 Mr. Michael D. Lyster Resident Inspectors Office BWR SRC Consultant James A. FitzPatrick Nuclear Power Plant 5931 Barclay Lane U.S. Nuclear Regulatory Commission Naples, FL 34110-7306 P.O. Box 136 Lycoming, NY 13093 Mr. John Doering BWR SRC Consultant Mr. Michael Balboni P.O. Box 189 Deputy Secretary for Public Safety Parker Ford, PA 19457 State Capitol, Room 229 Albany, NY 12224 Mr. Charles Donaldson, Esquire Assistant Attorney General New York Department of Law 120 Broadway New York, NY 10271 Mr. John P. Spath New York State Energy, Research, and Development Authority 17 Columbia Circle Albany, NY 12203-6399 Mr. Paul Eddy New York State Depart. of Public Service 3 Empire State Plaza Albany, NY 1223-1350 Oswego County Administrator Mr. Steven Lyman 46 East Bridge Street Oswego, NY 13126