MONTHYEARML19301A5042019-08-13013 August 2019 JAF-CALC-NBI-00206 Setpoint Calculation for Vessel Lo-Lo Lvl Primary Containment Isolation Function (02-3LT-58A,B and 02-3STU-259A,B) Project stage: Other JAFP-19-0083, License Amendment Request - Proposed Change to the Technical Specifications to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Isolation2019-09-0505 September 2019 License Amendment Request - Proposed Change to the Technical Specifications to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Isolation Project stage: Request ML19291A0352019-10-18018 October 2019 NRR E-mail Capture - FitzPatrick Supplemental Information Needed for Acceptance: Revise Allowable Value for Reactor Water Cleanup System Primary Containment Isolation Project stage: Other ML19302F8772019-11-0404 November 2019 Summary of the October 28, 2019, Meeting with Exelon Generation Company, LLC, Regarding a Planned Supplement to a License Amendment Request Regarding Revising the Allowable Value for Reactor Water Cleanup System Isolation Project stage: Meeting JAFP-19-0105, Response to Request for Supplemental Information to Revise the Allowable Value for Reactor Water Cleanup (RWCU)2019-11-0606 November 2019 Response to Request for Supplemental Information by the Office of Nuclear Reactor Regulation to Support Review of a License Amendment Request to Revise the Allowable Value for Reactor Water Cleanup (Rwcu). Project stage: Supplement ML19301A5022019-11-0707 November 2019 Draft Response to Request for Supplemental Information by the Office of Nuclear Reactor Regulation to Support Review of a License Amendment Request to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Is ML19319C3582019-11-15015 November 2019 NRR E-mail Capture - Accepted for Review - FitzPatrick License Amendment Request to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Isolation Project stage: Other ML20027A0112020-01-23023 January 2020 Request for Additional Information: License Amendment Request for Change to the Technical Specifications to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Isolation Project stage: RAI JAFP-20-0020, Response to Request for Additional Information to Support Review of a License Amendment Request to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Isolation2020-02-21021 February 2020 Response to Request for Additional Information to Support Review of a License Amendment Request to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Isolation Project stage: Response to RAI ML20066L3682020-03-0505 March 2020 Request for Additional Information: License Amendment Request for Change to the Technical Specifications to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Project stage: RAI JAFP-20-0026, Response to Request for Additional Information to Support Review of a License Amendment Request to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Isolation2020-03-31031 March 2020 Response to Request for Additional Information to Support Review of a License Amendment Request to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Isolation Project stage: Response to RAI JAFP-20-0064, Withdrawal of License Amendment Request to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Isolation2020-07-28028 July 2020 Withdrawal of License Amendment Request to Revise the Allowable Value for Reactor Water Cleanup (RWCU) System Primary Containment Isolation Project stage: Withdrawal ML20216A3742020-08-0505 August 2020 Letter with Withdrawal of an Amendment Request Project stage: Withdrawal 2019-09-05
[Table View] |
Text
November 4, 2019 LICENSEE:
Exelon Generation Company, LLC FACILITY:
James A. FitzPatrick Nuclear Power Plant
SUBJECT:
SUMMARY
OF THE OCTOBER 28, 2019, MEETING WITH EXELON GENERATION COMPANY, LLC, REGARDING A PLANNED SUPPLEMENT TO A LICENSE AMENDMENT REQUEST REGARDING REVISING THE ALLOWABLE VALUE FOR REACTOR WATER CLEANUP SYSTEM ISOLATION (EPID L-2019-LLA-0190)
On October 28, 2019, a Category 1 public meeting was held between the U.S. Nuclear Regulatory Commission (NRC) and representatives of Exelon Generation Company, LLC (Exelon, the licensee) at NRC Headquarters, One White Flint North, 11555 Rockville Pike, Rockville, Maryland. A telephone bridge line was available for remote participants. The purpose of the meeting was to discuss the licensees plan to submit a supplement to a license amendment request regarding revising the allowable value for the reactor water cleanup system isolation for the James A. FitzPatrick Nuclear Power Plant (FitzPatrick). The meeting notice and agenda, dated October 17, 2019, are available in the Agencywide Documents Access and Management System (ADAMS) under Accession No. ML19290G550. A list of attendees is provided as an enclosure.
The licensee presented information of its plans to submit a supplement in response to a request from the NRC staff regarding information needed to begin the staffs detailed review (ADAMS Accession No. ML19291A035). The license amendment request was dated September 5, 2019 (ADAMS Accession No. ML19248B085). The licensee provided a draft supplement (ADAMS Accession No. ML19301A502) and supporting information (ADAMS Accession Nos.
ML19301A505, ML19301A504, and ML19301C555) to facilitate the discussion at the public meeting.
The NRC staff discussed the information needed to begin its detailed review. The licensee agreed to: (1) include information indicating that an operator would have procedures in hand during normal or plant transient conditions in response to the NRC staffs question 3.a, (2) enclose FitzPatrick plant procedure CC-JAF-IC-G-003 after verifying that it would address the NRC staffs question 2, and (3) provide the past license amendment that approved the licensees methodology in response to staff question 2.
Members of the public were not in attendance. Public Meeting Feedback forms were not received.
Please direct any inquiries to me at 301-415-3168, or via email at Samson.Lee@nrc.gov.
/RA/
Samson S. Lee, Project Manager Plant Licensing Branch LPL1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-333
Enclosure:
List of Attendees cc: Listserv
Enclosure LIST OF ATTENDEES OCTOBER 28, 2019, MEETING WITH EXELON GENERATION COMPANY, LLC PLANNED SUPPLEMENT TO LICENSE AMENDMENT REQUEST REGARDING REVISING THE ALLOWABLE VALUE FOR REACTOR WATER CLEANUP SYSTEM ISOLATION NRC Participants Jerome Bettle James Danna Victoria Huckabay Samson Lee David Nold David Rahn Gursharan Singh Tarico Sweat Exelon Participants Mark Hawes Jason Ritzel Christian Williams Anthony Yost
ML19302F877 OFFICE NRR/DORL/LPL1/PM NRR/DORL/LPL1/LA NRR/DORL/LPL1/BC NRR/DORL/LPL1/PM NAME SLee CSmith JDanna SLee DATE 11/4/2019 11/4/2019 11/4/2019 11/4/2019