(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
|
---|
Category:NPDES NONCOMPLIANCE NOTIFICATION
MONTHYEARML20043J1001990-05-25025 May 1990 NPDES Nonccompliance Notification:On 900329,discharge of 30-40 Gallons of Fuel Oil Into Storm Sewer Drain Occurred & Release of 25 Gallons Fuel Oil Into Discharge Canal Occurred on 900510.Spill Prevention Control Plan Encl.W/O Encl ML20247G9191989-09-14014 September 1989 NPDES Noncompliance Notification:On 890907,bypass of Onsite Sewage Plant Resulted in Discharge of Not More than 1,000 Gallons of Untreated Sewage.Caused by Crack in Sewage Line. Domestic Water Secured & Sewage Pipe Repaired ML20245H4811989-08-0707 August 1989 NPDES Noncompliance Notification:On 890626,11 Gallons of Houghto-Safe 620 Hydraulic Fluid Spilled in Subpile Room of Unit During Preparation for CRD Removal Work.Major Portion of Spill Collected in Dry Well Sumps & Floor Flushed ML20247P8831989-05-26026 May 1989 NPDES Noncompliance Notification:Biological Oxygen Demand of Sample from Disharge Point 501 Exceeded Monthly Average Permit Limit.Caused by Increase in Sewage Treatment Plant Loading.Sampling Frequency Increased & Trench Backfilled ML20246N6891989-05-0202 May 1989 NPDES Noncompliance Notification Re Bod of Sample Taken from Discharge Point 501 Exceeding Monthly Average Permit Limit. Caused by Increase in Sewage Treatment Plant Loading Due to Increase in Power Plant Outage Work Force ML20235V8771989-02-27027 February 1989 NPDES Noncompliance Notification:On 890127,sample Taken from Storm Drain 101 Exceeded Oil & Grease Monthly Limit.Oil Absorbent Matl Placed at Discharge of Storm Drain Inside Oil Retaining Boom ML20206M1641988-11-22022 November 1988 NPDES Noncompliance Notification:On 881017,pH Samples from Discharge Point 301 Exceeded Monthly Permit Limit.Caused by Leakage of Sump Discharge Valves.Action Taken to Neutralize Settling Basin W/Addition of Acid ML20155D1061988-09-22022 September 1988 NPDES Noncompliance Notification:On 880829,wet Well in Front of Unit 1 Administration Bldg Overflowed.Caused by Lack of Pumping Wet Well as Scheduled.Restrooms Secured in Temporary Trailers & Parking Access Blocked ML20196K6841988-06-22022 June 1988 NPDES Noncompliance Notification:On 880501,pH of Settling Basin Discharge Point Exceeded Permit Limit.Cause Unknown. Discharge to River Stopped & Soda Ash Added to Neutralize Settling Basin ML20245D4211988-05-25025 May 1988 NPDES Noncompliance Notification:On 880406,total Phosphorus Sample Exceeded Monthly Average.Caused by High Solids Carryover from Clarifers & Lower than Normal Phs.Alum to Sewage Plant Equalization Basin Increased ML20154P4851988-05-25025 May 1988 NPDES Noncompliance Notification:On 880406,BOD of Sample from Discharge Point 501 Exceeded Monthly Average & Instantaneous Max Limits.Caused by High Solids Carryover Through Sewage Plant.Wet Well Pumps Repaired & Cleaned ML20154P4771988-05-25025 May 1988 NPDES Noncompliance Notification:On 880414,pH of Sample from Discharge Point 301 Exceeded Monthly Permit Limit.Caused by Release of Neutralizing Tank a W/O Continuous Ph Indication &/Or Trip Protection.Settling Basin Isolated & Neutralized ML20154P4271988-05-25025 May 1988 NPDES Noncompliance Notification:On 880406,suspended Solids from Discharge Point 501 Exceeded Max Permit Limit.Caused by High Solids Carryover Through Sewage Plant Resulting from Wet Well Pumps Tripping on Thermals.Pumps Repaired/Cleaned ML20147B6431988-02-23023 February 1988 NPDES Noncompliance Notification:On 880106-28 Samples from Discharge Point 501 Sewage Treatment Plant Exceeded Monthly Average & Instantaneous Max Limits.Cause Unknown.Program of Wasting Will Be Implemented to Reduce Solids ML20147B4301988-02-23023 February 1988 NPDES Noncompliance Notification:Total Phosphorus of Samples Taken from Discharge Point 501 Exceeded Monthly Average & Max Permit Limit.Caused by Inability of Sewage Treatment Plant to Continously Reduce Phosporus Level ML20236J1741987-10-28028 October 1987 NPDES Noncompliance Notification:On 870911 & 24,biochemical Oxygen Demand of Two Samples from Discharge Point 501 Exceeded Monthly Average Permit Limit.Caused by Excessive Carryover from Clarifiers.Solids Passed Through Sys Reduced ML20236J1441987-10-28028 October 1987 NPDES Noncompliance Notification:On 870911 & 24,total Phosphorus of Samples for Discharge Point 501 Exceeded Monthly Average Permit Limit.Caused by Sewage Treatment Plant Inability to Reduce Phosphorus Below Permit Limit ML20237H5481987-08-31031 August 1987 NPDES Noncompliance Notification:On 870701 Oil Spill Occurred.Caused by Personnel Error Associated W/Failure to Pump Down Full Dirty Oil Storage Tank.Individuals Involved Counseled & Supervisory Attention Increased ML20214S3581987-05-28028 May 1987 NPDES Noncompliance Notification:Monthly Average Total Phosphorus of Discharge Point 501 Exceeded Monthly Average Permit Limit.Caused by Sewage Treatment Plant Not Able to Reduce Phosphorus Below Permit Limit.Mods Underway ML20214S3191987-05-28028 May 1987 NPDES Noncompliance Notification:On 870413,suspended Solids of Sample from Discharge Point Exceeded Instantaneous Max Permit Limit.Caused by High Suspended Solids in Aeration Tank.Wasting of Sludge Increased to Reduce Solids Level ML20214B4691987-04-30030 April 1987 NPDES Noncompliance Notification:Thermal Discharge from Discharge Point 001 Cooling Towers Exceeded Permit Requirements.Caused by Erroneous Recorded Measurements & Permit Requirements.Malfunctioning Monitors Repaired ML20205B9541987-03-17017 March 1987 NPDES Noncompliance Notification:During Jan 1987,two Samples from Discharge Point 501 Exceeded Monthly Average & Instantaneous Max Permit Limits.Caused by High Settleable Solids in Aeration Tank.Program of Wasting Solids Begun ML20205B8671987-03-17017 March 1987 NPDES Noncompliance Notification:During Jan 1987,total Phosphorus Samples from Discharge Point 501 Exceeded Limit. Caused by Sewerage Treatment Plant Not Being Able to Reduce Phosphorus Below Limit.Feed Rate of Ultrion Increased ML20205B8481987-03-17017 March 1987 NPDES Noncompliance Notification:During Feb 1987,total Phosphorus Samples from Discharge Point 501 Exceeded Limit. Caused by Sewerage Treatment Plant Not Being Able to Reduce Phosphorus Below Limit.Feed Rate of Ultrion Increased ML20214T7791986-11-13013 November 1986 NPDES Noncompliance Notification:On 861024,pH Sample from Discharge Point 301 Exceeded Permit Limit.Caused by out-of- Svc Neutralizing Tank Ph Meter & Ph Meter for Raw Water Sump Which Drifted Out of Calibr.Raw Water Sump Ph Meter Calibr ML20215N2051986-10-24024 October 1986 NPDES Noncompliance Notification:On 860930,oil & Grease of Sample from Settling Basin Exceeded Monthly Average Permit Limit.Cause Unknown.Analysis Not Received in Time to Allow Resample to Bring Average Value Into Compliance ML20215N2181986-10-23023 October 1986 NPDES Noncompliance Notification:On 860902,pH of Sample from Wastewater Settling Basin Exceeded Permit Limit.Caused by out-of-svc Neutralizing Tank Ph Meter & out-of-calibr Ph Meter for Raw Water Pump ML20215M8821986-10-17017 October 1986 NPDES Noncompliance Notification:Phosphorus Level Exceeded Monthly Average Permit Limit for Sept 1986.Caused by Sewage Treatment Plant.Feed Rate Increased Incrementally While Phosphorus Levels Monitored ML20210P5591986-09-29029 September 1986 NPDES Noncompliance Notification:On 860806,pH of Sample from Discharge Point 301 (Waste Water Settling Basin) Exceeded Limits.Caused by Acid Inadvertently Entering Raw Pump Through Open Drain Valve.Liquid Added to Lower Ph Limit ML20206K0441986-06-23023 June 1986 Noncompliance Notification:On 860507,total Phosphorous Sample from Discharge Point 501 Exceeded Permit Limits for Instantaneous Max.Caused by Sewage Treatment Plant Incapable of Reducing Phosphorous.Flow Element Installed ML20198N6001986-05-22022 May 1986 NPDES Noncompliance Notification:On 860402,biological Oxygen Demand of Samples from Discharge Point 501 Exceeded Permit Limits.Cause Unknown.Waste Sludge Tank Pumped to Prevent Recirculation of Ultrion 8155 During Decant ML20210E5531986-03-15015 March 1986 NPDES Noncompliance Notification:On 860205 & 26,samples of Discharge Point 501 Exceeded Monthly Average Biological Oxygen Demand.Caused by Degradation of Biological Activity Associated W/Nalco & Ultrion 8155 Addition Sys ML20210E1361986-03-15015 March 1986 NPDES Noncompliance Notification:On 860205,sample from Discharge Point 501 Exceeded Permit Limit for Instantaneous Max.Caused by Sewage Treatment Plant Unable to Reduce Phosphorous to Below Permit Level ML20210E5631986-03-14014 March 1986 NPDES Noncompliance Notification:On 860225 & 0304,pH Limit of Samples from Discharge Point 401 (Auxiliary Boiler Blowdown) Exceeded Permit Limit.Caused by High Blowdown Rate of Auxiliary Boilers.Blowdown Rates Will Be Reduced ML20210E2691986-03-14014 March 1986 NPDES Noncompliance Notification:On 860210,pH of Sample from Discharge Point 301 Exceeded Limit.Caused by Placing Raw Water Sump Ph Meter in Standby Allowing High Ph Water Into Setting Basin.Mod to Ph Monitor Planned ML20154J5081986-02-10010 February 1986 NPDES Noncompliance Notification:On 860108,phosphorus from Discharge Point 501 (Sewage Treatment Plant) Exceeded Permit Limit.Caused by Inability of Plant to Reduce Phosphorus Level.Aluminum Chloride Coagulant Treatment Sys Installed ML20210E2571986-02-10010 February 1986 NPDES Noncompliance Notification:On 860203,pH Sample from Discharge Point 301 (Wastewater Settling Basin) Exceeded Permit Limit.Caused by Effluent Ph Monitors Out of Calibr. Neutralization Tank & Raw Water Ph Meters Recalibr ML20136G3831985-12-30030 December 1985 NPDES Noncompliance Notification:On 851117,pH of Discharge Point Sample Exceeded Permit Limit.Caused by non-neutral Overflow from Neutralizing Tank.Acid Added to Settling Basin & Personnel Training Planned ML20136G5411985-12-30030 December 1985 NPDES Noncompliance Notification:On 851127,pH of Sample Taken from Discharge Point 301 in Wastewater Setting Basin Exceeded Permit Level.Cause Unknown.No Unusual Entries Noted in Operator Log ML20136G5631985-12-27027 December 1985 NPDES Noncompliance Notification:On 851107,pH of Sample from Wastewater Settling Basin,Discharge Point 301 Found Above Limit.Cause Unknown.On 851108,pH Measured 8.6. Corrective Action Unnecessary ML20136G6491985-12-27027 December 1985 NPDES Noncompliance Notification:On 851104,06,11,20 & 26, Total Phosphorous of Samples Taken from Sewage Treatment Plant Discharge Point 501 Exceeded Permit Limit.Corrective Actions:Use of Phosphorous Cleaning Products Minimized ML20137X8661985-11-26026 November 1985 NPDES Noncompliance Notification:On 851002,03,07,09,12,13, 14,15,16,17,19 & 26,pH of Samples from Discharge Point 301 Exceeded Permit Limit.Caused by Failure to Inform Operators of New Requirement.Operators Informed of New Requirement ML20137X9171985-11-26026 November 1985 NPDES Noncompliance Notification:On 851006,09,16 & 22,total Phosphorus of Samples from Discharge Point 501 Exceeded 4.0 mg/1 Limit.Cause Unknown.Investigation Into Cleaning Substances & Other Possible Sources Initiated on 851113 ML20127E4011985-05-21021 May 1985 NPDES Noncompliance Notification:On 850510,biological Oxygen Demand of Sample from Discharge Point 108 Exceeded Permit Limit.Cause Under Investigation.Operational Controls & Monitoring Increased ML20127M6571985-05-0303 May 1985 NPDES Noncompliance Rept:On 850418,biological Oxygen Demand of Sample from Discharge Point 108 in Sewage Treatment Plant Exceeded Permit Limit.Caused by Pin Floc Carryover from Clarifier.Pressure Filters Utilized ML20116H6901985-04-22022 April 1985 NPDES Noncompliance Notification:On 850410,total Suspended Solids of Sample from Discharge Point 108 Exceeded Permit Limit.Caused by Clogging of Sludge Return Pump A.Lines Blown Back & Valves Lined Up ML20112F7281985-01-0202 January 1985 NPDES Noncompliance Notification:Biological Oxygen Demand of 841204 Sample Taken from Discharge Point 108 Exceeded Instantaneous Max Permit Limit.Caused by Low Flow Condition Due to Malfunction of Filter Feedpumps.Pump Repaired 1990-05-25
[Table view] Category:TEXT-ENVIRONMENTAL REPORTS
MONTHYEARML20210T5591999-08-12012 August 1999 Environ Assessment & Finding of No Significant Impact Re 990202 Application for Amends to Plant,Units 1 & 2.Proposed Action Would Correct Existing Editorial & Typographical Errors in TSs ML20195B6241998-12-31031 December 1998 PBAPS Units 2 & 3 Annual Radiological Environ Operating Rept 56 for 980101-1231 ML20206E0351998-12-31031 December 1998 PBAPS Units 2 & 3 Radiation Dose Assessment Rept 14 for 1998. with ML20206C5631998-12-31031 December 1998 Radioactive Effluent Release Rept 41 for Jan-Dec 1998 for Pbaps,Units 1 & 2 ML20249A7781998-06-15015 June 1998 Environ Assessment & Finding of No Significant Impact. Proposed Action Would Exempt Licensee from Requirement of 10CFR70.24(a) ML20217H5791997-12-31031 December 1997 Radiation Dose Assessment Rept Number 13 Jan-Dec 1997 ML20217M7971997-12-31031 December 1997 Radioactive Effluent Release Rept 40,970101-1231, for Peach Bottom Atomic Power Station Units 1 & 2 ML20248E1801997-12-31031 December 1997 PBAPS Annual Radiological Environ Operating Rept,Rept 55 for Jan-Dec 1997 ML20197G3991997-12-0202 December 1997 Environ Assessment & Finding of No Significant Impact Re Indirect Transfer of Control of Interests in Units 2 & 3, Licenses to Extent Affected by Proposed Merger of Alantic Energy,Inc & Delmarva Power & Light Co ML20138A9931996-12-31031 December 1996 Annual Effluent Release Rept Number 39,for 960101-1231 ML20138C8201996-12-31031 December 1996 PBAPS Units 2 & 3 Radiation Dose Assessment Rept 12 for Period Jan-Dec 1996 ML20141C7391996-12-31031 December 1996 PBAPS Units 2 & 3 Annual Radiological Environ Operating Rept,Rept 54 Jan-Dec 1996 ML20112B6061995-12-31031 December 1995 PBAPS Units 2 & 3 Annual Radiological Environ Operating Rept 53,Jan-Dec 1995 ML20107L9201995-12-31031 December 1995 Annual Effluent Release Rept No 38 Jan-Dec 1995 ML20107M2521995-12-31031 December 1995 PBAPS Units 2 & 3 Radiation Dose Assessment Rept 11 for Jan-Dec 1995 ML20082P9991994-12-31031 December 1994 Annual Effluent Release Rept 37 Jan-Dec 1994 ML20082M6551994-12-31031 December 1994 PBAPS Units 2 & 3 Radiation Dose Assessment Rept 10 for Jan-Dec 1994 ML20084A0411994-12-31031 December 1994 PBAPS Units 2 & 3 Annual Radiological Environ Operating Rept, Rept 52 for Period of 940101-1231 ML20029C7651993-12-31031 December 1993 Radiation Dose Assessment Rept 9 for 1993. ML20076K7801993-12-31031 December 1993 Corrected Copies of Semi-Annual Effluent Release Rept 36 Jul-Dec 1993, for PBAPS Units 2 & 3 ML20064H8801993-12-31031 December 1993 Revised Occupational Exposure Rept for 1993 ML20067D2611993-12-31031 December 1993 Semiannual Effluent Release Rept 36 Jul-Dec 1993 ML20063K2881993-12-31031 December 1993 PBAPS 1993 Occupational Exposure Tabulation 18 ML20056G0921993-06-30030 June 1993 Semiannual Effluent Release Rept 35 for Jan-June 1993 for Pbaps,Units 2 & 3 ML20044E3811992-12-31031 December 1992 Annual Radiological Environ Operating Rept,Rept 50 for Jan-Dec 1992. ML20114B5291992-06-30030 June 1992 Semiannual Effluent Release Rept 33,Jan-June 1992,Peach Bottom Atomic Power Station,Units 2 & 3 ML20095J8231991-12-31031 December 1991 Radiation Dose Assessment Rept,1991 ML20096G6911991-12-31031 December 1991 Annual Radiological Environ Operating Rept,Rept 49, for 1991 ML20094G7731991-12-31031 December 1991 Semi-Annual Effluent Release Rept for Jul-Dec 1991 ML20115A6251991-12-31031 December 1991 Revised 1991 Recorded Annual Whole Body Exposure Rept, Consisting of Listing of Std Format for Reporting Number of Personnel & man-rem by Work & Job Function for 1991 & Number of Individuals in Each Range ML20090B4321991-12-31031 December 1991 Standard Format for Reporting Number of Personnel & Man-Rem by Work & Job Function for the Period Jan-Dec 1991 ML20082L8751991-06-30030 June 1991 Semiannual Effluent Release Rept,Jan-June 1991 ML20115A6351990-12-31031 December 1990 Revised 1990 Occupational Exposure Rept, Consisting of Listing of Recorded Annual Whole Body Exposures ML20073Q7051990-12-31031 December 1990 Annual Radiological Environ Operating Rept 48,1990 ML20073H3461990-12-31031 December 1990 Radiation Dose Assessment Rept, 1990 ML20082M0181990-12-31031 December 1990 Corrected Solid Radwaste Portion of Semiannual Effluent Release Rept for Jul-Dec 1990 ML20029B0801990-12-31031 December 1990 Exposure Rept. W/910227 Ltr ML20090B4441990-12-31031 December 1990 Revised Annual Whole Body Exposure for 1990 ML20029B0791990-12-31031 December 1990 Semiannual Effluent Release Rept 30,Jul-Dec 1990. W/910227 Ltr ML20028G8201990-06-30030 June 1990 Peach Bootom Atomic Power Station Semiannual Effluent Release Rept,Jan-June 1990. ML20043J1001990-05-25025 May 1990 NPDES Nonccompliance Notification:On 900329,discharge of 30-40 Gallons of Fuel Oil Into Storm Sewer Drain Occurred & Release of 25 Gallons Fuel Oil Into Discharge Canal Occurred on 900510.Spill Prevention Control Plan Encl.W/O Encl ML20090B4561989-12-31031 December 1989 Revised Annual Whole Body Exposure for 1989 ML20043B6441989-12-31031 December 1989 1989 Annual Radiological Environ Operating Rept 47. W/ 900524 Ltr ML20115A6391989-12-31031 December 1989 Revised 1989 Occupational Exposure Rept, Consisting of Listing of Recorded Annual Whole Body Exposure ML20012C2541989-12-31031 December 1989 Recorded Annual Whole Body Exposure for Period Jan-Dec 1989. W/900309 Ltr ML20012C6181989-12-31031 December 1989 Semiannual Effluent Release Rept 28,Jul-Dec 1989. W/900228 Ltr ML20247G9191989-09-14014 September 1989 NPDES Noncompliance Notification:On 890907,bypass of Onsite Sewage Plant Resulted in Discharge of Not More than 1,000 Gallons of Untreated Sewage.Caused by Crack in Sewage Line. Domestic Water Secured & Sewage Pipe Repaired ML20245H4811989-08-0707 August 1989 NPDES Noncompliance Notification:On 890626,11 Gallons of Houghto-Safe 620 Hydraulic Fluid Spilled in Subpile Room of Unit During Preparation for CRD Removal Work.Major Portion of Spill Collected in Dry Well Sumps & Floor Flushed ML20246J9431989-06-30030 June 1989 Semiannual Effluent Releases Rept 27 for Jan-June 1989 ML20247M0291989-06-30030 June 1989 Rev 1 to Semiannual Effluent Releases Rept,Jan-June 1989 1999-08-12
[Table view] |
Text
..
PHILADELPHIA ELECTRIC COMPANY 2850596570 2301 MARKET STREET P.O. BOX 8699 PHILADELPHIA. PA.19101 (215)8414000 t
May 3, 1985
' Department.of-Environmental Resources Bureau of Water Quality Management-One Ararat Blvd.
Harrisburg, PA' 17110 Gentlemen:-
SUBJECT:
Noncompliance with NPDES Permit Peach Bottom Atomic Power Station Permit'No. PA 0009733 DESCRIPTION OF NONCOMPLIANCE:
The biological oxygen demand (BOD) of a sample from discharge point 108 (Sewage Treatment Plant) exceeded the permit limit.
Date Sample Taken: 4-18-85 Date Results Received: 4-29-85 Results of Analysis: 130 mg/l Permit Limitation: 45 mg/l CAUSE-OF NONCOMPLIANCE:
The cause of the noncompliance is believed to be pin floc carryover'from the clarifier. It is unknown what is causing the pin floc. carryover.
DURATION OF NONCOMPLIANCE:
U The duration of the noncompliance is unknown since this is a continuation of the April 4, 1985 exceedance which was previously reported. ,
5505230326 850503 a PDR ADOCK 05000277 PDR
[J S
'O
- ~ . -
.e , e.w - - ,, , , - . , , n .- - . -, , --. - - . - , - .,,
~& ~~ ~
' CORRECTIVE ACTION:
2850596570
~The Sewage Treatment Plant pressure filters were returned to service on April 19, 1985. It is believed that the effluent was within permit limits upon utilization of the pressure filters. The final effluent was resampled for BOD on April 25, 1985. The result of this sample'was 10 mg/1. The result of a sample for BOD on the equalization basin'on April 19 was 288 mg/1 and the result of a BOD sample of unchlorinated effluent was 31 mg/1. This represents a 89 percent decrease in. BOD by the sewage treatment plant. ,
r PREVENTION OF FUTURE OCCURRENCES:
Although the pressure filters have brought the effluent into compliance, we are continuing our efforts to correct the pin floc carrover from the clarifier. . Increased surveillance and sampling is being maintained to help determine and reduce the cause of the carryover.
Very truly yours, W. T. Ullrich Superintendent Nuclear Generation Division JAV/NTUtala cc s; Environmental Protection Agency
' Water Permits Branch Pennsylvania Section 3WM52 841 Chestnut Building
, Philadelphia, Pennsylvania 19107 Director /
Office of Nuclear-Reactor Regulation,/~f US Nuclear Regulatory Commisssion f Washington, DC 20555 Administrator Region I
(- Office of Inspection and Enforcement (
- US Nuclear Regulatory Commission 631 Park Avenue
,' ._ King of Prussia, Pennsylvania 19406 i
. . --