ML20154P427

From kanterella
Jump to navigation Jump to search
NPDES Noncompliance Notification:On 880406,suspended Solids from Discharge Point 501 Exceeded Max Permit Limit.Caused by High Solids Carryover Through Sewage Plant Resulting from Wet Well Pumps Tripping on Thermals.Pumps Repaired/Cleaned
ML20154P427
Person / Time
Site: Peach Bottom  Constellation icon.png
Issue date: 05/25/1988
From: Danni Smith
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
PENNSYLVANIA, COMMONWEALTH OF
References
NUDOCS 8806030334
Download: ML20154P427 (2)


Text

p-ee -

n-s,<s.

.m

- ?,

l' PHILADELPHIA ELECTRIC COMPANY '

PEACH BOTTOM ATOMIC POWER STATION k D.1 Box 208 Delta, Pennsyhula 17314

- re.cs wrm-rna rov sa or tuttttscs (717) 4$6 7014 D. M. Smith Vice PreWderit May 25, 1988 i

Department of Environmental Resources Bureau of Water Quality Management One Ararat Blvd.

Harrisburg, PA 17110

SUBJECT:

Noncompliance with NPUES Permit Peach Bottom Atomic Power Station Permit No.

PA 0009733 Gentlemen:

DESCRIPTIONOFNONCOMPLIANC[:

Tht saspended solids of d sample from discharge point 501 (Sewage Treatment Plant) exceeded the instantaneous maximum permit limit.

Date Sample Taken 4/6/88 Date Results Received:

4/7/88 Results of Analysis:

69.2 mg/l Permit Limitation:

30 mg/l Avg.

CAUSE OF__ NONCOMPLIANCE:

j The cause of the noncompliance was high solids carryover through the sewage plant. This was caused by #1 and #2 wet well pumps tripping on thermals due to clogging with debris. When the pumps were cleared, the high flows caused high carryover, and hydraulically overloading the clarifiers.

00RA110N OF NONCOMPLIANCE:

The estimated duration of the noncompliance was twelve hours.

l l

l W

s I

l 8806030334 880525

\\

PDR ADOCK 05000277 iO S

DCD

- w -..

-m g

CORRECTIVE ACTION:

The wet well pumps were repaired / cleaned on April 6, 1988.

Very truly yours, JAV:ala cc: Environmental Protection Agency Water Permits Branch Pennsylvania Section 3WM52 841 Chestnut Building Philadelphia, Pennsylvania 19107

-Director Office of Nuclear Reactor Regulation US Nuclear Regulatory Commission Washington, DC 20555 Administrator Region i Office of Inspection and Enforcement US Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406 I