.t g;

1

'PHIL ELPHIA ELF.C1'RIC COMPANY -

PEACH BOT 10M ATO.I.(IC POWER STATION R. D 1, Acx 208 Deka, Pennsylvania 173!4

,s mc Mw.mafo.se o, axcausix (71?) 4 $6 7014 D. M. Smith

/

Vice President May 25, 1988 I

Department of Environmental Resources Bureau of Water Quality Management One Ararat Blvd.

Harrisburg, PA 17110

SUBJECT:

Noncompliance with NPDES Permit Peach Bottom Atomic Power Station Permit No.

PA 0009733 Gentlemen:

DESCRIPT_ ION OF NONCOMPLIANCE:

The B00 of a sample from discharge point 501 (Sewage Trettnent Plant) exceeded the monthly aver 6ge and instantaneous. maximum limits.

Date Sample Taken:

4/6/88 4/13/88 4/20/88 Date Results Received:

5/12/88 4/26/88 5/8/88 Results of Analysis 150 mg/l 7 mg/l 22 mg/l Monthly Avg.

59.7 Permit Limitation:

30 mg/l Monthly Average 60 mg/l Instantaneous Maximum CAUSE Or NONCOMPLIANCE:

The cause of the noncompliance was high solids carryover through the sewage plant.

This was caused by the #1 and #2 wet we'll pumps returning to service on April 6, 1988 after tripping on thermals due to clogging with debris.

DURATION OF NONCOMPLIANCE _:

The estimated duration of the noncompliance was twelve hours, i

i JgpSB8Bi2ggggm

.s nc.n N

j';

. t..

G,,

,p, a

CORRECTIVE ACTION:

The il and #2 wet well pumps were repaired / cleaned on' April 6, 1988.

)

)

\\

Ver$trulyyours, JAV/ala g

cc: Eruironmental Proteck, ion Agency Wzter Permits Branch Pannsylvania section 3WM52 641 Chestnut Building Philadelphia, Pennsylvania 19107 Director Aoininistrator OhRR Re.gion I US NRC 09fice of Inspection and Enforcement j Washington, DC 20555 US Nuclear Regulatory Commission 631 Park Avenue

' fMh,g of Prussia, Pennsylvania 19406 J

s 3

t I

r"

/

L p.

A