.r.-.,
, i u
WV PHILADELPHIA ELECTRIC COMPANY-2301 MARKET STREET P.O. BOX 8699 PHILADELPHI A. PA.19101 (215)841 4000 October 24, 1986 Department of Environmental Resources Bureau of Water Quality Management One Ararat Blvd.
Harrisburg, PA 17110
SUBJECT:
Noncompliance with NPDES Permit Peach Bottom Atomic Power-Station Permit No.
PA 0009733 Gentlemen:
DESCRIPTION OF NONCOMPLIANCE:
The oil and grease of a sample from discharge point 301 (Settling Basin) exceeded the monthly average permit limit.
l
\\
Date Sample Taken 9/30/86 Date Result Received:
10/14/86 Results of Analysis:
17.6 mg/l Monthly Average Result:
17.6 mg/l Monthly Average Permit Limitation:
15 mg/l CAUSE OF NONCOMPLIANCE:
I 7
l gg-2 There was { { ) 7 The cause of the noncompliance is unknown.
no visible oil at the time of sampling.
The results of I
the analysis were not received in time to allow for a resample to bring the average value into compliance.
This sample point has not had a noncompliance for oil and grease in at least the last three years.
j p
8611040434 861024 PDR ADOCK 0000 S
PR
_ 7 g
DURATION OF NONCOMPLIANCE:
The duration of the noncompliance is unknown.
A sample taken on October 2, 1986 was 0.9 mg/l oil and grease indicating the discharge was in compliance with~the NPDES permit.
V,ery truly yours, T
G. M.
Leitch Superintendent Nuclear Generation Division JAV/WTU:ala cc:
Environmental Protection Agency Water Permits Branch Pennsylvania Section 3WM52 841 Chestnut Building Phila'delphia, Pennsylvania 19107 Director Office of Nuclear Reactor Regulation US Nuclear Regulatory Commission Washington, DC 20555 Administrator Region I of fice of Inspection and Enforcement US Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406 l
4 4
G 4
m-,.-,my
-,--,.-.-.,s
,_m, w-4
,-----*-.-r~
-... - - -,