PHILADELPHIA ELECTRIC COMPANY 2301 MARKET STREET P.O. BOX 8'699 PHILADELPHIA. PA.19101 (215)841-4000 September 29, 1986 Department of Environmental Resources Bureau of Water Quality Management One Ararat Blvd.

Harrisburg, PA 17110

SUBJECT:

Noncompliance with NPDES Permit Peach Bottom Atomic Power Station Permit No.

PA 0009733 Gentlemen:

DESCRIPTION OF NONCOMPLIANCE:

The pH of a sample from discharge point 301 (Waste Water Settling Basin) exceeded the permit limit.

l Date Samples Taken 8/6/86 Date Results Received:

8/6/86 Results of Analysis:

5.0 Permit Limitation:

6.0 to 9.0 CAUSE OF NONCOMPLIANCE:

When the acid day tank for the water plant demineralizers was drained in preparation for maintenance, the acid inadvertently entered the raw water pump through an open drain valve on a neutralizing tank.

When the sump was being recirculated to neutralize *it, some of the acid went to the settling basin.

DURATION OF NONCOMPLIANCE:

The duration of noncompliance was approximately two hours.

8610060797 860729 PDR ADOCK ODOOO:T/7

< /$5 S

PDR P

O

h

- CORRECTIVE ACTION:

Liquid sodium hydroxide was added to the settling basin to bring the pH into the acceptable range.

~

PREVENTION OF FUTURE OCCURRENCES :

A letter was written to shift supervision suggesting neutralization of the raw water sunp should be accomplished by processing the water back through the neutralization tank.

A copy of the letter was also forwarded to the training section.

,Very ruly yours, G. M Leitch Superintendent Nuclear Generation Division JAV/GML:ala Environmental Protection Agency.

cc:

Water Permits Branch Pennsylvania Section 3WM52 841 Chestnut Building Philadelphia, Pennsylvania 19107 Director Office of Nuclear Reactor Regulation US Nuclear Regulatory Commission Washington, DC 20555 Adninistrator Region 1 Office of Inspection and Enforcement US Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406 L

-