_

l' t

~

PHILADELPHIA ELECTRIC COMPANY 2301 MARKET STREET P.O. BOX 8699 PHILADELPHI A. PA.19101 12151841-4000 May 28, 1987 Department of Environmental Resources Bureau of Water Quality Management One Ararat Blvd.

Harrisburg, PA 17110

SUBJECT:

Noncompliance with NPDES Permit Peach-Bottom Atomic Power Station Permit No.

PA 0009733 Gentlemen:

DESCRIPTION OF NONCOMPLIANCE:

The suspended solids of a sample from discharge point 501 (Sewage Treatment Plant) exceeded the instantaneous maximum permit limit.

Date Sample Taken 4/13/87 Date Results Received:

4/13/87 Results of Analysis:

132 ppm Permit Limitation:

60 ppm Maximum CAUSE OF NONCOMPLIANCE:

.The cause of the noncompliance was high suspended solids in the aeration tank resulting in a heavy sludge loading on the clarifiers and subsequent carryover of solids.

The problem was compounded by the filters being out of service for maintenance.

b 8706090227 B70528 PDR ADOCK 05000277 g

S PDR I

I I

4

  • DURATION OF NONCOMPLIANCE:

The exact duration is unknown, but the turbidity data indicate that the instantaneous maximum was exceeded intermittently over a four day period.

CORRECTIVE ACTION:

The corrective action was to increase the wasting of sludge to reduce the solids level.

In addition, flow was stopped from the sewage plant and the effluent was reprocessed through the equalization basin.

The filters were returned to service on May 4 after several maintenance items were completed.

PREVENTION OF FUTURE OCCURRENCES The solids level is being closely monitored and increased wasting of solids is being performed as needed.

The sludge level in the clarifiers is being monitored so that appropriate and timely action can be taken to reduce carryover.

Very truly yours, J

(r(e v

G. M. Leitch Superintendent Nuclear Generation Division JAV/WTU:ala cc:

Environmental Protection Agency Water Permits Branch Pennsylvania Section 3WMS2 841 Chestnut Building Philadelphia, Pennsylvania 19107 Director Office of Nuclear Reactor Regulation US Nuclear Regulatory Commission Washington, DC 20555 Administrator Region I Office of Inspection and Enforcement US Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406 L