G CAROLINA POWER & LIGHT COMPANY r

BRUNSWICK STEAM ELECTRIC PLANT UNIT 2

[

r i

PROCEDURE TYPE:

ALTERNATIVE SAFE SHUTOOWN PROCEDURE I

t NUMBER:

ASSD-01 PROCEDURE TITLE:

ALTERNATIVE SAFE SHUTDOWN PROCEDURE INDEX i

es:

Rev. 0 4/4/88

{

W0 h,+qf.

O

,,p 90g

\\< ;}[$((.'

l I

Approved By:

-[

Date:

if GeneralManager/Malpager-Oper{ ions

'/

/

t te i

BSEP-2/ASSD-01 Page 1 of 128 Rev 0 8811110002 081025 DR ADOCK 050 4

i l

r

~

LIST OF EFFECTIVE PAGES

'(")

L A$5D-01 r

Pace (s )

, Rey 1'sion 1-128 0

i i

b i

1

,l R B.:

()

i h

l 1

i L

k bb B'. EP-2/ A550-01 Page 2 of 128 Rey, 0 l

l

TABLE OF CONTENTS

~

Section h

LIST OF EFFECT!YE PAGES 2

TABLE OF CONTENTS 3

FIGURE"5 6

A.

INTRODUCTION 7

1.

Title 7

2.

Purpose 7

B.

ENTRY CONDITIONS 7

C.

OPERATOR ACTIONS 8

TABLE 1 ASSO FIRE AREA 11 TABLE 2 EMERGENCY POWER SYSTEM AC 16 4.16KV EMERG SWGR El 16 RB 4.16KV EMERG SWGR Et 17

)

4.16KV EMERG SWGR E3 18 4.16KV EMERG SWGR E4 19 480V Substation E5 20 480V Substation E6 21 480V Substation E7 22 480V Substation E8 23 Reactor Building MCC 2XA 24 Reactor Butiding MCC 2XA-2 28 Reactor Building MCC 2XB 29 Reactor Building MCC 2X8-2 33 Reactor Building MCC 2XC 34 Reactor Building MCC 2XD 36 b

BSEP-2/ASSD-01

.Page 3 of 128 Rev. O

TABLE OF CONTENTS Section Paes

(-)

Diesel Generator Building MCC DGA 38 Diesel Generator Building MCC DG8 40 Diesel Generat.or Building MCC DGC 42 Diesel Gen.erator ' Building MCC DGO,

'44 Control. Building MCC 2CA 47 Control Building MCC 268 49 Service Water Intake Structure MCC 1PA 51 Service Water Intake Structure MCC 1P8 53 i

Service Water Intake Structure MCC 2PA 55 Service Water Intake Structure MCC 2PS 57 Emergency 120V AC Distribution Panel 2E7 59 Emergency 120V AC Distribution Panel 2E8 60 R B.

Emergency 120V AC Distribution Panel 1A-DG 61 O

Emergency 120V AC Distribution Panel 18-DG 63 i

Emergency 120V AC Dit tribution Pane) 2A-DG 65 i

Emergency 120V AC Distributioe, Panel 28-DG 67 Uninterruptible Power Supp'iy 2A 69 Reactor Protection System Power Distribution Panel 70 Emergency 120V AC Dittribution Panel 32A 74 Emergency 120V AC Distribution Panel 328 76 Emergency 120V AC Distribution Panel 1A-SW 78 Emergency 120V AC Distributtori Panel 2A-SW 79 Vital 120V AC Distribution Panel V-8A 80 l

h' BSEP-2/ASSD-01 Page 4 of 128 Rev. O

TABLE OF CONTENTS Section Pa ge 6'

Vita) 120V AC Distribution Panel V-10A 81 Emergency 120V AC Distribution Panel 2A 82 1

Emergency 120V AC Distribution Panel 2R 8 5..

Emergency 120V AC Distribution Panel 32A8 88 TABLE 3 EERGENCY POWER SYSTEM DC 91 125/250V DC $witchboard 1A 91 125/250V DC Switchboard 18 93 Reactor Building MCC 1XDA 95 Reactor Building MCC IXD8 97 125V DC Distribution Panel 1A 99 125V DC Distribution Panel 1B 100 125V DC Distribution Pane') 3A 102 A B.

125Y DC Distribution Panel 3B 104 125V DC Distribution Par.cl 11A 106 125V DC Distribution Panel 118 108 125/250V DC $witchboard ?.A 110 125/250V DC Switchboard 28 112 Reactor Building MCC 2XDA 114 Reactor Building MCC 2XD8 116 125V DC Distribution Panel 2A 118 125V DC Distribution Panel 28 119 125V DC Distribution Panel 4A 121 125V DC Distribution Panel 4B 123 125Y DC Distribution Pane) 12A 125 125V DC Distribution Panel 128 127

}b, BSEP-2/ASSD-01 Fage 5 of 128 Rev. O i

F i

FIGURES 71oure Page 4

h.

. Unit 2 Reactor Building -17'-0*

13

.- Elevation Fire Areas 2

Unit 2 Re' actor Building 20'-0" 14 Elevation Fire Areas 3

Unit 2 Reactor Building 50'-0*

15 Elavation Fire Areas RB C

l l

\\

l l

l l

c:

L.s 85EP-2/ASSD-01 Page 6 of 128 Rev. O

A.

INTRODUCTION g

1.

Title:

Alternative Safe Shutdown Procedure index 2.

Purpose a.

The purpose of ASSD-01 and branch ASSD procedures for given fire areas is to provide alternative shutdwn capabilities for a worst case fire in any one of those fire areas with or without a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> loss of off-site power to achieve the following goals:

(1)

Achieve and maintain suberitical reactivity conditions in the reactor (2)

Maintain reactor coolant inventory (3)

Achieve and maintain hot shutdowr, (4)

Achieve cold shutdown within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> (5)

Maintain cold shutdown conditions thereafter b.

Analysis submitted to the NRC in the Alternative Shutdown Capability Assessment Report indicates that a fire in any area will not affect the ability to scram the reactor. Therefore R B.

suberitical reactivity conditions can be achieved for all fire treas.

ASSD-01 and the appropriate branch procedure provide unique guidance to be used in conjunction with E0P's and other operations procedures to achieve the remaining goals.

c.

ASSD-01 provides the following:

(1)

A comon branching point for all ASSD procedures i

1 1

(2)

An index for determining the appropriate ASSD procedure I

to be used (3) to allow positive identification of the Figures,iate procedure to be entered for fire in the appropr reactor butiding (4)

A table for all AC p>er feeds to safe shutdown equipment and associated non-safe shutdown equipment (5)

A table for all DC power feeds to safe shutdown equipment and associated non-safe shutdown equipment B.

ENTRY CONDITIONS This procedure is entered from.PFP-013 General Fire Plan.

G BSEP-2/ASSD-01 Page 7 of 128 Rev. O

C.

OPERATOR ACTIONS O

1.

WHEN the specific location of the fire has been identified.

TR M REFER to Table 1 to determine if an ASSD fire area is involved.

2.

E the fire is NOT located in an ASSD fire area, THEN EXIT this procedure.

3.

IF the fire is in ai ASSD fire area on either unit, THEN the 37ilft Foreman will ASSESS the situation considering the following.

a. Location, size and severity of the fire.
b. Effect of the fire on ASSD equipment.
c. Limiting conditions for operation resulting due to fire.

R8

d. Control room habitability.
e. Effect of the fire on balance of plant.

4.

IF the Shift Foreman determines that the ability to confirm Te' actor power less than 3% is in jeopardy, THEN

a. Manually SCRAM the reactor.
b. CONFIRM reactor power is less than 3% by using one of the following.

(1)

Neutron monitoring system (2)

Rod position indication system I

I l

l BSEP-2/ASSD-01 Page S of 128 Rev. 0 l

L

i 5.

IF the Shift Foruman determinos that alternative safe shuttlown he actions are required, THEN

a. E the Unit is NOT in Hot Shutdown, THEN (1)

Manually SCRAM the Reactor.

i (2)

CONFIRM reactor power is less than 3 by using one of the following (a)

Neutron monitoring system (b)

Rod position indication system

b. E the fire is in the Control Building, THEN i

(1)

Manually SCRW,the reactor (2)

Place the MSIV controi switches in the CLOSE position l

(3)

EXIT this proceriure.

(4)

ENTER ASSD-02, Control Building.

R S, @

c. IF the fire is in the North side of Unit 2 Reactor

@i Wilding,THEN (1)

Monually SCRAM the reactor (2)

Place the MSIV control switches in the CLOSE position (3)

EXIT this procedure A@..

l t

(4)

ENTER ASSD-05, Reactor Building f4 orth, i

d. IF the fire is NOT in tne Control Building OR Reactor i

WildingNorthTireareas.THENENTERtheaW11cabic ASSD procedure AND EXECU1E it concurrently with this procedure.

[

t t

I I

l 1

1

! h l

BSEP-2/ASSD-01 Page 9 of 128 Rev. 0 l

l I

g CAUTION Fire damage may result in high impedance f aults involving nan-safe shutdown equipment which could cause safe shutdown power sources to be doenergized.

I

.........**.*******..**......***.......***......... u.....***********.......

6.

IF while executing the applicablo ASSD proceduro, any safe siiutdown equipment for the safe shutdown train designated in that procedure is deenergized due to electrical faults, THEN

a. REFER to TABLE 2. Emergency Power System AC for AC
loads,
b. REFER to TABLE 3. Emergency Power System DC for DC
loads,
c. SHED all loads from the affected powcr supply THEN (1)

REENERGlZE all required safe shutdown loads.

(2)

ISSVE clearances on oli non-safe shutdown loads.

@)

7.

WHEN

a. The fire has been extinguished, AND
b. The applicable ASSD procedure has been exited, AttD
c. All equipment shed in Step 6 is either reenergized or under cicarance Am
d. The Shift Foreman has determined that the reactor can be maintained in a safe condition without the use of ASSD procedures. THEN EXIT this procedure.

Date/ Time Completed Performed By (Print)

Initials Reviewed By:

Shif6 Foreman g

BSEP-2/ASSD-01 Page 10 of 128 Rev. O

ASSD FIRE AREA Q"-

ASSD PROCEDURE LOCATION SAFE SHUTDOWN TRAIN i

ASSD-02 Control Building B

ASSD-03 Control Building 23' Elevation B

i Battery Room 2A r

ASSD-04 Control Building 23' Elevation A

Battery Room 28 ASSD-05 Unit 2 Reactor Building North 8

(See Figures 1, 2, 8 3)

ASSD-06 Unit 2 Reactor Building South A

(See Figures 1, 2, & 3)

ASSD-07 Reactor Building ECCS Pipe Tunnel A/B i

(See Figure 2)

R B.

ASSD-08 Turbine Building (Excluding Electrical Tunnels)

A ASSD-09 Service Water Building A/B b

ASSD-10 Condensate Storage Tank Area B

ASSD-11 Diesel Generator Cooling Water Valve Pit B

A550-12 Diesel Generator Building 2' Elevation A/B Diesel Generator Basement ASSD-13 Diesel Generator Building 23' Elevation B

l Diesel Generator Cell 1 l

ASSD-14 Diesel Generator Building 23' Elevation A

Diesel Generator Cell 2 t

ASSD-15 Diesel Generator Building 23' Elevation 8

Diesel Gsnerator Cell 3 ASSD-16 Diesel Jenerator Building 23' Elevation A

Diesel Generator Cell 4 ASSD-17 Diesel Generator Building 23' Elevation B

E5 Switchgear Room ASSD-18 Diesel Generator Building 23' Elevation A/B E6 Switchgear Room l

Q')

BSEP-2/ASSD-01 Page 11 of 128 Rev. O

TABLE 1 (Cont'd)

ASSD FIRE AREA

(])

A550 PROCEDURE LOCATION 5AFE SHUTDOWN TRAIN ASSD-19 Diesel Generator Building 23' Elevation A/B E7 Switchgear Room i

ASSD-20 Diesel Generator Butiding 23' Elevation A

E8 Switchgear Room ASSD-21 Diesel Generator Building 50' Elevation B

El Switchgear Room ASSD-22 Diesel Generator Building 50' Elevation A

E2 Switchgear Roon ASSD-23 Diesel Generator Building 50' Elevation B

E3 Switchgear Roam i

ASSD-24 Diesel Generator Building 50' Elevation A

E4 Switchgear Room ASSD-25 Diesel Generator Building l' Elevation 8

Diesel Generator No.1 Four Day Storage Tank Room b

ASSD-26 Diesel Generator Building l' Elevation A

i Diesel Generator No. 2 Four Day Storage Tank Roos i

ASSD-27 Diesel Generator Building l' Elevation B

Diesel Generator No. 3 Four Day Storage Tank Room l

ASSD 28 Diesel Generator Building l' Elevation A

I Diesel Generator No. 4 Four Day Storage Tank Room I

ASSD-29 Control Building Battery Room 1A B

i t

ASSD-30 Control Building Battery Room 18 A

j ASSD 31 Unit 1 Reactor Building South A

[

j AS$0-32 Unit 1 Reactor Building North 8

l

'h BSEP-2/ASSD-01 Page 12 of 128 Rev. 0

NCRTH _

O 1

\\

DRYWELL SEE DETAIL'A' MEACTOR BLOG. //

SOUTH ASSD oS

/

REACTOR SLDG ASSO-OS i

N O-

[,

j

/

a i

HPCl ll/\\

ROOM

/

Cd

/

2///// m % w m E L, - 17*-0" O

c f/f; - RE ACTOR SUILDING SOUT H I

8-

'j ASSD-04.

g 5/E

/<

' g g g -REACTOR SulLDING NORTH s

o A S S D-OS.

o S/E - 20

. Wlot SEP AR ATION o

~

COoo o-WATER CURTAIN.

+ 5' ELEV.

(SPM AY NOIILES)

ABOVE HPCI ROOM D ETAIL "A" noun i Unit. i

'Or Building -17' O' L

.. ton Fire Areas C

i BSEP-2/AS50-01 Page 13 of 128 Rev. O

14 v M PW ITAI

/

/

REACTOR BLDG

/

NORTH

/

/

/

ASSD 05

[r y

/

j

/

DRYWEi L

/

b s

RE' ACTOR BLOG.

TUNNE

=

SOUTH,

/

)

p ASSD 06 t

g,

/,

Q S/2

,/ /

M

(

/

R%

UN!T 2 LEGEND

[//j-RE ACTOR BUILDING SOUTH M

  • REACTOR BUILDING NORTH S/2 - 20FT. WIDE SEPAR A TION EONE.

00000 - WATER CURTAIN l

SPR AY NOEZLES FIGURE 2 Unit 2 Reactor Building 20'-0" Elevation Fire Areas G

BSEP-2/ASSD-01 Page 14 of 128 Rev. O

J "" m

-J %

g y

r

~

SEE DETAIL'A'

.1 s

2 1 DRYWELL 1

/

W o

REACTOR OLOS

/ 3 o

RfACTOR BLOS j

SOUTH AS$0+04

/ o S/Z o NORTH A330-05

(

8 8

i o

o

? - -

/

f"1 o R B.

E L. 50'- 0" h

MI*E

.J l I

/

//j

- REACTOR SLOS SOUTH AS30-04

/

/

I f

(#8 - RE ACTOR BLOG NORTH i DRY r/

A330-05 5 / Z - 20 FT Wl0E SEPAR ATION b

ZONt ooooo - WATER CURT AIN

]

(SPRAY N0Z ZL E S)

EL. 60'-0*

MEZZMINE NtEA ABOVE RWCU RECIRC PLMP ROOM D E TAIL"A" FIGURE 3 Unit 2 Reactor Building 50'-0" Elevation Fire Areas n

i b

BSEP-2/A550-01 Page 15 of 128 Rev. O j

TABLE 2 p/

EMERGENCY POWER SY_ STEM AC y

Safe Shutdown Component:

4.16KV EMERG SWGR El Normal Power Supply:

4.16KV Switchgear Bus ID Compt. AD1 Alternate Power Supply:

Diesel Generator No. 1 Compt. AE9 Location:

Diesel Generator Bu1:aing - 4 6 Ceii 1 - Ei. W Safe Shutdown Loads Compt.

SSD Number T rain Component Description Open Verified AE9 A

Compt AE9 Diesel Gen No 1 g/A AF0 A

Compt AF0 RHR Pump 1C N/A AF5 A

Compt AFS RHR Pump 2C N/A AF6 A

Compt AF6 Cony Serv Wtr Pump 2C N/A N/A AF7 A

Compt AF7 Cony Serv Wtr Pump 1B N/A AF8 A

Compt AF8 Unit Substa E5 N/A AF9 A

Compt AF9 Nuc Serv Wtr Pump 1A

"^

AGO A

Compt AGO Tie Breaker '

'g Swgr E3 El AG1 A

Compt AG1 Tie Breaker Er.arg Swgr E2 N/A Non-Safe Shutdown loads Cntr1. Pwr.

Compt.

Fuses Clearance Number Component Description Open Removed Issued AE6

_ Compt AE6 Incoming Line Swgr 10 AF1 Compt AF1 RHR Serv Wtr Pump 1C AF2 Compt AF2 RX Core Spray Pump 1A AF3 Compt AF3 CRD Hydraulic Pump 1A AF4 Compt AF4 RHR Serv Wtr Pump 2C b

BSEP-2/ASSD-01 Page 16 of 128 Rev. O

TABLE 2 (Cont'd)

EMERGLNCY POWER SYSTEM AC Safe Shutdown Component:

4.16KV EMERG SWGR E2 h,

Normal Power Supply:

4.16KV Switchgear Bus 1C Compt. AC8 Alternate Power Supply:

Diesel Generator No. 2 Compt. AG7 I

Location:

Diesel Generator Building - 4KY Cell 2 - E1. 34' Safe Shutdown Loads Compt.

55D

~

~

. Number. Train Component Descriptice.

Open~

Variffe4 B

Compt AG7 Diesel Gen' No. 2 N/A AG7 AG9 B

Compt AG9 RHR Pump 2D N/A AH1 B

Compt AH1 Unit Substa E6 N/A N/A AH2 B

Co. apt AH2 Cot.v Serv.Wtr Pump 1C N/A AHS B

Compt AHS RHR Pump 10

^

AH6 B

Compt AH6 Nuc Serv Wtr Pump 1B E

AH8 B

Compt AH8 Tie Breaker Emerg Swgr El N/A AH9 B

Compt AH9 Tie Breaker Emerg Swgr E4 N/A 6

Non-Safe Shutdown Loads

~~

Gntr1. Pwr.

i Fuses Clearance l

l

- Compt.

Number Cogonent Description Open Removed Issued AG4 Compt AG4 Incoming Lir.e Swgr 1C AG8 Cogt AG8 RHR Serv Wtr Pump 2D l

j' AHO Compt AHO RX Core Spray Pump 18 l

i AH3 Compt AH3 CRD Hydraulic Pump 1B i

AH4 Cogt AH4 RHR Serv Wtr Pump 1D l

AH7 Compt AH7 Fire Pump Normal F=ed i

1 i

i l

0 BSEP-2/ASSD-01 Page 17 of 128 Rev. O I

b

~

l i

TABL_E 2 (Cont 'd )

EMERGENCY POWER SYSTEM AC 9q Safe Shutdown Component:

4.16KV EMERG SWGR E3 2

Normal Power Supply:

4.16KY.Switchgear Bus 2D Compt. AD1 Alternate Power Supply:- Diesel Generator No. 3 Compt. AIS Location:, Diesel Generator Building 4KV Cell 3 - Ei. 38' Safe Shutdown Leuds Compt.

55D j

. Number Train Component Description Open Verified AIS A

Compt AIS Diesel Gen No 3 N/A i

A18 A

Compt A18 RHR Pump 1A.

N/A AJO A

ComptAJOUnitSubstaE7 nf4 AJ1 A

Compt AJ1 RHR Pump 2A N/A AJ3 A

Compt AJ3 Nuc Serv Wtr Pump 2A N/A AJ4 A

Compt AJ4 Cony Serv Wtr Pump 2A N/A AJS A

Ccupt AJS Tie Breaker Emerg Swgr El N/A Non-Safe Shutdown Loads (md' Cnt r1. Pwr.

Compt.

Fuses Clearance Number Component Description Open Removed Issued A12 Compt A12 Incoming Line Swgr 20 A16 Compt A16 RX Core Spray Pump 2A '

A17 Compt A!7 RHR Serv Wtr Pump 2A A19 Compt A!9 RHR Serv Wtr Pump 1A AJ2 Compt AJ2 CR0 Hydraulic Pump 2A AJ6 Compt AJ6 Tie Breaker Emerg Swgr E4 b'

BSEP-2/ASSD-01 Page 18 of 128 Rev. 0

r TABLE 2 (Cont'd)

EMERGENCY POWER SYSTEM AC

'g Safe Shutdown Component:

4.16KV EMERG SWGR E4 Normal Power Supply:

4.16KV Switchgear Bus 2C Compt. AC8 Alternate Power Supply:

Diesel Generator No. 4 Compt. AK2 Location: Diesel Generator Butiding - 4KV Cell 4 - E1. 38' Safe Shutdown Loads compt.

ssD Number Train Component Description Open Veri fled AK2 B

Compt AK2 Diesel Gen'No 4 N/A AK3

'B.

Compt AK3 RHR Pump 2'8

~

AK6 B

Compt AK6 Cony Serv Wtr Pump 1A N/A AK7 B

Compt AK7 Unit Substa E8 N/A ALO B

Compt ALD RHR Pump 18 N/A All B

Compt All Nuc Serv Wtr Pump 23 N/A AL2 B

Compt AL2 Cony Serv Wtr Pump 28 N/A ALS B

Compt ALS Tie Breaker Emerg k gr E2 N/A' Non-Safe Shutdown Loads cntr1 Pwr.

Compt.

Fuses Clearance Number Component Description Open Removed

!ssued AJ9 Compt AJ9 Incoming Line Swgr 2C AK4 Compt AK4 RHR Serv Wtr Pump 2B I

AKS Compt AKS RX Core Spray Pump 28 AK8 Compt AK8 CR0 Hydraulic Pump 2B AK9 Com t AK9 RHR Serv Wtr Pump 1B AL3 Compt AL3 Fire Pump Feed AL4 Compt AL4 Tie Breaker Emerg Swgr E3 O

BSEP-2/ ASS 0-01 Page 19 of 128 Rev. O

TABLE 2 (Cont'd) h EMERd!NCY POWER SYSTEM AC l

Safe Shutdown Component:

4BOV Substation E5 Normal Power Supply:

4160V Emergency Bus El Compt. AF8 Alternate Power Supply:

480V Substation E6 Compt. AX1 Location:

Diesel Generator Building - Ei. 23' - NW Safe Shutdown Loads Compt.

SSD Ind Ind Number Train Component Description Open Ver Closed Ver ATS A

Control Building' MCC 1CA N/A AT8 A

Reactor Building MCC 2XA-2 N/A AT9 A

Reactor Building MCC 1XC N/A AVO A

Emergency 120V AC Distribution Panel N/A IES Supply Breaker AU3 A

Service Water Building MCC 1PA N/A AU4 A

Reactor Building MCC 1XA N/A RS

({[

AU6 A

Diesel Generator Building MCC DGA N/A AU9 A

Sub E5 480V Main Breaker N/A Non-Safe Shutdown Loads Compt.

Clearance l Number Component Description Open Issued AT4 Tie Breaker To E6 AT7 Off Gas Building MCC 10G AU1 Reactor Building MCC 2XJ AU2 Reactor Building MCC 1XE AUS Reactor Building MCC IXL AVO Reactor Building MCC IXG b_

BSEP-2/ASSD-01 Page 20 of 128 Rev. O

I TABLE 2 (Cont'd)

EMERGENCY POWER SYSTEM AC i

Safe Shutdown Component:

480V Substation E6 Normal Power Supply: 4160V Emergency Bus E2 Compt. AH1 Alternate Power Supply:

480V Substation E5 Compt. AT4 Location: Diesel Generator Building - E1. 23' NE Safe Shutdown Loads Compt.

SSD Ind lnd Number Train Component Description Open Yer Closed Ver AV4 B

Sub E6 480V Main Breaker N/A AV8 B

Reactor Building MCC 2XB-2 N/A AV9 B

Diesel Generator Building MCC DGB N/A AWO B

Reactor Building MCC IXB N/A AW3 B

Service Water Building MCC IPB N/A AW6 B

Reactor Building MCC 1XD N/A AW7 B

Control Building MCC ICB N/A S

AX3 B

Emergency 120V AC Distribution Panel N/A 1E6 Supply Breaker Non-Safe Shutdown Loads Compt.

Clearance Number Component Description Open Issued AV5 Reactor Building MCC 1XH AV6 480V Lighting Distribution Panel (10 AV7 480V Lighting Distribution Pant' E9 AW1 Reactor Building MCC 2XX AW2 Reactor Building MCC 1XF AW4 Off Gas Building MCC 20G AWS Reactor Building MCC 1XM AX1 Tie Breaker To E5 Gk.

BSEP-2/ASSD-01 Page 21 of 128 Rev. O

TABLE 2 (Cont'd) h EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

430V Substation E7 Normal Power Supply: 4160V Emergency Bus E3 Compt. AJO Alternate Power Supply:

480V Substation E8 Compt. AIO Location:

Diesel Generator Building - El. 23' - SW Safe Shutdown Loads Compt.

SSD Ind Ind Number Train Component Description Open Ver Closed Ver AX9 A

Reactor Building MCC IXA-2 N/A AYO A

Reactor Building MCC 2XC N/A AY1 A

Emergency 120V AC Distribution Panel N/A 2E7 AY2 A

Reactor Building MCC 2XA N/A AYS A.

Service Water Building MCC 2PA N/A AY8 A

Diesel Generator Building MCC DGC N/A RI AY9 A

Control Building MCC 2CA N/A

~

g09 AZ1 A

Sub E7 480V Main Breaker N/A Non-Safe Shutdown Loads Compt.

Clearance Number Component Description Open Issued AX5 Tie Breaker to E8 AX6 Reactor Building MCC 2XL AY3 Reactor Building MCC 1XJ AY4 Reactor Building MCC 2XE AZ2 Reactor Building MCC 2XG h

BSEP-2/ ASS 0-01 Page 22 of 128 Rev. O

TABLE 2 (Cont'd) iM, EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

480V Substation E8 Normal Power Supply:

4160V Emergency Bus E4 Compt. AX7 Alternate Power Supply:

480V Substation E7 Compt. AX5 Location:

Diesel Generator Building - El. 23' - SE Safe Shutdown Loads Compt.

SSD Ind Ind Number Train Component Descri pion Open Ver Closed Ver A12 B

Emergency 120V AC Distribution Panel N/A 2E8 A01 B

Diesel Generator Building MCC DGD N/A A02 B

Reactor Building MCC 2XB N/A A05 B

Service Water Building MCC 2PB N/A A08 B

Reactor Building MCC 2XD N/A RE A09 B

Control Building MCC 2CB N/A (y

AZ5 B

Sub E8 480V Main Breaker N/A AZ9 B

Reactor Building MCC IXB-2 N/A Hon-Safe Shutdown Loads Compt.

Clearance Number Component Description Open Issued A10 Tie Breaker To E7 A03 Reactor Building MCC IXX A04 Reactor Building MCC 2XF A07 Reactor Building MCC 2XM AZ6 Reactor Building MCC 2XH AZ7 Standby Distribution Panel E12 AZ8 Standby Distribution Panet E11 k

BSEP-2/ASSD-01 Page 23 of 128 Rev. O

TABLE 2 (Cont'd)

EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XA Normal Power Supply:

480V Substation E7 Compt. AY2 Alternate Power Supply:

N/A

~

Location:

Reactor Building - El. 20' - North Safe Shutdown loads Compt.

SSD Ind Ind Number Train Component Description Open Ver Closed Ver 006 A

Recirculation Pump 2A Suction Valve, N/A 2-832-F023A, Circuit Breaker OE1 A

Vital Service Header Divisional Tie N/A Valve, 2-SW-V118. Circuit Breaker DE2 A

HPCI Turbine Exhaust Vacuum Breaker N/A Valve, 2-E41-F075, Circuit Breaker I

DE3 A

Nuclear Header To RBCCW Heat Exchangers N/A Isolation Valve, 2-SW-V106, Circuit Breaker pd.

DE4 8

RCIC Turbine Exhaust Vacuum Breaker N/A N/A N/A Valve, 2-E51-F062, Circuit Breaker 6

OE5 A

RHR HX-A Service Water Discharge N/A C

Valve, 2-E11-F002A, Circuit Breaker DE6 A

RHR HX 2A Outlet Valye, 2-E11-F003A, N/A Circuit Breaker DE7 A

RHR Pump 2A Suppression Pool Suction N/A Valve, 2-E11-F004A, Circuit Breaker OE8 A

RHR Pump 2C Suppression Pool Suction N/A Valve, 2-E11-F004C, Circuit Breaker

  • 0E9 A

RHR Pump 2A Shutdown Cooling Suction N/A Valve, 2-E11-F006A Circuit Breaker

  • 0F0 A

RHR Pump 2C Shutdown Cooling Suction h/A Valve, 2-E11-F006C Circuit Breaker

  • NOTE:

i Shutdown Cooling Suction Valves, 2-E11-F006A and 2-E11-F006C are normally under a Shift Foreman's clearance when the unit is operating.

The Shift Foreman may remove this clearance at his discretion when it has been verified that maintenance on the valves is not in progress.

i l

BSEP-2/ ASS 0-01 Page 24 of 128 Rev. O l

i

TABLE 2 (Cont'd)

EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XA Safe Shutdown Loads (Cont'd)

Conpt.

55D Ind Ind Number Train Component Description Open Ver Closed Ver DF1 A

RHR Minimum Flow Bypass Valve, 2-E11-F007A, Circuit Breaker N/A DF2 A

RHR HX 2A Drain To Suppression Pool Valve, 2-E11-F011 A, Ci rcuit Breaker N/A DF4 A

Drywell Spray Outboard Isolation Valve, 2-E11-F016A, Circuit Breaker N/A DF6 A

Drywell Spray Inboard Isolation Valve, N/A 2-E11-F021A, Circuit Breaker DF7 A

Suppression Pool Cooling Isolation N/A Valve, 2-E11-F024A, Circuit Breaker R

DF8 A

RHR HX 2A Drain to RCIC Valve, N/A 2-E11-F026A, Circuit Breaker

([@

DF9 A

Suppression Pool Spray Isolation Valve, N/A 2-E11-F027A, Circuit Breaker DG1 A

RHR HX 2A Inlet Valve, 2-E11-F047A, N/A Circuit Breaker DG2 A

RHR HX 2A Bypass Valve, 2-E11-F048A, N/A Circuit Breaker

  • DG3 A

LPCI Injection Check Valve Bypass N/A Valve, 2-E11-V32, Circuit Breaker DG5 A

RHR HX A Service Header Outlet Valve, 2-E11-POV-F068A, Circuit Breaker N/A

  • NOTE:

LPCI Injection Check Valve Bypass Valve, 2-E11-V32 is normally under a Shift Foreman's clearance when the unit is operating.

The Shift Foreman may retrove this clearance at his discretion when it has been verified that maintenance on the valve is not in progress.

b BSEP-2/ASSD-01 Page 25 of 128 P.ev. O

gn TABLE 2 (Cont'd)

W' EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XA Safe Shutdown loads (Cont'd)

Compt.

SSD Ind Ind Number Train Component Description Open Ver Closed Ver DG8 A

RHR Pump 2A And 2C Suppression Pool N/A Suction Valve, 2-E11-F020A, Circuit Breaker

  • DH3 A

Compt. 2-DH3 Motor 2-XM2 RHR Suction N/A Isol. Viv. 2-E11-F009 Normal Feed

  • DH4 A

RHR To Radwaste Inboard Isolation N/A Valve, 2-E11-F049, Circuit Breaker DH5 A

Conventional Header to RHR Service N/A Water Pump 2A And 2C Supply Valve, 2-SW-V101, Circuit Breaker Et OH6 A

Vent RHR HX Area Cooling Fan, N/A 2A-FCV-RB, Circuit Breaker en Wi Non-Safe Shutdown Loads Compt.

Clearance Number Component Description Open Issued BT7 Primary Containment Atmosphere Radiation Monitor, 2-CAC-AT-1262, Circuit Breaker

  • NOTE:

RHR Suction Isolation Valve, 2-E11-F009 and RHR To Radwaste Inboard 1 solation Valve, 2-E11-F049 are normally under a Shift Foreman's clearance when the unit is operating.

The Shift Foreman may remove this clearance at his discretion when it has been verified that maintenance on the valves is not in progress.

BSEP-2/ASSD-01 Page 26 of 128 Rev. O

TABLE 2 (Cont'd)

EMERGENCY PDWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XA Non-Safe Shutdown Loads (Cont'd)

Compt.

Clearance Numbe r Component Description Open Issued DG6 RHR HX 2A Outboard Vent Yalve, 2-E11-F103A, Circuit Breaker DG7 RHR HX 2A Inboard Vent Valve, 2-E11-F104A, Circuit Breaker DH1 Recirculation Pump 2A Seal Water Injection Valve, 2-B32-V22, Circuit Breaker DH2 Reactor Vessel Head Spray Inboard Isolation Valve, 2-E11-F022, Ci rcuit R

Breaker DH7 Reactor Building Off Gas Drain Tank Pump A, 2-G16-2A-1, Circuit Breaker gg DH8

'TBCCW HX Service Water Header Outboard

%W Isolation Valve, 2-SW-Y4, Circuit Breaker DIO Conventional Header To Vital Header Supply Valve, 2-SW-V111, Circuit Breaker Disconnect Switch 9KVA 39 480-208Y/120V Transformer k

BSEP-2/ ASS 0-01 Page 27 of 128 Rev. O

.1 i

TABLE 2 (Cont'd)

EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XA-2 Normal Power Supply:

480V Substation E5 Compt. AT8 Alternate Power Supply:

N/A Location:

Reactor Building - El. 20' - North I

Safe Shutdown Loads Compt.

SSD I nd I nd Number Train Component Description Open Ver Closed Ver l

DD7 A

Recirculation Pump 2A Discharge Valve, N/A 2-832-F031A, Circuit Breaker D08 A

Recirculation Pump 2A Discharge Bypass N/A Valve, 2-B32-F032A, Circuit Breaker DF3 A

LPCI Inboard Injection Valve, N/A 2-E11-F015A, Circuit Breaker DFS A

LPCI Outboard Injection Valve, El 2-E11-F017A, Circuit Breaker N/A DGO A

Suppression Pool Discharge Isolation

, gig Valve 2-E11-F028A, Circuit ' Breaker N/A Non-Safe Shutdown Loads Compt.

Clearance Number Component Description Open Issued N/A l

t i

I t

t I

l I

h, BSEP-2/ASSD-01 Page 28 of 128 Rev. 0

TABLE 2 (Cont'd)

G EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XB Normal Power Supply:

480V Substation E8 Compt. A02 Alternate Power Supply:

N/A Location:

Reactor Building - El 20' - South s

Safe Shutdown loads Compt.

SSD Ind i nd Number Train Component Description Open Ver Closed Yer DK1 B

Recirculation Pump 2B Suction Valve, N/A 2-832-F023B, Circuit Breaker

  • DK6 B

RHR System Divisional Cross-tie Isola-tion Valve, 2-E11-F010, Circuit Breaker N/A N/A N/A N/A DK8 B

RHR HX 2B Outlet Valve, 2-E11-F003B, Circuit Breaker N/A

{l DK9 8

RHR Pump 2B Suppression Pool Suction Valve, 2-E11-F004B, Circuit Breaker N/A DL0 B

RHR Pump 2D Suppression Pool Suction g

Valve, 2-E11-F004D, Circuit Breaker N/A

  • DL1 B

RHR Pump 28 Shutdown Cooling Suction N/A Valve, 2-E11-F006B, Circuit Breaker

  • DI.2 B

RHR Pump 2D Shutdown Cooling Suction N/A Valve, 2-E11-F0060 Circuit Breaker DL3 8

RHR Minimum Flow Bypass Valve, N/A 2-E11-F007B, Circuit Breaker DLS B

RCIC Turbine Exhaust Vacuum Breaker N/A Valve, 2-E51-F066, Circuit Breaker

  • DL6 B

RHR HX 2B Drain To Suppression Pool Valve, 2-E11-F0118, Circuit Breaker N/A DL8 B

Drywell Spray Outboard Isolation Valve, 2-E11-F016B, Circuit Breaker N/A

  • NOTE:

Shutdown Cooling Suction Valves, 2-E11-F006B and 2-E11-F006D, RHR Divisional Cross-tie Isolation Valve, 2-E11-F010, and Rm HX 28 Drain To Suppression Pool Valve, 2-E11-F011B are normally under a Shif t Foreman's clearance when the unit

< h, is operating.

The Shift Foreman may remove this clearance at his discretion when it has been verified that maintenance on the valves is not in progress.

BSEP-2/ASSD-01 Page 29 of 128 Rev. O

TABLE 2 (Cont'd) g EMERGENCf POWER SYSTEM AC Safe Shutdown Component:

Reacter Building MCC 2XB Safe Shutdown Loads (Con't)

Compt.

550 Ind

nd Number Train Component Description Open Ver Closed Ver DN B

Drywell Spray Inboard Isolati'on Valve, N/A 2-E11-F021B, Circuit Breaker DM1 B

RHR Service Water Booster Pumps B And N/A D Inboard Isolation Valve, 2-SW-V105, Circuit Breaker DM2 B

Suppression Pool Cooling Isolation N/A Valve, 2-E11-F024B, Circuit Breaker

  • DM3 B

RHR HX 2B Drain to RCIC Valve, N/A N/A N/A N/A 2-E11-F026B, Circuit Breaker DM4 B

Suppression Pool Spray Isolation N/A Valve, 2-E11-F027B. Circuit Breaker gg DM6 B

Service Water To RHR Service Water N/A

(?)

Header Cross-tie Valve, 2-SW-V102, Circuit Breaker DM7 B

RHR HX 2B Inlet Valve, 2-E11-F047B, N/A Circuit Breaker DMB B

RHR HX Bypass Valve, 2-E11-F048B, N/A Circuit Breaker

  • DM9 B

LPCI Injection Check Valve Bypass N/A Valve, 2-E11-V33, Circuit Breaker DN1 B

RHR HX B Service Header Outlet Valve, N/A 2-E11-PDV-F068B, Circuit Breaker DN2 B

RHR SW Outboard Injection N/A Valve, 2-E11-F073, Circuit Breaker

  • NOTE:

RHR HX 2B Drain to RCIC Valve, 2-E11-F026B and LPCI Injection Check Valve Bypass Valve, 2-E11-V33 are normally under a Shift Foreman's clearance when the unit is operating.

The Shif t Foreman may remove this clearance at his discretion when it 3

has been verified that maintenance on the valves is not in progress.

Qi BSEP-2/ASSD-01 Page 30 of 128 Rev. O

TABLE 2 (Cont'd) h EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XB Safe Shutdown loads (Cont'd)

Compt.

SSD Ind Ind Number Train Component Description Open Ver Closed Ver DN3 B

RHR SW Inboard Injection N/A Valve, 2-E11-F075 Circuit Breaker DN6 B

RHR Pump 2B & PC Suppression Pool N/A Suction Valve, 2-E11-FU20B, Circuit Breaker DN9 B

RHR HX B Service Water Discharge N/A Valve, 2-E11-F002B, Circuit Breaker OP2 B

Nuclear Service Water To Vital Header N/A R1 Inboard Isolation Valve, 2-SW-V11/,

Circuit Breaker

  • DP3 B

Shutdown Cooling Inboard Suction N/A o.

Isolation Valve, 2-E11-F009, Circuit G

Breaker UP7 8

Vent RHR HX Area Cooling Fan, N/A 2B-FCU-RB, Circuit Breaker DQ0 A

HPCI Turbine Exhaust Vacuum Breaker N/A N/A N/A N/A Valve, 2-E41-F079, Circuit Breaker Non-Safe Shutdown Loads Compt.

Clearance Number Component Description Open Issued BN9 Primary Containment Atmosphere Radiation lionitor, 2-CAC-AT-1260, Circuit Breaker

  • NOTE:

Shutdown Cooling Inboard Suction Isolation Valve, 2-E11-F009 is normally under a Shift Foreman's clearance when the unit is operating.

The Shift Foreman may remove this clearance at his discretion when it has been verified that maintenance on the valve is not in progress.

G BSEP-2/ASSD 01 Page 31 of 128 Rev. 0

TABLE 2 (Cont'd)

EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XB Non-Safe Shutdown Loads (Cont'd)

Compt.

Clearance Number Component Description Open Issued DN4 RHR HX 2B Outboard Vent Valve, 2-E11-F103B, Circuit Breaker DNS RHR HX 2B Inboard Vent Valve, 2-E11-F1048, Circuit Breaker DP1 Recirculation Pump 2B Seal Water Injection Valve, 2-B32-V30, Circuit Breaker DP8 Reactor Building-Off Gas Drain Tank Pump B, 2-G16-C0408, Circuit Breaker DP9 TBCCW HX Service Water Header R

Inboard Isolation Valve, 2-SW-V3, Circuit Breaker

("??

EF5 Reactor Building Personnel Decontam-ination Room Hot Water Heater Circuit Breaker Disconnect Switch 9KVA 30 480-208Y/120V Transformer G_

BSEP-2/ASSD-01 Page 32 of 128 Rev. 0

TABLE 2 (Cont'd) 9 VS!

EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XB-2 Normal Power Supply:

480V Substation E6 Compt. AV8 Alternate Power Supply:

N/A Location:

Reactor Building - El. 20' - South Safe Shutdown Loads Compt.

SSD Ind inc _

Number Train Component Description Open Ver Closed Ver DK2 B

Recirculation Pump 2B Discharge Valve s N/A 2-B32-F031B,' Circuit Breaker DK3 B

Recirculation Pump 2B Discharge Bypass N/A Valve, 2-B32-F032B, Circuit Breaker DL7 B

LPCI Inboard injection Valve, N/A 2-E11-F0158, Circuit Breaker DL9 B

LPCI Outboard Injection Valve, 2-E11-F017B, Circuit Breaker N/A DHS B

Suppression Pool Discharge Isolation 6

g5 j.,

Valve, 2-E11-F0288, Circuit Breaker N/A nw Non-Safe Shutdown loads Compt.

Clearance Number Component Description Open Issued N/A 1

h BSEP-2/ASSD-01 Page 33 of 128 Rev. 0

TABLE 2 (Cont'd) h EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Reactor Building HCC 2XC Normal Power Supply:

480V Substation E7 Compt. AYO Alternate Power I,upply:

N/A Location:

Reactar Building - El. 20' - East safe Shrtdown Loads Compt.

SSD Ind ind Number Train Comporent Description Open Ver Closed Ver DS1 A

Compt. 2-DS1 Hotor 2-KH4 HPCI Steam Supply Line Isol. Viv. 2-E41-F002 N/A ASSD Feed DS3 A

HSL Inboard Drain Isolatie Valve, N/A 2-B21-F016, Circuit Breaker DS4 B

RCIC Steam Supply Inboard Isolation N/A Valve, 2-ES1-F007. Circuit Breaker N/A N/A DT2 A

Compt. 2-DT2 Hotor 2-RR6 HPCI Turb.

Vac. Bresker Viv. 2-E41-F079 N/A ASSD 'eed k

imD DT9 A

RWCV Inlet Inboard Isolation Valve, 2-G31-F001, Circuit Breaker N/A Non-Safe Shutdown Loads Compt.

Clearance Number Component Description Open Issued DS5 Feedwater Line A Isolation Valve, 2-B21-F032A, Circuit Breaker DS6 Containment Atmospheric Honitoring Cabinet Vacuum Pump AT-1259 DS7 Vent Core Spray Pump Area Cooling Fan, 2C-FCU-RB, Circuit Breaker DS8 Recirculation Pump 2A Hotor Heater Circuit Breaker DS9 Core Spray Pump A Suppression Pool Suction Valve, 2-E21-F001A, Circuit Breaker b

BSEP-2/ASSD-01 Page 34 of 128 Rev. O i

a m.

TABLE 2 (Cont'd) 49 EMER6 MCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XC Non-Safe Shutdown Loads (Cont'd)

Compt.

Clearance Number Component Description Open Issued DT0 Core Spray Outboard Injection Valve, 2-E21-F004A, Circuit Breaker DT1 Core Spray Inboard injection Valve, 2-E21-F005A, Circuit Breaker DT3 Core Spray Full Flow Test Bypass Valve, 2-E21-F015A, Circuit Breaker DT4 Core Spray M'.nimum Flow Bypass Valve, 2-E21-F031 A, Circuit Breaker DT5 Welding Receptacia (Elev. 20'-0") 480V 30 RI DT6 "3CCW Drywell Supply Header Valve, 2-RCC-Y52, Circuit Breaker

([$}

DT7 RBCCW Drywell Discharge Header Valve, 2-RCC-Y28, Circuit Breaker DT8 Reactor Building Floor Drain Sump Pump B 2-G16-C001B, Circuit Breaker DU1 Standby Air Compressor 2A Circuit Breaker DU2 Welding Receptacle (Ele. (-) 17'-0")

480V 30 DU7 Miscellaneous 120V AC Distribution Panel 2DXA Supply Breaker EV3 Hoist Motor 2MR7 (Elev. -20'-0")

Disconnect Switch 9KVA 30 480-208Y/120V Transformer O

BSEP-2/ASSD-01 Page 35 of 12')

Rev. 0

e)

TABLE 2 (Cont'd)

NI EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2X0 Normal Power Supply:

480V Substation E8 Compt. A08 Alternate Power Supply:

N/A Safe Shutdown loads Compt.

550 I nd Ind Number Train Component Description Open Ver Closed Ver DW1 A

HPCI Steam Supply Inboard Isolation N/A N/A N/A Valve, 2-E41-F002, Circuit Breaker DW2 B

Compt. 2-0W2 Motor 2-RR7 RCIC Turb.

N/A Vac Breaker Viv. 2-E51-F062 ASSO Feed

  • 0X5 8

Compt. 2-0X5 Motor 2-KM2 RHR Suction N/A

! sol. Viv. 2-E11-F009 ASSO Feed DX9 A

Compt 2-0X9 Motor 2-KE3 NSSS Mn Stm N/A N/A N/A Drn Line Viv 2-821-F016 ASSD Feed DY1 B

Compt. 2-0Y1 Motor 2-KS8 RCIC Steam N/A Supply Line Isol. Viv. 2-E51-F007

({}

ASSO Feed g

03A B

Compt. 2-03A Service 2-GB6 Battery N/A g

Charger 28-1 Alternate Feed 038 B

Compt 2-03B Service 2-GB7 Battery N/A Charger 2B-2 Alternate Feed Non-Safe Shutdown loads Compt.

Clearance Number Component Description Open issued DV9 Miscellaneous 120V AC Distribution i

20XB Supply Breaker DW3 Core Spray Pump B Suppression Pool Suction Valve, 2-E21-F001B, Circuit Breaker

  • NOTE:

RHR Suction Isolation Valve, 2-E11-F009, is normally under a Shif t Foreman's clearance when the unit is operating.

The Shift Foreman may remove this clearance at his discretion when it has been verified that maintenance on the km.,J valve is not in progress.

BSEP-2/ ASS 0-01 Page 36 of 128 Rev. O i

p TABLE 2 (Cont'd)

V EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Reactor Building MCC 2XD Non-Safe Shutdown Loads (Cont'd)

Compt.

Clearance Number Component Description Open Issued DWS Core Spray Outboard Injection Valve, 2-E21-F004B Circuit Breaker DW6 Core Spray Inboard Injection Valve, 2-E21-F005B, Circuit Breaker DW8 Core Spray Full Flow Test Bypass Valve, 2-E21-F015B, Circuit Breaker DW9 Core Spray Pump B Minimum Flow Bypass Valve, 2-E21-F031B, Circuit Breaker DXO Feedwater Line B Isolation Valve, 2-B21-F032B, Circuit Breaker R

DX2 Vent Core Spray Pump Area Cooling Fan, (g) 2D-FCU-RB, Circuit Breaker DX3 Recirculation Pump 2B Hotor Heater Circuit Breaker DX4 Suppression Pool 2 Inch Purge Exhaust Valve, 2-CAC-V22, Circuit Breaker DX6 Welding Receptacle (Ele. 20'-0") 480V 30 DX7 Reactor Building Equipment Drain Tank Pump A, 2-G16-C006A, Circuit Breaker DX8 Standby Air Compressor 2B Circuit Breaker DYO Welding Receptacle (Elev. -17' 0")

480V 39 Disconnect Switch 9KVA 39 480-208Y/120V Transformer b

BSEP-2/ASSD-01 Page 37 of 128 Rev. 0

TABLE 2 (Cont'd)

EMERGENCY POWER SYSTEM AC Safe Shutdown Component:

Diesel Generator Building MCC DGA Normal Power Supply: 480V Substation E5 Compt. AU6 Alternate Power Supply:

N/A Location:

Diesel Generator Building - Diesel Generator Cell 1 Safe Shutdown Loads Compt.

SSD Ind Ind Number Train Component Description Open Ver Closed Ver DQ7 A

Diesel Generator No.1 Crarkease N/A Vacuum Blower Circuit Breaker DR1 A

Diesel Generator No.1 Starting Air N/A Compressor 2 Circuit Breaker DR4 A

Diesel Generator No. 1 Fuel Oil N/A Transfer Pump 1B Circuit Breaker DR6 A

Exhaust Fan E-EF-DG Circuit Breaker N/A D37 A

Diesel Generator No.1 Fuel Oil N/A Transfer Pump 1A Circuit Breaker R

khI'[

038 A

Diesel Generator No.1 Starting Air N/A Compressor 1 Circuit Breaker D44 A

Service Water Valve,1-SW-V255, N/A Circuit Breaker D45 A

Emergency 120V AC Distributing Panel N/A 1A-LG Supply Breaker EB9 A

Jacket Water Cooler M0 Supply N/A Isolation Valve, 2-SW-V210, Circuit Breaker ECO A

Jacket Water Cooler M0 Supply N/A*

Isolation Valve,1-SW-Y210, Circuit Breaker Non-Safe Shutdown loads Compt.

Clearance Number Component Description Open issued DQ3 Diesel Generator No.1 Fuel Oil Booster Pump Circuit Breaker k.

DQ4 Diesel Generator No.1 Filter And Prelube Pump Circuit Breaker BSEP-2/ASSD-01 Page 38 of 128 Rev. 0

TABLE 2 (Cont'd)

EMERGENGY POWER SYSTEM AC g

Safe Shutdown Component:

Diesel Generator Building MCC DGA Non-Safe Shutdown Loads (Cont'd)

Compt.

Glearance Number Com onent Description Open Issued DQS-

. Diesel Generator No.1 Jacket Water Pump Circuit. Breaker 006 Diesel Generator No.1 Jacket Water Heater Pump Circuit Breaker M8 Diesel Generator No.1 Barring Gear Circuit Breaker DQ9 Diesel Generator No.1 Crankcase Drain /

Fill Pump Circuit Breaker D.R0 Diesel Generator No.1 Lube,011 Filter Heater Circuit Breaker F

DR2 Diesel Generator No.1 Auxiliary Lube Oil Pump Circuit Breaker DR7 Supply Fan A-SF-DG Circuit. Breaker (w>.

D39 Diesel Generator No.1 Jacket Water Heater Circuit Breaker D40 Exhaust Fan A-EF-DG Circuit Breaker D41 Exhaust Fan L-EF-DG Circuit Breaker 042 Exhaust Fan N.EF-DG Circuit Breaker EB7 Smoke Removal Fan 2A-SFSR-DG Circuit Breaker EBB Service PS2 Rolling Door Disconnect Switch 9XVA 30 480-20BY/120V Transformer V,

BSEP-2/ ASSD-01 Page 39.of 12B Rev. O

TABLE 2 (Cont'd)

EMERGDRTPDWER SYSTEM AC

@W Safe Shutdown Component:

Diesel Generator Building MCC DGB

)

Normal Power Supply:

480V Substation E6 Cont. AV9 Alternate Power Supply:

N/A Location:

Diesel Generator Building - Diesel Generator Cell 2 Safe Shutdown Loads compt.

550 Ind Inc humber Trafn Component Description Open Ver Closed Ver DY6 B

Diesel Generator No. 2 Crankcase Vacuum Blower circuit Breaker N/A DZ5 B

Diesel Generator No. 2 Starting Air Compressor 2 Circuit Breaker N/A DZB B

Diesel Generator No. 2 Fuel Oil Transfer Pump 28 Circuit Breaker '

N/A D89 8

Emelgency 120V AC Distribution Panel 18-DG Supply Breaker N/A D94 5

Diesel Generator No. 2 Starting Air gf3' Compressor 1 Circuit Breaker p

D95 B

Diesel Generator No. 2 Fuel 011 N/A (h

Transfer Pump 2A Circuit Breaker D99 8

Exhaust Fan F-EF-DG Circuit Breaker N/A EC3 B

Diesel Generator No. 2 Jacket Water Cooler Supply Isolation Valve, N/A 2-SW-V211, Circuit Breaker EC4 B

Diesel Generator No. 2 Jacket Water Cooler Supply Isolation Valve, N/A 1-SW-V211 Circuit Breaker Non-Safe Shutdown Loads togt.

clearance Number Component Description Open Issued A51 Distribution Panel, 2-FB-2, Supply Breaker DY2 Diesel Generator No. 2 Fue) 011 Booster Pump Circuit Breaker DY3 Diesel Generator No. 2 Filter And Prelube Pump Circuit Breaker BSEP-2/ASSD-01 Page 40 of 128 Rev. O

TABLE 2 (Cont'd)

EMERr.NGT PUWER SYSTEM AC

(} Safe Shutdown Component: Diesel Generator Building MCC DGB. Non-Safe Stutdown Loads (Cont'd) Compt. Clearance Number Component Description Dpen Issued DY4 Diesel Gen'erator No. 2 Jacket Water Pump Circuit Breaker

DYS,

, Diesel Generktor No. 2 dacket Water Heater Pump Circuit Breaker DY7 Diesel Generator No. 2 Barring Gear Circuit Breaker DY8 Diesel Generator No. 2 Crankcase Drain / Fill Pump Circuit Breaker DY9 Diesel Generator No. 2 Lube Oil Filter Heater Circuit Breaker g DZ6 Diesel Generator No. 2 Auxiliary Lube 011 Pump Circuit Breaker k'?{} DZ9 Vent Supply Air Fan B-SF-DG Circuit Breaker D91 Swgr. Room Exhaust Fan B-EF-DG Circuit Breaker D92 Swgr. Room Exhaust Fan J-EF-DG Circuit Breaker D93 Diesel Generator No. 2 Jacket Water Heater Circuit Breaker EC1 Smoke Removal Fan 28-SFSR-DG Circuit Breaker i l Disconnect Switch 9KVA 30 4BO-20BY/120V Transformer i l ($.) BSEP-2/ASSD-01 Page 41 of 128 Rev. 0

TABLE 2 (Cont'd) p(9 EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Diesel Generator Building MCC DGC Normal Power Supply: 480V Substation E7 Compt. Ai8 Alternate Power Supply: N/A Location: Diesel Generator Building - Diesel Generator Cell 3 Safe Shutdown Loads i C;wnpt. SSD Ind Ind 1 humber Train Component Description Open Ver Closed Ver l 017 A Diesel Generator No. 3 Crankcase N/A Vacuum Blower Circuit Breaker DJ1 A Diesel Generator No. 3 Starting Air N/A Compressor 2 Circuit Breaker DJ4 A Diesel Generator No. 3 Fuel Oil N/A Transfer Pump 2 Circuit Breaker DJ6 A Exhaust Fan G-EF-DG Circuit Breaker N/A i 3 002 A Diesel Generator No. 3 Fuel Oil N/A Transfer Pump 1 Circuit Breaker RI h D03 A Diesel Generator No. 3 Starting Air N/A Compressor 1 Circuit Breaker r 009 A Emergency 120V AC Distribution Panel N/A 4 2A-DG Supply Breaker EF2 A Diesel Generator No. 3 Jacket Water N/A Cooler Supply Isolation Valve, 2-SW-Y212, Circuit Breaker Er3 A Diesel Generator No. 3 Jacket Water N/A Cooler Supply Isolation Valve, 1-SW-V212. Circuit Breaker i Non-Safe Shutdown (cads Compt. clearance [ Number Component Description Open Icsued 013 Diesel Generator No. 3 Fuel Oil Booster i Ptmp Circuit Breaker D14 Diesel Generator No. 3 Filter And Prelube Pump Circuit Breaker ) b.. BSEP-2/ASSD-01 Page 42 of 128 Rev. 0 i

TABLE 2 (Cont'd) 'r EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Diesel Genera.or Building MCC DGC Non-Safe Shutdown Loads (Cont'd) Compt. Clearance Number _ Component Description Open Issued D15 Diesel Generator No. 3 Jacket Water Pump Circuit Breaker 016 Diesel Generator No. 3 Jacket Water Heater Pump Circuit Breaker D18 Diesel Generator No. 3 Barring Gear Circuit Breaker DI9 Diesel Generator No. 3 Crankcase Drain / Fill Pump Circuit Breaker DJO Diesel Generator No. 3 Lube Oil Filter Heater Circuit Breaker DJ2 Diesel Generator No. 3 Auxiliary Lube k g

  • Oil Pump Circuit Breaker N7 Supply Fan C-SF-DG Cire.:it Breaker DM Diesel Generator No. 3 Jacket Water Heater Circuit Breaker DOS Exhaust Fan C-EF-DG Circuit Breaker 006 Exhaust Fan K-EF-DG Circuit Breaker D07 Smoke Removal Fan ' C-SFSR-DG Circuit e

Breaker i EF0 Diesel Building Sump Pump 2G-2 Circuit l Breaker EF1 Service PS4 Rolling Door Disconnect Switch 9KVA 30 480-208Y/120V Transformer b BSEP-2/ASSD-01 Page 43 of 128 Rev. O

TABLE 2 (Cont'd) EMERraLNCY POWER SYSTEM AC (;h Safe Shutdown Component: Diesel Generator Building MCC DGD

  • f Normal Power Supply:

480V Substation E8 Conpt. A01, A1, ternate Power Supply: N/A Location:. Diesel Generator Building'- Diesel Generator Cell 4 Safe Shutdown Loads Compt. 550 Ind Ind Number Train C4onent Description Open .Ver Closed Ver 04 9 B Emergenef 120V AC Distribution Panel 28-DG Supply Breaker N/A i 054 8 Diesel Generator No. 4 Starting Air Compressor 1 Circuit Breaker N/A 055 B Diesel Generator No. 4 Fuel Oil NM Transfer Pump 4A Circuit Breaker 3 059 B Exhaust Fan H-EF-DG Circuit Breaker D60 B Diesel Generator No. 4 Crankcase N/A-Vacuum Blower Circuit Breaker p D64 B Diesel Generator No. 4 Starting Air N/A Compressor 2 Circuit Breaker

b-..

D67 B Diesel Generator No. 4 Fuel 011 Transfer Pump 4B Circuit Breaker N/A EF4 B Service Water Valve 2-SW-Y255, Circuit Breaker N/A EF6 B Diesel Generator No. 4 Jacket Water N/A Cooler M0 Supply Isolation Yalve, 2-SW-V213. Circuit Breaker EF7 B Diesel Generat.or No. 4 Jacket Water Cooler Supply 1 solation Yalve, sfg 1-SW-V213. Circuit Breaker f Non-Safe Shutdown Loads conet. Uh'Tiance Compon' nt Description Open Issued Number e B06 Distribution Panel 2-FB-1 Supply Breaker D2A Off Gas Stacc Rad Mon Building (~) Distribution Panel Supply Breaker BSEP-2/ASSD-01 Page 44 of 128 Rev. 0

TABLE 2 (Cont'd) EMERGENGT POWER ' SYSTEM AC g Safe Shutdown Component: Diesel Generator Building MCC DGD Non-Safe Shutdown Loads (Cont'd) Compt. Clearance Number Component Description Open Issued D43 Diesel Generator No. 4 Jacket Water Pump Circuit Breaker ~ D46 Service No 6 Diesel Generator No. 4 'Cond Receiver Pump D47 Diesel Generator No. 4 Fuel Oil Booster 1 Pump Circuit Breaker D48 Diesel Generator No. 4 Filter And Prelube Pump Circuit Breaker D50 Diesel Generator No. 4 Jacket Water Heater Pump Circuit Breaker 051 Exhaust Fan D-EF-DG Circuit Breaker D52 Exhaust Fan M-EF-DG Circuit Breaker 053 Diesei Generator No. 4 Jacket Water Heater Circuit Breaker 057 Smoke Removal Fan 2D-SFSR-DG Circuit Breaker D61 Diesel Generator No. 4 Barring Gear Circuit Breaker - D62 Diesel Generator No. 4 Crankcase Drain / Fill Pump Circuit Breaker D63 Diesel Generator No. 4 Lube Oil Filter Heater Circuit Breaker 06 5 Diesel Generator No. 4 Auxiliary Lube Oil Pump Circuit Breaker l D66 Diesel Butiding Sump Pump 2G-1 C1heuit 1 Breaker I L D68 Supply Fan D-SF-DG Circu't Breaker l (In c. l BSEP-2/ASSD-01 Page 45 of 128 Rev. 0 +

TABLE 2 (Cont'd) EMERst.McY POWER SYSTEM AC (3) S , afe Shutdown Component: Diesel Generator Building MCC DGD Non-Safe Shutdown Loads (Cont'd) conpt. Clearance Number Component Description Open Issued D69' Service No 5 Cond Receiver Pump.A-CRP-DG - Disconnect Switch 9KVA 39 480-208Y/120Y Transformer e @i D l +r v BSEP-2/ASSD-01 Page 46 of 128 Rev. O i l

TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Control Building MCC 2CA Normal Power Supply: 480V Substation E7 Compt AX6 Alternate Power Supply: N/A Location: Control Building - E1. 23' - Cable Spread Area Safe Shutdown loads Corp t. 55D Ind 1 Ind Number Train Component Descr,ption Open Yer Clo,ed(Ver C05 A Battery Charger 2A-1 AC Input Breaker C06 A Battery Charger 2A-2 AC Input Breaker C07 A UPS 2A (Primary Power Converter input N/A Breaker) C10 A RPS M-G Set 2A Control Panel N/A 2-C72-5001A Circuit Breaker C29 A UPS 2A Heater Circuit Breaker N/A C77 A Emerge,1cy 120V AC Distribution Panel 32A Supply Breaker N/A R h Non-Safe Shutdown Loads Conpt. Clearance Number Component Description Open Issued C03 Air Cooler Condenser Fan, 20-CV-CB Circuit Breaker C04 Control Room Supply Fan, 2D-SF-CB, Circuit Breaker C08 Control Building Floor Drain Sump Pump, 2-G16-2E-2, Circuit Breaker C09 Control Building Heating Coil, 2A-EHC-CB, Circuit Breaker C11 Conventional 120V AC Distribution Panel 2G-CB Supply Breaker C12 Lighting Distribution Transfo'mer, 2CEl, Circuit Breaker C13 Floor Drain Filter Holding Pump C.t G16-C017 BSEP-2/ASSD-01 Page 47 of 128 Rev. 0

TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC ((i. Safe Shutdown Component: Control Building MCC 2CA Non-Safe Shutdown Loads (Cont'd) Compt. Clearance Number Component Description Open Issued C14 Waste Collector Filter Holding Pump Circuit Breaker C16 Control Building Standby Instrument Air Conpressor 2B-AC-CB, Circuit Breaker Control Bukiding Floor Drain Sump Pump, C17 2-G16-2E-1, Circuit Breaker C18 Cable Spreading Room Exhaust Fan, 2A-EF-CB, Circuit Breaker C19 Cable Spreading Room Supply Fan, 2A-SF-CB, Circuit Breaker C20 Battery Room 2A Exhaust Fan, 2C-EF-CB, Circuit Breaker R ~( ;,. C21 Battery Room 2A Supply' Fan, 2C-SF-CB, Circuit Breaker C22 Mechanical Equipment. Room Exhaust Fan, 2E-EF-CB, Circuit Breaker C23 Control Room Emergency Recirculation Fan, 2A-ERF-CB, Circuit Breaker C26 Elevator C27 Mechanical Equipment. Room Electrical Heating Unit, 2A-EHC-CB Circuit Breaker C28 Fuel Pool F/D Holding Pump 2A Circuit Breaker C30 UPS 2A Switching Bay Heater Circuit Breaker C32 Control Building Mechanical Room Booster Fan, 2A-BF-CB, Cir:uit Breaker Disconnect Switch 9KVA 30 480 208Y/120Y Transformer l BSEP-2/ASSD-01 Page 48 of 128 Rev. O

TABLE 2 (Cont'd) g EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Control Building MCC 2CB Normal Power Supply: 480V Substation E8 Compt. A09 Alternate Power Supply: N/A Location: Control Building - El. 23' - Cable Spread Area Safe Shutdown Loads Compt. SSD Ind I nd Number Train Component Description Open Ver Closed Yer C52 B RPS MG Set 2B Control Panel, N/A 2-C72-S001B, Circuit Breaker C56 B Compt. 2-C56 Service 2-GB7 Battery N/A Charger 28-2 Normal Feed C57 8 Compt. 2-C57 Service 2-GB6 Battery Charger 28-1 Normal Feed N/A C78 B Emergency 120V AC Distribution Panel 32B Supply Breaker N/A Non-Safe Shutdown Loads Compt. Clearance R[ Number Component Description Open Issued C34 Welding Receptacle 480V 30 C38 Mechanical Equipment Room Supply Fan, 2F-SF-CB, Circuit Breaker C40 Control Room Exhaust Fan, 20-EF-CB, Circuit Breaker C41 Conventional 120V AC Distribution Panel, 2H-CB, Supply Breaker C42 Battery Room Exhaust Fan, 28-EF-CB, Circuit Breaker C43 Battery Room 2B Supply Fan, 28-SF-CB, Circuit Breaker C44 Control Room Emergency Recirculation i Fan, 2B-ERF-CB, Circuit Breaker C45 Condensate Filter Demin 2A Holding Pump Circuit Breaker RSEP-2/ASSD-01 Page 49 of 128 Rev. O

TABLE 2 (Cont'd) EMERGENGY POWER SYSTEM AC Gj Safe Shutdown Component: Control Building MCC 2CB Non Safe Shutdown Loads (Cont'd) Comp t. Glearance Number Component Description Open Issued C46 Condensate Filter Demin 2B H61 ding Pump Circuit Breaker C47 Condensate Filter Demin 2C Holding Pump Circuit Breaker C48 Condensate Filter Demin 2D Holding Pump Circuit Breaker C50 Fuel Pool Filter Demin Holding Pug 28 Circuit Breaker CSI UPS 2B Heater Circuit Breaker R C53 Control Building Heating coil, 28-EHC-CB. Cir 'it Breaker C55 UPS 2B (Standby Power Converter g. Input Breaker) C58 Air Cooled Condensing Fan. 2E-CU-CB, Circuit Breaker C59 Control Room Spare Supply Fan, 2E-SF-CB, Circuit Breaker C79 UPS Static Transfer Switch Circuit Breaker (UPS Reserve Source)

81 Computer Room Air Conditioning Unit 2 2-AC-CR-CB, Circuit Bre'aker

)isconnect Switch 9KVA 30 480-208Y/120V Transformer .K, v BSEP-2/ASSD-01 Page 50 of 128 Rev. 0 l I 1

TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC {J Safe Shutdown Component: Service Water Intake ' Structure MCC 1PA Normal Power Supply: 480V Substation E5 Compt. AU3 Alternate Power Supply: N/A Location: Service Water Building - E1. 20' - NW Safe Shutdown Loads compt. ssp Ind Ind Number Train Component Description Open Yer Closed Yer BU4 A Nuclear Service Water Pump 1A Dis-charge Strainer Motor Circuit Breaker N/A BUS A Conventional Service Water Pump 18 Discharge Strainer Motor Circuit Breaker N/A BU6 A Nuclear Service Water Pump 1A Discharge Valve,1-SW-V19, Circuit N/A Breaker BU7 A Conventional Service Water Pump 18 Discharge Valve To Conventional N/A Header,1-SW-Y15 Circuit Breaker h BU8 A Conventional Service Water Pump 18 Discharge Valve To Nuclear Header, N/A 1-SW-V16, Circuit Breaker BU9 A Conventional Service Water Pump 2C Discharge Valve To Nuclear Header, 2-SW-V18, Circuit Breaker N/A BVD A Conventional Service Water Pump 2C Discharge Valve To Conventional Header, 2-SW-V17 Circuit Breaker N/A BV1 A Conventional Service Water Pump 2C Discharge Strainer Motor Circuit gjg Breaker BV2 A Service Water tube Water Pump 1A ufA Circuit Breaker BV4 A Emergency 120V AC Distribution Panel N/A 1A-SW Supply Breaker h N BSEP-2/ ASSD-01 Page' 51 of 128 Rev. O

TABLE 2 (Cont'd) G EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Service Water Intake Structure MCC 1PA Non-Safe Shutdown Loads Compt. Clearance Number Component Description Open Issued BV7 Motor 1-PV5 Bldg Drainage Serv Water Intk Struct Sump Pump 20-2 BV8 Motor 1-KY3 Serv Water To CWP Brgs Pri Isol Viv-11-SW-V36 BV9 Screen Wash Water Service Water Traveling Screen, SCW-1A, Circuit Breaker BW1 Service Water To Chlorination System Outboard Isolation Valve,1-SW-V294, Circuit Breaker Disconnect Switch 9KVA 39 480-208Y/120V Transformer il ) h BSEP-2/ ASS 0-01 Page 52 of 128 Rev. O

TABLE 2 (Cont'd) ..,G EMERGENCY POWER SYSTEM AC { Safe Shutdown Component: Service Water Intake Structure MCC 1PB Normal Power Supply: 480V Substation E6 Compt. AW3 Alternate Power Supply: N/A Location: Service Water Building - El 20' - West Safe Shutdown Loads Compt. SSD Ind ind Number Train Component Description Open Ver Closed Ver BX1 B Service Water Lube Water Pump 1B Circuit Breaker N/A BX8 B Conventional Service Water Pump 1C Discharge Valve To Conventional Header,1-SW-V17, Circuit Breaker N/A. BX9 B Conventional Service Water Pump 1C Discharge Valve To Nuclear Header, gfg E. 1-SW-V18, Circuit Breaker BYO B Nuclear Service Water Pump 1B Discharge Valve, 1-SW-V20, gfg g Circuit Breaker BY1 B Conventional Service Water Pump 1C Discharge Strainer Motor Circuit n/A Breaker I BY2 B Nuclear Service Water Pump 1B l Discharge Strainer Motor N/A l Circuit Braaker l Non-Safe Shutdown loads Compt. Clearance Number Component Description Open issued BY9 Emergency 120V AC Distribution Panel 18-SW Supply Breaker BX2 Service Water To Chlorination System Outboard Supply Valve,1-SW-Y295, Circuit Breaker BX3 Service 1-MR5 Welding Receptacle 480V 30 @) lBX4 Screen Wash Water Service Water Traveling Screen, SCW-1B, Circuit Breaker BSEP-2/ASSD-01 Page 53 of 128 Rev. O

1 TABLE 2 (Cont'd) EMERGDICT7DWER SYSTEM AC j (}jL' Safe Shutdown Component: Service Water Intake Structure MCC 1PB Non-Safe Shutdown Loads (Cont'd) Compt. Clearance Number Component Descr.iption Open Issued 1 Ventilation Pump ' ouse Exhaust Fan, 816 H 1A-EF-SWIS, Circuit Breaker SK) Service Water To Circu1~ating Water Pumps' Bearing Lubricating Water Supply Valve,1-SW-V37, Circuit Breaker L Disconnect i Switch 9KVA 39 480-208Y/120V Transformer ( ) (b! I l I t 1 1 I k '$ i BSEP-2/ASSD-01 Page 54 of 128 Rev. 0

p"s TABLE 2 (Cont'd) b EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Service Water Intake Structure MCC 2PA Normal Power Supply: 480V substation E7 Compt. AYS Alternate Power Supply: N/A Location: Service Water Building - El. 20' - SW Safe Shutdown loads Compt. SSD I nd l nd Number Train Component Description Open Yer Closed Ver E04 A Nuclear Service Water Pump 2A Dis-N/A charge Strainer Motor Circuit Breaker E05 A Conventional Service Water Pump 2A Discharge Strainer Motor Circuit N/A Breaker E06 A Nuclear Service Water Pump 2A Dis-charge Valve, 2-SW-V19, Circuit N/A Breaker k E07 A Conventional Service Water Pump 2A Discharge Valve To Conventional N/A c% Header, 2-SW-V13 Circuit Breaker d+. E08 A Conventional Service Water Pump 2A N/A Discharge Valve To Nuclear Header, 2-SW-V14 Circuit Breaker E12 A Service Water Lube Water Pump 2A, gjg Circuit Br3aker E14 A Emergency 120V AC Distribution Panel N/A 2A-SW Supply Breaker Non Safe Shutdown Loads Compt. Clearance Number Component Description Open Issued E09 Service Water To Chlorination System Outboard Isolation Valve, 2-SW-V294, Circuit Breaker BSEP-2/ASSD-01 Page 55 of 128 Rev. O i

TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Service Water Intake Structure MCC 2PA Non-Safe Shutdown loads (Cont'd) Comp t. Clearance Number Component Description Open Issued E15 Ventilation Pump House Fan Supply 2A-SF-SWIS, Circuit Breaker E17 Motor 2-PXO Bldg Drn Serv Wtr Intake Struct Sump Pump 2D-1 E18 Service Water To Circulating Water Pumps Bearing Lubricating Water Supply Valve, 2-SW-V36. Circuit Breaker E19 Screen Wesh Water Service Water Traveling Screen SCW-2A, Circuit Breaker gg Disconnect Switch 9KVA 39 480-208Y/120V Transformer () r. l 1 i F i i L (h$ BSEP-2/ ASS 0-01 Page 56 of 128 Rev. 0 I

(73 TABLE 2 (Cont'd) 'e EMERGENCF POWER SYSTEM AC Safe Shutdown Component: Service Water intake Structure MCC 2PB Normal Power Supply: 480V Substation E8 Compt. A05 Alternate Power Supply: N/A Safe Shutdown Loads Compt. 550 Ind ind Number Train Component Description Open Yer Closed Yer E29 B Service Water Lube Water Pump 28 N/A Circuit Breaker E36 B Conventional Service Water Pump 28 N/A Discharge Valve To Conventional Header, 2-SW-V15, Circuit Breaker

l i

E37 B Conventional Service Water Pump 28 N/A I Discharge Valve To Nuclear Header, 2-SW-V16, Circuit Breaker 1 E38 B Nuclear Service Water Pump 2B Dis-N/A charge Valve, 2-SW-V20, Circuit (,y';. Breaker RI E39 B Nuclear Service Water Pump 28 N/A Discharge Strainer Motor Circuit i Breaker i E40 B Conventional Service Water Pump 28 N/A Discharge Strainer Motor Circuit Breaker E44 B Conventional Service Water Pump 1A N/A Discharge Valve To Nuclear Header, 1-SW-V14, Circuit Breaker 4 E45 B Conventional Service Water Pump 1A N/A Discharge Valve To Conventional Header,1-SW-V13, Circuit Breaker E46 B Conventional Service Water Pump 1A N/A Discharge Strainer Motor Circuit Breaker l C. BSEP-2/ASSD-01 Page 57 of 128 Rev. 0 m-- - - _ - _ _

TABLE 2 (Cont'd) 'z EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Service Water Intake Structure MCC 2PB Non-Safe Shutdown Loads Compt. Clearance Number Component Description Open Issued E31 2-MRS Welding Receptacle 480V 39 E32 Screen Wash Water Service Water Traveling Screen SCW-2B, Circuit Breaker E34 Ventilation Pump House Exhaust Fan 2A-EF-SWIS, Circuit Breaker E35 Motor 2-KY4 Sers Water To Cire Wtr Pmp Brgs Sec Isol Viv 2-SW-V37 E47 Emergency 120V AC Distribution Panel 28-SW Supply Breaker RI E49 Service Water To Chlorination System Outboard Supply Valve, 2-SW-V295, Circuit Breaker Disconnect Switch 9KVA 39 480-208Y/120V Transformer Os E SEP-2/ ASSD-01 Page 58 of 128 Rev. O

TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC distribution Pan'el 2E7 Normal Power Supply: 480V Substation E7 Compt. AY1 Alternate Power Supply: N/A Location: Control Building - E1. 49' - Electronic Equipment Room Safe Shutdown' Loads Circuit 55D Ind Ind Number Train Component Description Open Ver Closed Yer ~ 1 A Emergency l20V AC Distribution Panel N/A 2A Supply Breaker. 6 .A Emergency 120V AC Distribution Panel 32AB Normal Supply Breaker N/A Non.-Safe Shutdown Loads Circuit clearance I Number Component Description Open Issued 2 Emergency 120V AC Distribution Panel 2AB TB Alternate Supply Breaker i 3 Emergency 120V AC Distribution Panel ' 2A-TB Supply Breaker D, 4 Emergency 120V AC Distribution Panel 2AB-RX Normal Supply Breaker 5 Emergency 120V AC Distribution Panel 2AB Normal Supply Breaker 7 Emergency 120V AC Distribution Panel 2C Supply Breaker 8 Emergency 120V AC Distribution P'anel 2A-RX Supply Breaker 10 R.P.S. Transfer Switch (LG3) Normal Supply Breaker BSEP-2/ASSD-01 Page 59 of 128 Rev. 0 IM

g-TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 2E8 Normal Power Supply: 480V Substation E8 Compt. A12 Alternate Power Supply: N/A Location: Control 3uilding - El. 23' - Cable Spread Area Safe Shutdown loads Circuit SSD Ind Ind Number Train Component Description Open Ver Closed Ver 1 8 cmergency 120V AC Distribution Panel 2B Supply Breaker Non-Safe Shutdown Loads Ci rcuit Clearance Number Component Description Open Issued 2 Emergency 120V AC Distribution Panel 2AB-TB Normal Supply Breaker 3 Emergency 120V AC Distribution Panel 2B-1B Supply Breaker R {I 4 Emergeiey 120V AC Distribution Panel 2AB-RX Alternate Supply Breaker 5 Emergency 120V AC Distribution Panel 2AB Alternate Supply Breaker 6 Emergency 120V AC Distribution Panel 32AB Alternate Supply Breaker 7 Emergency 120V AC Distribution Panel 2D Supply Breaker 8 Emergency 120V AC Distribution Panel 28-R,\\ Supply Breaker 9 Emerg Power Sys Dist Pnl 2-C95-DR-H11 Main Feed 10 R.P.S. Transfer Switch (LG3) Alternate Supply Breaker h. m BSEP-2/ASSD-01 Page 60 of 128 Rev. O

.,f, TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 1A-DG i Normal Power Supply: Diesel Generator Building MCC DGA Compt. D45 Alternate Power Supply: N/A Location: Diesel Generator Building - 4KV Cell 1 - El. 38' Safe Shutdown loads Ci rcuit SSD Ina I nd Number Train Component Description Open Yer Closed Ver MAIN A Incoming Feeder Breaker 1 12 A Diesel Generator No.1 - Generator Control Panel Instrumentation Circuit N/A Breaker 24 A Diesel Generator No.1 Engine Control N/A Panel Instrumentation Circuit Breaker d Non-Safe Shutdown Loads ' Circuit Clearance Number Component Description Open Issued i g'~ ' 1 1 Diesel Generator Building North Airlock Door Circuit Breaker ) 3 Remote Shutdown Panel l 1 7 Diesel Generator No.1 Engine Control l l Panel Space Heaters Circuit Breaker i

T e

Diesel Generator No.1 - Exciter Control Panel Space Heaters Circuit Breaker j 9 Bus Duct Heater For Buses El-E3 Circuit i Breaker 10 Diesel Generator No.1 - Exciter Control 1 Panel Space Heaters Circuit Breaker 13 480V Substation E7 Heater And Fan Circuit Breaker 14 Diesel Generator No.1 - Generator Control Panel Lights And Space Heaters Circuit Breaker ikh 15 RHR SW. Pp.1C Control Pnl H80 Bus E-1 I J f BSEP-2/ASSD-01 Page 61 of 128 Rev. O l

TA8LE 2 (Cont'd) EMERGENCT7DWER SYSTEM AC ([i Safe Shutdown C'omponent: Emergency 120V AC Distribution Panel 1A-DG Non-Saf a Shu'tdown Loads (Cont'd) circuit clearance Number Congonent Description Open Issued 18 . RHR SW. PP.1A Control Pn1 H82 Bus. E-3 23

  • 4160 Emergency Bus El Heater And Control Bus Circuit Breaker R

(:); u i 4 O BSEP-2/AS$0-01 Page 62 of 128 Rev. O l

TAALE 2 (Cont'd) EMERMWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 15-DG grp*, %^ Normal Power Supply: Diesel Generator Building MCC DG8 Compt. D89 Alternate Power Supply: N/A Location: Diesel Generator Building - 4KV Cell 2 - E1. 38' Safe Shutdown Loads circuit s5p Ind Ind Number Train conponent Descriptidn Open Ver Closed Ver N/A B Incoming Feeder Breaker MAIN ~ 12 B Diesel Generator No. 2 Generator Control Panel Instrumentation Circuit N/A Breaker 24 B Diesel Generator No. 2 Engine Control N/A Panel Instrumentation Circuit treaker Non-Safe Shutdown Loads circuit clearance Number Component Description Open Issued f 7 Diesel Generator No. 2 Enqine Control Panel Space Heaters Circu' t treaker Q' 8 Diesel Generat'or No. 2 Exciter Control Panel Lights And Receptacles Circuit Breaker g Bus Duct Heater For tuses E2-El 10 Diesel Generator No. 2 Exciter Control Panel Space Heater Circuit Breaker 13 480V Substation Et Heater And Fan Circuit Breaker 14 Diesel Generator No. 2 Generator Control Panel Lights And Space Heaters Circuit Breaker 15 RHR SW. PP.10 Control Pn1 H81 Bus E-2 18 RHR SW. PP. 1B Control Pn1 H81 Bus E4 b BSEP-2/AS50-01 Page 63 of 128 Rev. O

TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC (}}: Safe Shutdown Component: Emergency 120V AC Distribution Panel 18-DG Non-Safe Shutdown Loads (Cont'd) circuit clearance Number Component Description Open Issued 21 Remote Shutdown Panel RCIC Flow Controller Circuit Breaker 23 4160Y Emergency Bus E2 Heater And. Control Bus Circuit Breaker (j.;h e .n

(23 BSEP 2/ASSO 01 Page 64 of 128 Rey, O

.A TABLE 2 (Cont'd) ENERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 2A-DG Normal Power Supply: Diesel Generator Building MCC DGC Compt. 009 Alternate Power Supply: N/A Location: Diesel Generator Building - 4KY Cell 3 - El. 38' Safe Shutdown Loads Circuit SSD 'I nd I nd Number Train Component Description Open Ver Closed Ver MAIN A Incoming Feeder Breaker n/A 4 A Solenoid Valve, 2-FO-SV-2012, Circuit N/A Breaker 5 A Solenoid Valve, 2 F0-SV 2036, Circuit Breaker N/A 4 12 A Diesel Generator No. 3 Generator Control Panel Instrumentation Circuit N/A 1 Breaker 24 A Diesel Generator No. 3 Engine Control cy, Panel Instrumentation Circuit Breaker N/A E; Non-Safe Shutdown Loads i i circuit Clearance Number Component Description Open Issued t I Recote Shutdown Panel l 7 Diesel Generator No. 3 Engine Control Panel Space Heaters Circuit Breaker 8 Diesel Generator No. 3 Exciter Panel i j Lights and Receptacles Circuit Breaker { f 10 Diesel Generator No. 3 Exciter Control Panel Space Heaters Circuit Breaker l 13 480V Substation E5 Heater And Fan Circuit Breaker i 14 Diesel Generator No. 3 Generator Control I Panel Lights And Space Heaters Circuit i Breaker j 01 [ BSEP-2/ASSD-01 Page 65 of 128 Rev. O j 1 i

TABLE 2 (Cont'd) EMERcer.ncT POWER SYSTEM AC g* Safe Shutdown Component: Emergency 120V AC Distribution Panel 2A-DG Non-Safe Shutdoirn Loads (Cont'd) circuit Glearance haber Component Description Open Issued i 15 RHR SW. Pp 2C Control Pn1 H80 Bus E-1 16 ARM Alera 1-4 Stack Filter House Circuit i Breaker 4 17 Diesel Generator Building Fire Detection 3 i Control Panel Circuit Breaker 18 RHR SW. P'p 2A Control Pnl H82 Bus E-3 19 Diesel Generator Building Fire Detection Control Panel Circuit Breaker 20 Tegerature $ witches 2 VA-TS-31642,1643, 1644, 1645 Circuit Breaker g l 21 Bus Duct Heater For E3-E4 Circuit treaker' l gew 22 Diesel Generator B1dg Vent. Cell-1 O. Dag er Ct1 i 23 4160V Emergency Bus E3 Heater And Control l Bus Circuit Breaker i 1 1 1 J i i j b' j BSEP-2/ASSD-01 Page 66 of 128 Rev. O I I

TABLE 2 (Co2t'd) EMERGUTCT7DWER SYSTEM AC i Safe Shutdown Component: Emergency 120V AC Distribution Panel 28-06 {h Normal Power Supply: Diesel Generator Building MCC DGD Conpt. 049 Alternate Power Supply: N/A Location: Diesel Generator Building - 4KV Cell 4 - E1. 38' 1 Safe Shutdown Loads i Circuit 559 Inc Inc Number Train Congonent Description Open Ver Closed Ver i MAIN 8 lecoming Feeder Breaker N/A 4 B Solenoid Yalve, 2-F'-SV-2DJD Circuit N/A I D Breaker 6 B Solencid Valve, 2-FD-SV-2024, Circuit Breaker N/A i 12 B Diesel Generator No. 4 Generator N/A control Panel Instrumentation Circuit Breaker 4 i 13A B D.G. Bldg. Halon Control Panel N/A f-(Node H1Z) 24 8 Diesel Generator No. 4 Engine Control N/A Panel Instrumentation Circuit Breaker (,t. ~ 4 Non-Safe Shutdown Loads Utrcuit Glearance j Number Conconent Description Open Issued l l l 1 Diesel Generator Building South Airlock J Door Circuit Breaker l ( .l Diesel Generator Building Deluge Valve, t 2 2-FP-DV15. Circuit Breaker i 3 Remote Shutdown Panel RCIC Flow 2 Controller l l 5 Diesel Generator Building Fire Protection l Annunciator 2-UA-41 Circuit Breaker l 7 Diesel Ger.erator No. 4 Engine Control Panel Space Heaters Circuit Breaker sg. L: BSEP-2/ASSD-01 Page 67 of 128 Rev. D

TABLE 2 (Cont'd) ha". EMERGEMGT POWER SYSTEM AC Safe Shutdown Component: Emergency 12DV AC Distribution Panel 28-DG Non-Safe Shutdown Loads (Cont'd) G1rcutt Glearance Number Component Description Open Issued B Diesel Generator No. 4 Exciter Control Panel Lights And Receptacles Circuit Breaker g Diesel Generator Building Deluge Valve. 2-FP_DV14 Circuit Breaker 10 Diesel Generator No. 4 Exciter Panel Space Heaters Circuit Breaker 11 Diesel Generator Building Deluge Valve. 2-FP-DV13 Circuit Breaker 13 480V Substation E6 Heater And Fan Circuit Breaker Rb 14 Diesel Generator No. 4 Generator Control Panel Lights And Space Heater Circuit (g+! Breaker 15 RHR SW. Pp 28 Control Pn1 H83 Bus C-4 16 Diesel Generator Building Deluge Valve 2-FP-DV17 Circuit Breaker 17 Diesel Generator Building Deluge Valve. 2-FP-DV18. Circuit Breaker 18 RHR SW. Pp 2D Control Pal HB1 Bus E-2 1g Diesel Generator Butiding Deluge Valve. 2-FP-DVl9 Circuit Breaker 20 Diesel Cererator Building Deluge Valve. l 2-FP-DV16. Circuit Breaker 21 Bus Dact Heater For E2-E4 Circuit Breaker 22 Diesel Gen. Bldg. Vent cell #2 Damper Cont. 23 4160 Energency Bus E4 Heater And Control g Bus Circuit Breaker l BSEP-2/ASSD-01 Page 68 of 128 Rev. D l l

i b, TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Uninterruptible Power Supply 2A Normal Power Supply: Control Building MCC 2CA Compt. C07 l Alternate Power Supply: 12S/250V DC SWBD 2A Compt. (k15 Location: Control Building - E1. 23' - Bettery Room 2A Safe Shutdown 1.oads i Ci rcuit SSD I nd I nd I Number Train Component Description Open Ver C1esed Ver i i MAIN A Incoming Feeder Breaker N/A l l 1 A Vital 120V AC Distribution Panel V-10A N/A (HG9) Supply Breaker 1 2 A Vital 120V At tistribution Panel V-8A N/A t j (HGB) Sup;j:., Breaker Non-Safe Shutdown Loads j Ci rcuit Clearance Number Component Description Open Issued ] f"a 3 Vital 120V AC Distribution Panel Y-6A (HG7) Supply Breaker 4 i 4 Computer Central System Power Supply lo Transformer (J14) Supply Breaker l 6 Sample Detector Skid l l l 1 i i i i l 4 l i j BSEP-2/ASSD-01 Page 69 of 128 Rev. O

R 1 1 TABLE J (Cont'd) EMERGENCY POWER SYSTEM AC ) Safe Shutdown Cog onent: Reactor Protection System Power Distrioution Panel t Normal Power Supply: Reactor Protection System H-G Set 2A Alternate Power Supply:' RPS M-G Set Isolation Transformer Locationi Control Building. El. 23' - Cable Spread Area - North Wall Safe Shutdown loads Circuit 550 Ind Ind Number Train Component Description Open Yer Closed Ver CB2A A Scram Trip System A Sensors, A.;te am Ckt - Trip System A, .schg Vol High Water Level Trip ss - Trip System A Rei..or Scram Reset (Gps 1, 2, 3, & 4) - - Trip System A Shutdown Scram deset Intik - Trip System A N/A Pilot Scram Valve Sol (Gps 1, 2, 3, & 4) - And Indicator Lights - Trip System A i R Reactor Manual Scram - Trip System A NSSS - Trip System A Logic Select Rod - Insert Trip System A Scram Dischg Vol Redundant - Level Switches (2-C12-LSH-4516A (3 - & 4516C) APRM Setdown - Trip System A Scram Reset Valve Test & CRD - Scram Dischg Vol High Water - Level Bypass - Trio System A CBSA A Reactor Water Sample Yhlve (832-F019) - - Inboard Main Stm Line Valve & Test Sol - Inboard RHR System (Isol Valve Control) - Inboard RWCU System (Isol Valve Control) - InboarU N/A Drywell Isolation Valves (G16-F003 & F019) - Inbosrd RHR Sagle Line Valves (E11-F079A & F079B) -Inboard Reactor Water Sample Valve Logic - Inboard tDuring fire conditions requiring A Train equipment for safe shutdown, the RPS power distribution panel is to be re-energized using RPS M-G Set A per OP-03 h* BSEP-2/ASSD-01 Page 70 of 128 Rev. 0

l TABLE 2 (Cont'd) SMERGENCY POWER SYSTEM AC hh l Safe Shutdown Component: Reactor Protection System Power Distribution Panel Non-Safe Shutdown Loads circuit clearance Number Component Description Open Issued CB1 Alternate Feed Transformer CB3A APRM Channels A, C, & E LPRM Group A RBM Channel A Flow Units A & C CB4A Off-Gas Rad Mon (012-K601A) CB6A Main Stm Line Rad Monitors (K603A & K603C) r l Reactor Building Vent Rad Monitor (K609A) R (hh l (b ' B'JE P-2/ ASSD-01 Page 71 of 128 Rev. 0 l l [

TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC Q O Safe Shutdown Component: Reactor Protection System Power Distribution Panel 't Normal Power Supply: Reactor Protection System M-G Set 28 Alternate Power Supply: RPS H-G Set Isolation Transformer Location: Control Butiding - E1. 23' - Cable Spread Area - North Wall Safe Shutdown loads ~ Circuit 55D Ind Ind Number Train Comonent Description Open Yer Closed Ner CB2B B Scram Trip System B Sensors Auto Scram Ckt - Trip System B Scram Dischg Vol High Water - Level Trip Bypass - Trip - System B N/A Reactor Scram Reset (Gps 1, 2, 3 & 4) - Trip System B Shutdown Scram Reset intik - Trip - System B Pilot Scram Valve Sol (Gps 1, 2, 3 and - 4) And Indicator Lights-Trip System B Reactor Manual Scram - Trip System B3 R NSSS - Trip System B Logic Select Rod Insert , Trip System B Scram Dischg Vol Redundant Level Switches n Igp - (2-C12-LSH-45168, 45160, & 4516F) APRM Setdown - Trip' System B Scram Reset Valve Test & CRD Scram Dischg -Vol High Water Level Bypass - Trip - System B CB5B B Main Stm Line Valve & T6st Sol - - Outboard RHR System (Isol Valve Control) - - Outboard RWCU System (Isol Valve Control)

  • N/A I

- Outboard I Drywell Isolation Valves (G16-F004 & - F020) - Outboard - RHR Samle Line Valves (E11-F080A A - F0 BOB) - Outboard Reactor Water Sample Valve (B32-F026) - - Outboard Reactor Water Sample Valve Logic - Outboard 3 ..ucing fire conditions requiring B Train equipment for safe shutdown, the RPS power distribution panel is to be re-energized using RPS M-G Set B per OP-03. (/ BSEP-2/ASSD-01 Page 72 of 128 Rev. 0

TABLE 2 (Cont'd) EMERGENGY POWER SYSTEM AC k Safe ShJtdown Component: Reactor Protection System Power Distribution Panel Non-Safe Shutdown Loads (Cont'd) G1rcuit Glearance Number Component Description Open Issued CB1 Alternate Feed Transformer CB3B APRM Channels B, 0, & F LPRM Group B RBM Channel B Flow Units 8 & D CB4B Off-Gas Rad Monitor (D12-K601B) CB6B Main Stm Line Rad Monitors (K603B & K603D) Reactor Bu'lding Vent Rad Monitor (K6098) R (S t i i l(b BSEP-2/ASSD-01 Page 73 of 128 Rev. O

Eg TABLE 2 (Cont'd) \\E" EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 32A Normal Power Supply: Control Building MCC TCA Compt. C77 Alternate Power Supply: N/A Location: Control Building - El. 23' - Cable Spread Area Safe Shutdown Loads Tircuit SSD Ind Ind Number Train Component Description Open Ver Closed Ver HAIN A Incoming '/eeder Breaker N/A 4 A Containment High Range Rad Hon Iso'iation AMPS X-XY-4354 A & B, X-XY-4355 A & B Panel XU-77 N/A 6 A Diesel Generator No.1 & 3 Damper Control Power Circuit Breaker N/A 24 A RTGB XV-51 120V For 2-CAC-LR-2602, Circuit Breaker N/A E Non-Safe Shutdown Loads G^I^ Circuit Clearance-Number Component Description Open Issued 1 Steam I.eak Detection System Control Panel 2-H12-P614 And HPCI Timer Logic Circuit Breaker 2 Hiscellaneous Instrument Rack XU-62 Terbine Builouig Ventilation Circuit Breaker 5 D.C. Swbd 2A Strip Htrs. 7 Power Supply For Valves SV-5262, SV-5253 & SV-5482 8 RTG Board-PH2-Plug Hold For Recorders 9 Rtg Board-PH1-Plug Hold For Recorders 10 Power Supply, 2-CAC-ES-3689, Circuit Breaker 11 ERFIS Hultiplexer Cab. 2-C95-P652 (HUX-2) 12 RTG Board-PH3-Plug Hold For Recorders l' 13 Suppression Pool Level Switch, 2-CAC-LSHL-4177, Circuit Breaker BSEP-2/ASSD-01 Page 74 of 128 Rev. O I

I'j TABLE 2 (Cont'd) 0 EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 32A Non-Safe Shutdown Loads (Cont'd) Circuit clearance Number Component Description Open Issued 14 ARM Recorders R600 And R601, Circuit Breaker 16 RTG Board-PM11-Plug Mold For Recorders 18 RTG Board-PMS-Plug Mold For Recorders 19 Drywell Hydrogen And Oxygen Recorder 2-CAC-AR-4409 Circuit Breaker 21 Drywell Hydrogen And Oxygen Analyzer, 2-CAC-AT-4409, Circuit Breaker R 22 Computer-Digital Output Cab. C91-P609 23 CAC-AT-4409 Sample Select Valves, @.) 2-CAC-SV-4409-1 through 5, Circuit Breaker BSEP-2/ ASS 0-01 Page 75 of 128 Rev. O

i TABLE 2 (Cont'd) ENERGLNCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 32B Normal Power Supply: Control Building MCC 2CB Compt. C78 Alternate Power Supply: N/A Location: Control Building - E1. 49' - Electronic Equipment Room Safe Shutdown loads Glecuit 55D Ind Ind Numuer Train Component Description Open Ver Closed Ver MAIN B Incoming Feeder Breaker 6 B Diesel Generator No. 2 & 4 Damper , Control Power Circuit Breaker N/A Non-Safe Shutdown Loads circuit clearance Number Component Description Open Issued 1 Steam Leak Detection Systea Control Panel 2-H12-P614 And HPCI Timer Logic Circuit Breaker R 2 Ind. Ckt. For Flood Status Serv. Wtr. h). Intake Structure 3 CAC AC Div I Isolation Override Switch, 2-CAC-CS-4179, Circuit Breaker 4 Suppression Pool To Reactcr Building Vacuum Breaker Isolation Valve, 2-CAC-V17, Control Switch 2-CAC-CS-4223 Circuit,reaker B 5 0.C. Switchboard 2B Strip Htr. 7 CAD System Supply Valve, 2-CAi:-V56, Control Switch 2-CAC-CS-2S71, Circuit Breaker B Converter Isolation For 2-CAC-FV-2720-4 Circuit Breaker 9 Gaseous Analyzer Panel XV-51 (Power Supply 2-CAC-ES-3690) Circuit Breaker 10 MSIV Pit Temperature Switches Testing Circuit Breaker b$'. BdEP-2/ASSD-01 Page 76 of 128 Rev. V l 1

c a TABLE 2 (Cont'd) , e EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 32B Non-Safe Shutdown Loads (Cont'd) Circuit Clearance Number Component Description Open Issued 11 Fluid Flow Detector Cabinet, CB-XU-73, Circuit Breaker 12 Voltage Input For 2-SCW-LRA-285-1 13 Containment High hange Rad Mon' tors 2-RI-4197, 2-RI-4198, And 2-R'<-4197 Circuit Breaker 15 Panel XU-56 (Outboard L0f A Isolation Logic) Circuit Breakce 16 Inboard Suppression Pool Purge Exhaust Valve, 2-CAC-V7, Control Switch 2-CAC-CS-1538, Circuit Bresker 17 Outboard Suppression Pool Purge Exhaust R Valve 2-CAC-V8, Control Switch 2-CAC-CS-1539, Circuit Breaker 18 Inboard Drywell Purge Exhaust Valve 2-CAC-V9, Control Switch 2-CAC-CS-1533, Circuit Breaker 19 Outboard Drywell Purge Exhaust Valve 2-CAC-V10, Control Switch 2-CAC-CS-1534, Circuit Breaker 22 A0G Instrument Air Backup From CAD System Isolation Yalves, 2-NP-CV-2889 And 2-NP-CV-2890, Circuit Breaker 23 CAD Loop A/ Loop B Crosstie Valve 2-NP-CV-2716 And Control Switch 2-CAC-CS-2716 And 2-CAC-CS-2716-2 Circuit Breaker 24 Power Supply To 2-CAC-TY-4426-2 And 2-CAC-TR-4426-2 Circuit Breaker k BSEP-2/ASSD-01 Pago 77 of 128 Rev. O

1 i: TABLE 2 (Cont'd) ll EMERGENGY POWER SYSTEH AC p2*, Safe Shutdown Component: Emergency 120V AC Distribution Panel 1A-SW Normal Power Supply: Service Water Intake Struc*ure MCC IPA Cogt. BV4 Alternate Power Supply: N/A Location: Service Water Building - E1. 20' - North Wall Safe Shutdown loads Circuit 55D Ind Ind Number Train Cogonent Description

Open, Ver Closed Ver MAIN A

Incomitig Feeder Breakep N/A ~ 4 A Lube Water Pum,'s Suct. Shut-Off Valve PV-135 N/A t Non-Safe Shutdown Loads U1rcuit clearance Number Cog onent Description Open Issued 1 Service Water Screen Nash System '1A' g 2 Circulating Water Screen Wash Sys Screens 1A, 18, 1C, & 10 3 Cire. Pump Bearings Lub Water hm4 7 Service Water' Intake Structure Fire Detection Control Panel Circuit Breaker 9 Service Water Intake Structure Fire Detection Control Panel Circuit Breaker f l G BSEP-2/ASSD-01 Page 78 of 128 Rev. O i

TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC (}[j Safe Shutdown Component: Emergency 120V AC Distribution Panel 2A-SW Normal Power Supply: Service Water Intake Structure MCC 2PA Corpt. E14-Alternati Power Supply: N/A Location: Service Water Building - E1. 20' - West Wall Safe Shutdown Loads. G1rcuit 550 Inc Ina humber Train Component Description Open Ver Closed Ver KAIN A Incoming Feeder Breaker N/A 6 A Lube Water Pumps Suct. Shut-Off V1v. N/A PV-136 Non-Safe Shutdown Loads Circuit Clearance Number Component Description Open Issued 1 Service Water Screen. Wash System '2A' g 2 Circulating Water Screen Wash Sys. Screens 2A. 2B, 2C. & 2D bbh 3 Circulating Pumps Bearing Lub Water 4 l Vent Fan 1A-SF-SWIS, a 2A-SF-SWIS l kI.I BSEP-2/ASSD-01 Page 79 of 128 Rev. O

,' "g TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Vital 120V AC Distribution Panel V-8A Normal Power Supply: Uninterruptible Power Supply 2A CKT. 2 Alternate P a er Supply. N/A Location: Control Building - El. 49' - Electronic Equipment Room Safe Shutdown Loads Circuit 550 Ind Ind Number Train Component Description Open Ver Closed Ver 2 A Control Power to Panel 2-H12-P603 N/A Circuit Breaker 11 A BOP Process Instr Cab Pwr Supply Cab. N/A XV-9 HG8-JP2 (Source B) Non-Safe Shutdown Loads Circuit Clearance Number Component Description Open Issued 1 Operator Console Circuit Breaker RI @3 5 Log Typer Table Circuit Breaker 6 2-CAC-FY-2717-4 7 Rod Display Fan Motor Circuit Breaker 9 SJAE Low Steam Pressure Relay Circuit Breaker 12 Rod Select Relays, Select Module Ind. Lights, and RWM Bufft.r 13 EHC Pressure Indicator On RTGB Circuit dreaker 4 0].. BSEP-2/ASSD-01 Page 80 of 128 Rev. O

TABLE 2 (Cont'd) ..s -(' EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Vital 120V AC Distribution Panel V-10A Normal Power Supply: Uninterruptible Power Supply 2A CKT.1 Alternate

  • ser Supply:

N/A Location: control Building - El. 49' - Electronic Equipment Room Safe Shutdown loads Ci rcuit SSD I nd i nd Number Train Component Description Open Yer Closed Ver 3 A Reactor Feed Pump Control System Logic And Reactor Water Level A Unit Circuit N/A Breaker 11 A B.O.P. Process Instr Power Supply N/A Cabinet XU-9 (Source "A") Non-Safe Shutdown Loads Ci rcuit Clearance Number Component Description Open Issued g 1 Control Power To Rod Position Information gs3 System Control Panel, 2-H12-P615, Circuit Breaker 2 EHC Control Cabinet Circuit Breaker 4 CHC Control Cibinet-Bay F Circuit Breaker 6 SJAE Off Gas Rad Hon Sample Timer, 2-D12-M001, Circuit Breaker 7 RX Building Vent Rad Recorder K605, Stack Rad Recorder K600B, Circuit Breaker 8 B0P Recorders XV-4 9 Sq. Rt. Cony'r 2-C00 FY-44-45 & 648, And Temp Xmtr 2-TCC-TT-615 9 XU-9 i 12 Unit Controller XU-6 BSEP-2/ASSD-01 Page. of 128 Rev. 0 __,,.,_,,m

..d TABLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distrioution Panel 2A Normal Power Supply: Emergency 120V AC Distribution Panel 2E7 CKT.1 Alternate Power Supply: N/A Location: Control Building - El. 23' - Cable Spread Area Safe Shutdown Loads Circuit SSO Ind Ir4 Ntrnber Train Component Description Open Ver Closed Ver MAIN A Incoming Feeder Breaker N/A 3 A Control Power To Panel 2-H12-P601 & N/A 2-E11-R604 Circuit Breaker 4 A Control Power To Panel 2-H12-P613, N/A 2-E11-K600A, K603A, 5600A, And K605A, Circuit Breaker Non-Safe Shutdown Loads Circuit Clearance Number Component Description Open Issued (30 1 LOCA Signal Fcr CAC (CAM Override Switch RE 2-CAC-CS-2986) Circuit Breaker 2 CAC-AT-4409 Outboard Sample Return Valve, 2-CAC-SV-4540, Circuit Breaker 5 Control Power To Panel 2-H12-P617, And 2-E11-F053A, Circuit Breaker 6 Panel 2-H12-P603, 2-H12-P612, And H/A Transfer Station Circuit Breaker 7 CAC Instrument Panel XU60 (Rectifier Supply) Circuit Breaker 9 CAC Instrument Panel XU60 (120V Supply) Circuit Breaker 11 HPCI Turbine Test And Vibration Circuits Circuit Breaker 12 Battery Charger 23A-2 AC Input Breaker 8,c BSEP-2/ASSD-01 Page 82 of 128 Rev. O

TABLE 2 (Cont'd) ~.. EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 2A Non-Safe Shutdown Loads (Cont'd) Circuit Clearance Number Companent Description Open Issued 14 CB Bridge And Indicating Units 2-VA-TI-1647-2, 2-VA-T1-1299, And 2-VA-TI-1310-2, Circuit Breaker 15 Battery Charger 23A-1 AC Input Breaker 16 CRD Pump 2A Cooling Water Inlet Valve, 2-RCC-V74 Solenoid, Circuit Breaker 18 RHR Pumps A And C Cooler Service Water Outlet Valves, 2-SW-V130 And 2-SW-V131, 1 Circuit Breaker 19 SJppression Pool Drywell Vacuum Breakers, 2-CAC-X18A thru 2-CAC-X18E Test Circuit, CiNuit Breaker 20 ERFIS Multiplexer Cab. 2-C95-P651 (MUX 1) RI g 21 Battery Grd. Det 22 RHR Service Water Booster Pumps A and C Coolers Service Water Inlet Valves, 2-SW-V136 And 2-SW-Y137, Circuit Breaker 23 RHR S1rvice Header Well Water Supply Valve, 2-SW-V143 Normal Circuit Breaker 24 R3CCW Discharge Header Pressure Switch 2-RCC-PS-672 Circuit Breaker 25 Well Water To Vital Header Valve, ?.-SW-V141, Circuit Breaker 26 RBCCW Inlet To Penetration Cooling System Valve, 2-RCC-V185 Solenoid Circuit Breaker 27 Turb Trip Air Relay Dump Viv Ct1 Hdr Press LO Relay Ckt i 28 Outboard Combined Sample Return Valve, 2-CAC-SV-3440. Circuit Breaker ) 4 BSEP-2/ASSD-01 Page 83 of 128 Rev. 0 4

l TABLE 2 (Cont'd) (};; EMERGENCY POWER SYSTEM AC, Safe Shutdown Component: Emergency 120V AC Distribution Panel 2A Non-Safe Shutdown Loads (Cont'd) Circuit clearance Number Component Description Open Issued 29 Main Steam Line Leak Detection Control And Test Cabinet, Circuit Breaker 31 Power Supply To Gaseous Analyzer Panel XV-55 (2-CAC-AT-1264) Circuit Breaker R' i hy' J h!) BSEP-2/AS50-01 Page 84 of 128 Rev. O l

c,, TABLE 2 (Cont'd) LM EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 2B Normal Power Supply: Emergency 120V AC Distribution Panel 2E8 CKT. 1 Alternate Power Supply: N/A Location: Control Building - El. 23' - Cable Spread Area Safe Shutdown Loads Circuit SSD Ind ind Number Train Component Description Open Ver Closed Ver MAIN B Incoming Feeder Breaker N/A 3 B Control Power To Panel 2-H12-P601, N/A Circuit Breaker 4 B Control Power To Panel 2-H12-P612, N/A 2-E11-K605B, K600B, K603B, K604, And 5600B Non-Safe Shutdown Loads ~ Circuit Clearance Number Component Description Open Issued R B.1 ' kb 1 (012) Process Rad Mon 2-D12-V27B 5 Control Power To Panel 2-H12-P618, 2-E11-F074, And 2-E11-F053B, Circuit Breaker 6 Reactor Reciq MV/I Transfer Station H12-P603 H12-P612 7 Post Accident Sample Valves 2-RXS-SV-4181, 4182, 4184, 4187, And 4189 Power Supply Circuit Breaker 7A Post Accident Sample Valves 2-RXS-SV-4192, 4193, And 4194 Power Supply Circuit Breaker 8 2-CAC-AT-4410 Sample Select Valves, 2-CAC-SV 4410-1 Through 5 Circuit Breaker 8A Drywell Hydrogen And Oxygen Recorder, 2-CAC-AR-4410, Circuit Breaker 9 Instrument Air Dryer g BSEP-2/ASSD-01 Page 85 of 128 Rev. O

r h. TABLE 2 (Cont'd EMERG1.NLY POWER SYS EM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 2B Non-Safe Shutdown Loads (Cont'd) Circuit clearance Number Component Description Open Issued 10 Containment High Range Rad Mon Isolation AMPS X-XY-4368 A & B, X-XY-4369A & B Panel XU-76 10A CAC-AT-4410 Aanlyzer Control 11 Scram Discharge Volurte Isolation Valve Position Indicating Lights Circuit Breaker i 12 Battery Charger 24B-2 AC Input Breaker 13 Battery Charger 24B-1 AC Input Breaker 14 PowerSupply2-Ej,K602SupplyBreaker 15 Reactor Building Vent Flow Measuring R B.l Equipment XV62 Circu',t Braaker 16-CRD Pump 2B Cooling Water Inlet Valve, 2-RCC-V73, Solenoid Circuit Breaker 17 Suppression Pool To Drywell Vacuum Breakers, 2-CAC-X1BF Thru 2-CAC-X185J, Test Circuit Circuit Breaker 18 Battery Ground Detector 19 RHR Service Water Booster Pumps B and D Coolers Service Water Inlet Valve, 2-SW-V138 and 2-SW-V139, Circuit Breaker 20 Tracking Rectifier And Inverter Heater Circuit, Circuit Breaker 21 RHR Pumps B and D Coolers Service Water Outlet Valves, 2-SW-V125 And 2-SW-V126 Circuit Breaker 22 Control Power For Scavenging Steam Valves Circuit Breaker 23 RHR Service Header Well Water Supply u. W, Valve, 2-SW-V143, Circuit Breaker l BSEP-2/ASSD-01 Page 86 of 128 Rev. O

f r TABLE 2 (Cont 'd) EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120Y AC Distribution Panel 28 G. Non-Safe Shutdown Loads (Cont'd) G1rcuit Glearance Number Coinponent Description Open Issued 24 RBCCW Inlet To Water Chiller. Isolation Yalve,'2-RCC-YS1, Solenoid Circuit Breaker 25 Stack Monitoring & Purging Equipment 26 2-::AC-AT-4410 Outboard Sample Return Yalve, 2-CAC-SY-4541, Circuit Breaker 27 Main Steam Line Leak Detection Control And Test Cabinet Circuit Breaker 28 Control Power For 2-CAC-AT-1262 Outboard Sample Return Valve, 2-CAC-SV-3439, Circuit Breaker 29 Bridge Indicating Unit,1-VA-TI-1648 Circuit Breaker F 0b ($ BSEP-2/ASSD-01 Page 87 of 128 Rev. 0

TABLE 2_ (Cont'd) h,' EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 32AB Normal Power Supply: Emergency 120V AC fistribution Panel 2E7 CKT 6 Alternate Power Supply: Emergency 120V AJ Distribution Panel 2E8 CKT. 6 Location: Control Builaing - El. 49' - Electronic Equipment Room Safe Shutdown Loads Ci rcuit SSD Ind Ind l,ui.te r Train Component Description Open Ver Closed Ver NORM A Normal Power Supply Incoming Feeder Breaker N/A 24 A Power Supply To 2-CAC-TY-4426-1 And 2-CAC-TR-4426-1 (Div I SPTHS) Circuit N/A Breaker 6 Non-Safe Shutdown Loads Ci rcuit Clearance Nunter Component Description Open issued [ Alt Alternate Incoming Feeder Breaker 1 Panel XU-S3 Inboard (LOCA Isolation Logic) Circuit Breaker 2 CAC Isolation Override Switch, 2-CAC-CS-4178, Circuit Breaker 3 Inboard Primary Containment inerting Valve, 2-CAC-V4 Control Switch 2-CAC-CS-1699, Circuit Breaker 4 Suppression Pool N2 Inlet Yalve 2-CAC-Vb, Control Switch 2-CAC-CS-1537, Circuit Breaker .m (' BSEP-2/ ASS 0-01 Page 88 of 128 Rev. O

l T/BLE 2 (Cont'd) EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 32AB Non-Safe Shutdown Loads (Cont'd) Circuit clearance Number Component Description Open Issued 5 Drywell N2 Inlet Valve, 2-CAC-V6, Control Switch 2-CAC-CS-1531, Circuit Breaker 6 Primary Containment Purge Air Isolation Valve 2-CAC-V15, Control Switch 2-CAC-CS-1530, Circuit Breaker 9 Cuppression Pool 2 Inch Purge Exhaust To SBGT 2-CAC-V172, Control Switch 2-CAC-CS-4498 Circuit Breaker 11 Outboard Primary Containment Valve 2-CAC-V58, Control Switch 2-CAC-CS-2573, Circuit Breaker RB h 12 RX Bldg. Term Cab. XV-53 2-CAC-CS-2683 13 2-HS-V503 [1-CAC-CS-2696 & 2-CAC-CS-2696-2] 14 Purge Vaporizer N2 Outlet Temperature Control Valve 2-NP-TCV-2695, And Control Switches 2-CAC-CS-2695-1 And 2-CAC-CS-2965-2, Circuit Breaker 15 CAD Vaporizer A Flow Control Valve 2-NP-FCV-2717. And Control Switches 2-CAC-CS-2717-1 And 2-CAC-CS-2717-2, Circuit Breaker 16 CAD Vaporizer A Inlet Valve 2-NP-CV-2713. And Control Switches 2-CAC-CS-2713-1 And 2-CAC-CS-2713-2, Circuit Breaker j B5EP-2/ASSD-01 Page 89 of 128 Rev. O

g TABLE 2 (Cont'd) O EMERGENCY POWER SYSTEM AC Safe Shutdown Component: Emergency 120V AC Distribution Panel 32AB Non-Safe Shutdown Loads (Cont'd) Circuit Clearance Number Component Description Open Issued 17 CAD Loop A/ Loop B Crosstie Valve 2-NP-CV-2715, And Control Switches 2-CAC-CS-271b-1 And 2-CAC-CS-2/15-2, Circuit Breaker 18 Ctl. Bldg. Seismic Mon. Cab. ENV-XR-823 Receptacle 19 Containment High Range Rad Monitors, 2-RI-4195, 2-RI-4196 And Recorder 2-RF-4196, Circuit Breaker g 20 Dasher Printer #S SAS 21 Suppression Pool 1 Inch CAD Inlet Valve 2-CAC-V162, Control Switch 2-CAC-CS-5029; Drywell 1 Inch CAD Inlet Valve 2-CAC-V163, Control Switch 2-CAC-CS-S032; Suppression Pool 1 Inch Makeup Valve 2-CAC-V170, Control Switch 2-CAC-CS-5028; And Drywell 1 Inch Hakeup Valve 2-CAC-V171, Control Switch 2-CAC-CS-5033, Circuit Breaker 23 Suppression Pool To Reactor Building Vacuum Breaker '. solation Valve 2-CAC-V16, Control Switch 2-CAC-CS-4222, Circuit Breaker h BSEP-2/ASSD-01 Page 90 of 128 Rev. O

TABLE 3 EMERGENCY POWER SYSTEM DC Safe Shutdown Component: 125/250V DC Switchboat-d 1A h) Normal Power Supply: Battery Chargers 1A-1 And 1A-2 Compt. GKO And GK3 Alternate Power Supply: Batteries 1A-1 And 1A-2 Location: Control Bui.1 ding - El. 23' - Battery Room 9 Safe Shutdown Loads Compt. 55D Ind Ind Number Train Congonent Descriptiort Open Yer Closed Ver GI6 A 125V DC Distributioh Panel 3A Supply Breaker N/A GJ3 A Reactor Building MCC 1XDA Supply Breaker '4/A GJ4 A 125V DC Distribution Panel 11A Supply Breaker N/A GJ5 A Power Conversion Unit '1A' U.P.S. Control Building N/A R GJ6 A 125V DC Distribution Panel 1A Supply N/A Breaker GKO A Battery Charger 1A-1 DC Output Breaker N/A h* GK1 A Battery 1A-1 Output Breaker N/A GK2 A ' Battery 1A-2 Output Breaker .N/A GK3 A Battery Charger IA-2 DC Output Breaker N/A Non-Safe Shutdown loads Comp t. Glearance Number Component Description Open Issued G17 125V DC Distribution Panel 3AB Alternate Supp1y Breaker GI8 125V DC Distribution Panel SA Normal Supply Breaker GI9 125V DC Distribution Panel 7A Normal Supply Breaker GJO 125V DC Distribution Panel 9A Alternate Supply Breaker { BSEP-2/AS!D-01 Page 91 of 128 Rev. 0

O... TABLE 3 (Cont'd) EMERGENCY POWER SYSTEM DC Safe Shutdown Component: 125/250V DC Switchboard 1A Non-Safe Shutdown Loads (Cont'd) Compt. Clearance Number' Component Description Open issued GJ1 125V DC Distribution Panel A0G-1 Supply Breaker GJ2 Turbine Building MCC 1TDA Supply Breaker GJ7 100 A DISC SW LB7 (CW Intake Pumps Exciter Field Temperature Power MCC 1SA Enclosure Breaker) GJ9 125V DC Distribution Panel 17 Alternate Supply Breaker RE O b BSEP-2/ASSD-01 Page 92 of 128 Rev. O i

r g., TABLE 3 (Cont'd) W EMERGENCY POWER SYSTEM OC Safe Shutdown Component: 125/250V DC Switchboard 1B Normal Power Supply: Battery Chargers 1B-1 And 1B-2 Compt. GH1 And GH4 Alternate Power Supply: Batteries 1B-1 And 3 8-2 Location: Control Building - El. 23' - Battery Room Safe Shutdown Loads Compt. SSD Ind i nd Number Train Component Description Open Ver Closed Yer GK6 B Control Building 125V DC Distribution N/A Panel 3B Supply Breaker GL3 B Reactor Building HCC 1XDB Supply N/A Breaker GL4 B 125V DC Distribution Panel 118 Supply Breaker N/A GL6 B Diesel Generator 8uilding Distribution O Panel IB Supply Breaker N/A N/A GL9 B Compt. GL9. Ltg. Inverter U-1 N/A GH1 B Battery Charger IB-1 DC Output Breaker "^ GH2 B Battery 18-1 Output Breaker GH3 B Battery 1B-2 Output Breaker N/A GH4 B Battery Charger 1B-2 DC Output Breaker ] Non-Safe Shutdown Loads ~ Cc,mpt. Clearance Number Component Description Open Issued B79 Emergency Bearing Oil Pump Starter, EB0P Circuit B,reaker GJ8 Alternate Supply To Unit 2 Tracking Rectifier GK7 125V DC Distribution Panel 3AB Normal Supply Breaker l GK8 125V DC Distribution Panel SA Alternate g. Supply Breaker I BSEP-2/ASSD-01 Page 93 of 128 Rev. O

TABLE 3 (Cont'd) EMEREIRT70WER SYSTEM DC {b Saf'e Shytdown Comp'onent: 125/250V DC Switchboard 1B Non-Safe Shutdown Loads (Cont'd) conyt. s clearance-Number Component Description Open Issued 'GK9 125V DC' Distribution Panel 7B Normal Supply Breaker GLD 125V DC Distribution Panel 9A Normal

  • Supply Breaker GL1 125V DC Distribution P%ul 13 Alternate Supply Breaker GL2 Turbine Building MCC ITDB Supply Breaker GL5 Power Conversion Unit IB (DC Input to Standby Power Converter IB) Circuit p

Breaker 4 GL7 Reactor Building Emergency Lighting Contactor Supply Breaker bSi GL8 Turbine Building Emergency Lighting Contactor Supply Breaker GM0 MWT Building Main Control Panel Alternate Supply Breaker ( l 1 l i BSEP-2/ASSD-01 Page 94 of 128 Rev. O \\ - - - - ~ ' - - ' ~ ' - ~ ' - ~ ' ' ~ ' ~~ ~~ ^^'

9 TABLE 3 (Cont'd) EMERGE.NCY POWER SYSTEM DC C.9 Safe Shutdown Component: Reactor Building MCC 1XDA V Normal Power Supply: 125/250V DC Switchboard 1A Conpt. GJ3 Alternate Power Supply: N/A Location: Reactor Building - E1. 20' - North Safe Shutdown Lo' ads . compt. 55D ind and Numben Tra;n Congonent Description Open Yer Closed Ver B10 A' Incoming Feeder Breaker N/.A B11 A HPCI Turbine Auxiliary Oil Pump Circuit Breaker N/A B12 A HPCI Turbine Barometric Condenser Conden3 ate Pump Circuit Breaker N/A B14 A HPCI Condensate Storage Tank Suction Valve,1-E41-F004, Circuit Breaker gjg ~ BIS A HPCI Cooling Water Supply Valve, 1-E41-F059 Circuit Breaker N/A g B16 A HPCI Pump Discharge Valve,1-E41-F007, N/A () ' Circuit Breaker B17 A HPCI Injection Valve,1-E41-F006, N/A Circuit Breaker B18 A HPCI Bypass To Condensate Storage Tank Valve,1-E41-F006, Circuit Breaker N/A B19 A HPCI Redundant Isolation Valve To Condensate Storage Tank, 1-E41-F011, N/A, Circuit Breaker B20 A HPCI Steam Supply Outboard Isolation Valve, 1-E41-F003, Circuit Breaker gfg B21 A HPCI Turbine Steam Supply Valve, 1-E41-F001, Circuit Breaker sf3 822 A HPCI Suppression Pool Suction Valve, N/A 1-E41-F042 Circuit Breaker B23 h HPCI Suppression Pool Suction Valve, N/A 1-E41-F041, Circuit Breaker i Q^ 'BSEP-2/ASSD-01 Page 95 of 128 Rev. 0

~~w TABLE 3 (Cent'd) EMERGENCY POWER SYSTEM DC Safe Shutdown Component: Reactor Building MCC IXDA Safe Shutdown Loads (Cont'd) cospt. 55D Ind Ind Numbgr Train Component Description Open Ver Closed Ver' B24 A HPCI Minimum flow Bypass To Suppression Pool Valve,1-E41-F012 N/A Circuit Breaker

  • B26 A

RHR Suction Isolation Valve. N/A 1-E11-F008. Alternate Feed Circuit Breaker Non-Safe Shutdown Loads

compt, clearance Number Congonent Description Open Issued 813 HPCI Vacuum Pump Circuit Breaker R

0?]

  • NOTE :

Shutdown Cooling Suction Isolation Valve,1-E11-F008 is normally under a Shift Foreman's clearance when the unit is operating. The Shif t Foreman may remove this clearance at his discretion when it has been verified that maintenance on the valve is not in progress. BSEP-2/ASSD-01 Page 96 of 128 Rev. O

TABLE 3 (Cont'd) EMERGENCY POWER SYSTFf '1, Safe Shutdown Component: Reactor Buil' >:. - 1XDB Nonnal Power Supply: 125/250V DC Switch'or ',B Conpt, GL3 u Alternate Power Supply: N/A Location: Reactor Building - El. 20' - South Safe Shutdown Loads Corpt. . 55D Jnd Ind Number Train Component Description Open Yer Closed Yer B30 B Incoming Feeder Breaker N/A B35 B RCIC Barometric Condenser Vacuum Pump Circuit Breaker N/A B36 B RCIC Barometric Condenser Vacuum Tank N/A Condensate Pump Circuit Breaker B37 B RCIC Turbine Trip And Throttle Valve s N/A 1-E51-V8, Circuit Breaker 838 B RCIC Condensate Storage Tank Suction N/A Valve 1-E51-F010, Circuit Breaker R B39 B P.CIC Cooling Water Supply Valve, N/A N 1-E51-F046, Circuit Breaker Q. B40 B RCIC Pump Discharge Valve,1-EP.-F012, N/A Circuit Breaker 841 B RCIC Injection Yalve '-E51-F013. l Circuit Breaker N/A B42 B RCIC Bypass To Condensate Storage Tank gf3 Valve,1-E51-F022, Circuit P.reaker B43 B RCIC Steam Supply

  • Outboard Isolation gfg Valve,1-E51-F008 Circuit Brr. ' -

944 B RCIC Turbine Steam Supply Val m n/A 1-E51-F045 Circuit Breaker B45 B RCIC Suppression Pool Sr.. ion Valve, N/A 1-E51-F031, Circuit Breaker B46 B RCIC Suppression Pool Suction Yalve. N/A 1-E51-F029, Circuit Breaker B47 B RCIC Minimum Flow Bypass To Suppression Pool Valve,1-E51-F019, N/A l Circuit Breaker BSEP-2/AS$D-01 Page 97 of 128 Rev. O

TABLE 3 (Cont'd) EMERGENCY POWER SYSTEM DC g Saft Shutdown Component: Reactor Suilding MCC iXDB Safe Shutdown Loads (Cont'd) Number Train Component Description Open Yer Closed Ver B4B B RWCU Inlet Outboard Throttle Isolation Valve,1-G31-F004, Circuit Breaker N/A

  • B50 B

Shutdown Coolirg Outboard Suction Isolation Valve,1-E11-F008, Circuit N/A Breaker

  • B51 6

RHR TJ Radwaste Outboard Isolation Valve 1-E11-F040. Circuit Breaker N/A B52 B Main Steam Line Outboard Drain Isolation Valve,1-B21-F019 Circuit Breaker N/A B53 B Remote Shutdown Panel IP-RB-4 ALT. gjg Safe Shutdown Instruments g Non dafe Shutdown Loads ,,.6 comt. clearance Number Com onent Description Open Issued B49 Reactor Vessel Head Spray Outboard Isolation Valve, 1-E11-F023 Ci rcuit Breaker

  • NOTE:
hutdown C'
Outbu* -

m* ion Isolation Valve,1-E11-F008 and RHR To Radwaste Outboa rd ter u=1 v.. .! 1-F040, are normally under a Shif t Fot.em 3's clear.nce otrating. The Shift Foreman may remove this clearanc,,; 't nen it has be:.u verified that maintenance on the valve it. +ot ,w fM-450-01 Page 98 of 128 Rev. O

TABLE 3 (Cont'd) EMERGENCY POWER SYSTEM DC (}} Safe Shutdown' Component: 125Y DC Distribution ' Panel 1A Normal Power Supply: 125/250V DC Switchboard 1A Compt. GJ6 Alternate Power Supply: N/A Location: Diesel Generator Building - 4KY Cell 1 - E1.' 38' i Safe Shutdown loads CT'rcuit 550 Inc Inc Number Train 'Co'mponent Description Open Yer Closed Yer M6IN A Incoming Feeder Breaker N/A 3 A 480V Substation E5 Norsd1 Control Power Ciecuit Breaker N/A 7 A ESS Logic Cabinet H58 Circuit Breaker N/A 15 A 480V Substation E7 Alternate Control gfg Power Circuit Breaker 17 A 4KY Emergency Bus El Normal Control gfA Power Circuit Breaker g i 18 A 4KY Emergency Bus E3 Alternate Control Power Circuit Breaker N/A r?x RJP 19 A tiormal Power For Diesel Generator No.1 Annunciator, Start And Load N/A Circuit Breaker 20 A Diesel Gen'.rator No. 3 Alternate Power Supply For Annunciator, Start, And N/A Load Circuit Breaker i Non-Safe Shutdown loads I JCircuit Glearance Number Component Description Open Issued 1 4KV Emergency Bus El Test Cabinet Circuit Breaker 2 Diesel Generator Building Emergency Lighting Contactor Supply Breaker t h[] i i BSEP-2/ASSD-01 Page 99 of 128 Rev. O I

TABLE 3 (Cont'd) EMERGr.NcY POWER SYSTEM DC {v.: Safe Shutdown Component: 125V DC Distribution Panel IB Normal Power Supply: 125/250V Switchboard 1B Conpt. GL6 Alternate Power Supply: N/A s Location: Diesel Genera;or Building - 4KY Cell 2 - E1. 3B' Safe Shutdown Loads Circuit 55D Ind Ind Number Train Component Description Open Ver Clored Yer MAIN B lneoming Feeder Breaker. N/A 3 B 480VSubstationE6NormalChntrol Power Circuit Breaker N/A 5 B Remote Shutdown Panel Circuit Breaker "^ "^ 7 B ESS Logic Cabinet H59 Circuit Breaker 8 B Remote Shutdown Panel Circuit Breaker N/A 15 B 4BOV Substation E8 Alternate Control Power Circuit Breaker N/A R 17 B 4KV Emergency Bus E2 Normal ContN1 p@ Power Circuit Breaker N/A 1B B 4KV Emergency Bus E4 Alternate Control Powei Circuit Breaker N/A 19 B Diesel Generator No. 2 Normal Power For Annunciator Start And Load gjg Circuit Breaker 20 B Diesel Generatar No. 4 Alternate Power Supply For Annunciator Start, And N/A l Load Circuit Breaker. Non-Safe Shutdown loads Circuit clearance Number Com onent Description Open Issued 1 4KV Emergency Bus E2 Test Cabinet Circuit Breaker 6 Diesel Generator Building Emergency Lighting Contactor Supply Breaker b 3SEP-C/ASSD-01 Page 100 of 128 Rev. 0

TABLE 2 (Cont'd) EMERGE 1RT"PDWER SYSTEM AC g. Safe Shutdown Component: 125V DC Distribution Panel 1B Non-Safe Shutdown Loads circuit clearance Number Component Description Open Issued ~ * ' 10 , ',Bir #1 Annunc (HA4) 12 Bir #2 Annunc (HA5) R (). b BSEP-2/ASSD-01 Psge 101 of 128 Rev. O

p'$ TABLE 3 (Cont'd) EMERGENCY POWER SYSTEM DC Safe Shutdown Component: 125V DC Distribution Panel 3A Normal Power Supply: 125/250V DC Switchboard 1A Compt. G16 Alternate Power Supply: N/A Location: Control Building - El. 49' - Electronic Equipment Room Safe Snutdown Loads Ci rcuit SSD I Ind l nd Number Train component Description Open Ver Closed Ver HAIN A Incoming Feeder Breaker N/A 2 A Eb1 Valves And Ell-Heter Circuit Breaker N/A 3 A Ell-Relay Logic A Cire.uit Breaker N/A 4 A E21 Relay Logic Panel 1-H12-P626 Circuit Breaker N/A 12 A Inboard Isolation Valve Logic Control Panel, 1-H12-P622. Circuit Breaker N/A @r 14 A HPCI Control And Relay Logic Circuit N/A Breaker t "#^ 17 A ESS LOGIC CAB "H60" 19 A Trip Calibration Cabinet AQ6 NfA (CB-XV-63) Inverter 1 Supply Breaker Non-Safe Shutdown loads Circuit Clearance Number Cc:nponent Description Open Issued l 1 Recctor Annunciator Logic Control Panel I 1-H12-P630 Circuit Breaker i 5 Cubicles P001A, P002A, And P003A Circuit Breaker l 6 RPS System A Backup Scram Circuitry Circuit Breaker i 6 C 7 Steam Leak Detection System Control Panel 1-H12-P614 Circuit Breaker r h BSEh2/ASSD-01 Page 102 of 128 Rev. O i

(.*/, TABLE 3 (Cont'd) W' EMERGENCY POWER SYSTEM DC Safe Shutdown Component: 125V DC Distribution Panel 3A Non-Safe Shutdor,i Loads (Cont'd) Circuit clearance Number Component Description Open Issued 9 C32-Feedwater Control System C32-K6A 1-H12-612 14 CSI-TIP Control And Monitor Cabinet 1-H12-P607 Circuit Breaker 15 Div I Annunciator XU-44 Logic Circuit Breaker ( Alternate Power Supply) 16 Div I Annunciator XV-36 Logic Circuit Breaker (Nonnal Power Supply) 18 Tenninal Cabinet XU-39 Circuit Breaker gQ 20 RFPT 1A Main Term Box EH b l l b, t i BSEP-2/AS50-01 Page 103 of 128 Rev. 0 l t

TABLE 3 (Cont'd) EMERGENCY POWER SYSTEM DC h Safe Shutdown Component: 125V DC 31stribution Panel 38 Normal Power Supply: 125/250V DC Seitchboard 18.Cogt. GK6 Alternate Power Supply: N/A Location: Control Building - E1. 49' - Electronic Equipment Room Safe Shutdown Loads Circuit 550 And Ind-Number Train Component Description Open Yer Closed Yer MAIN B Incoming Feeder Breaker N/A 2 B E41 Drain Valves, E11 Meter Circuit, And E51 Valves And Logic Circuit N/A Breaker 3 8 E11 Relay Logic 8 And E41 Isolation N/A Logic Circuit Breaker 4 B E21 Relay Logic Panel 1-H12-P627 gjg Circuit Breaker g 9 B RCIC Relay Logic 8 Remote Turbine Trip. And EGM Control Box Circuit n/A Breaker (Control Panel 1-H12-P621) h' 11 B ADS Rela,v Logic A And B Control Par.el N/A 1-H12-628 Circuit Breaker 12 8 Outboard Isolation Yalve Logic Control N/A Panel,1-H12-P623 Circuit Breake,- 16 B ESS Logic Cabinet H61 Circuit Breaker N/A 19 8 Trip Calibration Cabinet AQ7 (CB-XU-64) Inverter 1 Supply Breaker N/A l Nori-Safe Shutdown loads Circuit clearance Numbe r Cormonent Description Open Issued 1 Reactor Annunciator Logic Control . Par el 1-H12-P630 CircJit Breaker 5 Cubicles P0018, P002B, And P0038 Circuit Breaker 4 6 RPS System B Backup Scram Circuitry i {t. Circuit Breaker i BSEP-2/ASSD-01 Page 104 of 128 Rev. 0

g TABLE 3 (Cont'd) 'w EMERGENCY POWER SYSTEM DC Safe Shutdown Component: 125V DC Distribution Panel 3B Non-Safe Shutdown Loads (Cont'd) Circuit Clearance Nuraber Component Description Open Issued 7 Steam Leak Detection System Control Panel 1-H12-P614 Circuit Breaker 13 C32 Feedwater Control System C32-K68 1-H12-612 15 Div.11 Annun XU-45 Logic (Alternate Pwr. Supply) 17 Div. II Annun. XU-43 Logic (Normal Power Supply) 18 Terminal Cabinet XV-40 Circuit Breaker 20 RFPT 1B Hain Term. Box 'EH' hh CT BSEP-2/ASSD-01 Page 105 of 128 Rev. O

P TABLE 3 (Cont'd) EMERGGLT70ER SYSTEM DC Safe Shutdown. Component: 125V DC Distribution Panel 11A Normal Power Supply: 125/250V DC Switchboard 1A Conpt..GJ4 Alternate Power Supply: N/A Location: Control Building - El. 49' - Electronic Equipment Roon Safe Shutdown Loads. .' circuit 55D Ind Ind Number Train Component Description Open Ver Closed Ver "^ MAIN A Incoming Feeder Breaker l 1 A Trip Calibration Cabinet AQ6 gfA (CB-XU-63) Inverter 2 Supply Bresker i Non-Safe Shutdown Loads circuit clearahTe" Number Component Description Open Issued 2 Drywell Head Vent Inboard Isolation Valve 1-CAC-V49, 1-CAC-SC-1541 Circuit Breaker } 3 8.0.P. Annunc. %U-35 Logic (Normal Pwr g-Supply) 4' BOP Annunciators XU-31 To XU-34 Logic Circuit Breaker 5 Service Water Nuc. 8 Cony. Header Press Switches 6 8.0.P. Annunc. Control Circuit (Normal Supply) 7 Solenoid For Seal Staging Valve. 1-832-V14. Circuit Breaker g* Primary Bus-Generator Transf. Protect'n Relay Pnl. HJ5. 6. 7 8 8 11 $8GT System Train 1A Heat Detection Circuit Breaker 12 CAC !solattun Trip Override. DC Div. !. Keylock Isolation Override Switch Circuit Breaker G BSEP-2/ASSD-01 Page 106 of 128 Rev. 0

TABLE 3 (Cont'd) EMERGENCY POWER SYSTEM OC G Safe Shutdown Component: 125V DC Distribution Panel 11A Non-Safe Shutdown Loads (Cont'd) Circuit clearance Number Conponent Description Open Issued 14 Fire Protection Annunciator Logic Cabinet ?-CB-XV-71 Circuit Breaker 15 B.O.P. Annun. XV-46 Logic (Normal Pwr. Supply) 16 CAC Inboard LOCA Signal Trip, DC Div. I Circuit Breaker 18 Power to Annunciator Logic Cabinet 1-XU-52 Logir. Cabinet Breaker (Normal) 19 Trip Calibration Cabinet A26 And A27 (CB-XU-65 And 66) Supply Breaker R 20 Suppression Pool CAD DC Inlet Yalve 1-CAC-Y160, Control Switch 1-CAC-CS-5030, and Drywell 1-Cad-Y161, Control Switch (7;'._l 1-CAC-CS-5031, Circuit Breaker h. BSEP-2/ASSD-01 Page 107 of 128 Rev. O

TABLE 3 (Cont'd) EMERraENGY POWER SYSTEM DC Q Safe Shutdown Component: 125Y DC Distributio,n Panel 118 Normal Power Supply: 125/250V DC Switchboard IB Conpt. GL4 Alternate Power Supply: N/A Location: Control Building - E1. 49' - Electronic Equipment Room Safe S'hutdown loads Circuit 55D Ind Ind Nraber Train Component Description Open Ver Closed Ver MAIN B Incoming Feeder Breaker N/A 1 B Trip Calibration Cabinet AQ7 (CB-XU-64) Inverter 2 Supply Breaker N/A Non-Safe Shutdown Loads circuit clearance Number Component Description Open issued 3 B.0.P. Annunc. XU-35 Logic (Alternate Pwr Supply) R 4 BOP Annunciators XU-31 To XV-34 Logic Circuit Breaker (Alternate) 6 Service Water Nuc "B" Con Hdr Press. SW. 7 Solenoid For Seal Staging Valve, 1-832-Y17. Circuit Breaker 9 Backup Bus Generator & Transf. Protect'n Relay Panel HJ5. 6, 7. & 8 dternt Su p y 1?. Control poder For Non-Return Yalve. EX-V12 BreakerEX-V14. EX-V20 And EX-Y24 i Circuit i 14 Control Powei For Non-Return Yalve, EX-V11, EX-V13. EX-V19 And EX'-V23 Circuit Breaker 15 B.O.P. Annun. XU-46 Logic (Alternate Pwr Supply) i , b,) BSEP-2/ASSD-01 Pagt 108 of 128 Rev. 0 l ~-

TABLE 3 (Cont'd) EMERGENCY POWER SYSTEM DC P Safe Shutdown Component: 125V DC Distribution Panel llB Non-Safe Shutdown Loads (Cont'd) ci rcuit Glearance Number Component Description. Open Issued 1,6 Instrument Rack G31-2002-25 Ann. Ckt. 17 SBGT System Train IB Heat Detection Circuit Breaker 18 Power To Annunciator Logic Cabinet 1-XV-52 Circuit Breaker 19 Trip Calibration Cabinet A28 And A29 (CB-XU-67 And 68) Supply Breaker R p. vy b BSEP-2/ AS SD-01 Page 109 of 128 Rev. O

TABLE 3 (Cont'd) o. b.9 EHERGENCY POWER SYSTEM DC Safe Shutdown Component: 125/250V DC Switchboard 2A i Normal Power Supply: Battery Chargers 2A-1 And 2A-2 Corrpt. GKO And GK3 Alternate Power Supply: Batteries 2A-1 And 2A 2 Location: Control Building - El. 23' - Battery Room Safe Shutdown Loads Compt. 550 I nd I nd Number Train Component Description Open Yer Closed Ver GI6 A 125V DC Distribution Panel 4A Supply N/A I Breaker GJ3 A Rea: tor Building HCC 2XDA Supply N/A Breaker GJ4 A 12SV DC Distribution Panel 12A Supply N/A Breaker Z GJS A Power Conversions Unit 2A (DC Input To Primary Power Ccnverter 2A) N/A GJ6 A 125V DC Distribution Panel 2A Supply Breaker N/A g GK0 A Battery Charger 2A-1 DC Output Breaker N/A N/A GK1 A Battery 2A-1 Output Breaker N/A GK2 A Battery 2A-2 Output Creaker "^ GK3 A Battery Charger 2A-2 DC Output Breaker Non-Safe Shutdown loads ICompt. Clearance Number Component Description Open Issued GF8 CW Intake Pumps Exciter Field Temperature Power MCC 2SA Enclosure Breaker G17 125V DC Distribution Panel 4AB Alternate Supply Breaker G18 125V DC Distribution Panel 6A Normai l Supply Breaker nC Gl9 125V DC Distribution Panel 8A Normal Supply Breaker BSEP-2/ASSD-01 Page 110 of 128 Rev. 0 -n +


p

TABLE 3 (Cont'd) EMERGENCTTDWER SYSTEM DC {; Safe Shutdown Component: 125/250V DC Switchboard 2A Non-Safe Shutdown Loads (Cont'd). Conpt.. Clearance Number Component Description Open Issued GJO 125V DC Distribution Panel 10A Alternate !ipply Breaker GJ2 Turbine Building MCC 2TDA Supply Breaker GJ7 Reactor Building Emergency Lighting Contactor Supply Breaker GJ9 125Y DC Distribution Panel 17 Normal Supply Breaker R ([' (, BSEP-2/ASSD-01 Page 111 of 128 Rev. O

f, TABLE 3 (Cont'd) G EMERGENCY POWER SYSTEM DC Safe Shutdown Component: 125/250V DC Switchboard 28 Normal Power Supply: Battery Chargers 2B.1 AND 2B-2 Compt. GM1 And GM4 Alternate Power Supply: Batteries 2B-1 And 28-2 Location: Control Building - El. 23' - Battery Room Safe Shutdown Loads Compt. SSD Ind Ind gmber Train Component Description Open Ver Closed Ver G)8 B Normal Supply To Tracking Rectifier N/A Circuit Breaker GK6 B 125V DC Distribution Panel 4B Supply N/A Breaker GL3 B Reactor Building MCC 2XDB Supply Breaker N/A GL4 B 125V DC Distribution Panel 128 Supply Breaker N/A f) GL6 B 125Y DC Distribution Panel 2B Supply Breaker N/A g N/A GM1 B Battery Charger 2B-1 DC Output Breaker "^ GH2 B Battery 2B-1 Output Breaker ^ GH3 B Battery 2B-2 Output Breaker GH4 B Battery Charger 28-2 DC Output Brea) er N/A Non-Safe Shutdown Loads Compt. Clearance Number Component Description Open Issued B79 Emergency Bearing Oil Pump Starter, EBOP Circuit Breaker GK7 125V DC Distribution Panel 4AB Nortral Supply Breaker GK8 125V DC Distribution Panel 6A Alternate Supply Breaker GK9 125V DC Distribution Panel 8B Normal Supply Breaker BSEP-2/ASSD-01 Page 112 of 128 Rev. O ~

9 TABLE 3 (Cont'd) EMERGDR'17DWER SYSTEM DC (T Safe Shutdown Component: 125/250V DC Switchboard 28 Non-Safe Shutdown Loads (Cont'd) Comp t. Glearance Number Congonent Description Open Issued GL0 125V DC Distribution Panei '10A Normal Supp1,7 Breaker SL1 125V DC Distribution Pane) 13 Ndraal Supply Breaker I GL2 Turbine Building MCC 2TDB Supply Breaker GL5 Power Conversion Unit 28 (DC Input To Standby Power Converter 28) GL7 Radwaste Building Emergency Lighting Contactor Supply Breaker gl GL8 Turbine Building Emergency Lighting Contactor Supply Breaker GL9 Alternate supply To Tracking Rectifier. ,' g, Circuit Breaker l GM6 MWT Building Main Control Panel Normal l Supply Breaker 445 125Y DC Distribution Panel A0G-2 Supply Breaker i 1 i l i J I i b BSEP-2/ASSD-01 Page 113 of 128 Rev. O

TABLE 3 (Cont'd) EMERGENCY POWER SYSTEM DC f0' Safe Shutdown Component; Reactor Building MCC 2XDA Normal Power Supply: 120/250V DC Switchboard 2A Conpt. GJ3 Alternate. Power Suppfy: N/A Location: Reactor Building - E1. 20' - North Safe Shutdown Loads compt. sso Ind Inc Number Train Congonent Description Open Ver Closed Ver i L 810 A Incoming Feeder Breaker N/A i 811 A HPCI Auxiliary 011 Pung Circuit Breaker gfg 812 A HPCI Barometric Conderser Condensate Pump Circuit Breater gf3 814 A HPCI Condensate Storagt Tank Suction n/3 Valve, 2-E41-F004, Cirecit Breaker 815 A HPCI Cooling Water Supply Valve. Nf A 2-E41-F059, Circuit Breaker 816 A HPCI Pump Discharge Valve, 2-E41-F007 Circuit Breaker N/A 1 b.. s 7 817 A HPCI Injection Valve, J.E41-F006 Circuit Breaker N/A 818 A HPCI Bypass To Condensate Storage Tank Valve, 2-E41-F008. Circuit Breaker N/A 819 A HPCI Redundant Isolation Yalve To Condensate Storage Tank, 2-E41-F011 gfg Circuit Breaker i d20 A HPCI Steam Supply Outboard Isolation ' n/A Valve, 2-E41-F003, Circuit Breaker 821 A HPCI Turbine Steam Supply Valve. N/A 2-E41.F001, Circuit Breaker 822 A' HPCI Suppression Pool Suetior, Valve. N/A 2-E41-F042 Circuit Breaker a 823 A HPCI Suppression Pool Suction Valve. N/A 2-E41-F041 Circuit Braaker 824 A l@ HPCI MinirmJm Flow Bypass To Suppression Pool Valve, 2-E41-F012 Circuit Breaker N/A i QEP-2/ASSD-01 Page 114 of 128 Rev. 0 1

gra. TABLE 3 (Cont'd) Q# EHERGENCY POWER SYSTEM DC Safe Shutdown Component: Reactor Building MCC 2XDA Safe Shutdown loads Compt. SSD Ind lnd Number Train Component Description Open Ver Closed Ver

  • B26 A

RHR Suction Isolation N/A Valve 2-E11-F008 ASSO Feed I Non-Safe Shutdown Loads Compt. Clearance Number Component Description Open Issued 4 B13 HPCI Vacuum Pump Circuit Breaker a G l I l I i t

  • NOTE:

l RHR Suction Isolation Valve, 2-E114008, is normally under a Shift Foreman's l l clearance when the unit is operating. The Shift Foreman may remove this clearance at his discretion when it has been verified that maintenance on the hs? valve is not in progress. ) BSEP-2/ASSD-01 Page 115 of 128 Rev. 0 (

TABLE 3 (Cont'd) EMERGENCY. POWER SYSTEM DC ($ Safe Shutdown Component: Reactor Buildirg MCC 2XDB Nrrmal Power Supply: 125/250V DC Switchboard 2B Compt. GL3 Alternate Power Supply N/A Location: Reactor Building - E1. 23' - South Safe Shutdown Loads compt. sbu inc Inc Number Train Component Description Open-Ver Closed Yer B30 B Incoming Feeder Breaker n/a 835 B RCIC Barometric Condenser' Vacuum pus N/A Circuit Breaker B36 B RCIC Barometric Condenser Vacuum Tank N/A Condensate' Pump Circuit Breaker B37 B RCIC Turbine Trip And Throttle Valve, 2-E51-Y8, Circuit Breaker N/A B38 B RCIC Condensate Storage Tank Suction Valve, 2-E51-F010, Circuit Breaker N/A p B39 B RCIC Cooling Water Supply Valve, g 2-E51 F046, Circuit Breaker gfg B40 B RCIC Pump Discharge Valve, 2-E51-F012, Circuit Breaker yfg B41 B RCIC Injection Valve, 2-E51-F013 N/A Circuit Breaker B42 B RCIC Bypass To Condensate Storage Tank N/A Valve, 2-E51-F022. Circuit Breaker B43 B RCIC Steam Supply Outboard Isolation N/A Valve, 2-E51-F008. Circuit Breaker B44 B RCIC Turbine Steam Supply Valve, N/A 2-E51-F045, Circuit Oreaker B45 B RCIC Suppression Pool Suction Yalve, 2-E51 F031 Circuit Breaker N/A B46 B RCIC Suppression Pool Suction Valve, yfg 2-E51-F029. Circuit Breaker B47 B RCIC Minimum Flow Bypass To Suppression sfA c Pool Valve, 2-E51-F019 Circuit Breaker E: BSEP-2/ASSD-01 Page 116 of 128 Rev. O

TABLE 3 (Cont'd) EMERGENCY POWER SYSTEM DC h Safe Shutdown Component: Reactor Building MCC 2XDB Safe Shutdown Loads (Cont'd) Gorp t.- 55U And Ind Numbe r Train Component Description Open Yer Closed Ver B48 B RWCU Inlet Outboard Throttle Iso 1'ation gjg Valve, 2-G31-F004, Circuit Breaker

  • B50 B

Shatdown Cooling Outboard Suction Throttle Valve, 2-E11-F008. Circuit N/A Breaker 'B51 B RHR To Radwaste Outboard Isolation Valve, 2-E11-F040, Circuit Breaker N/A BS2 B MSL Outboard Drain Isolation Yalve, 2-B21-F019 Circuit Breaker N/A F B53 B Remote Shutdown Panel IR-RB-4 ALT. Safe Shutdown Instruments N/A Non-Safe Shutdown Loads {". Conpt. Clearance Number Component Description Open Issued B49 Reactor Yessel Head Spray Outboard Isolation Valve, 2-E11-F023 Circuit Breaker

  • NOTE:

Shutdown Cooling Outboard Suction Throttle Valve, 2-E11-F008 and RHR To Radwaste Outboard Isolation Yalve, 2-E11-F040 are normally under a 5hif t Foreman's clearance when the L, nit is operating. The Shift Foreman may remove this clearance at his discretion when it has been verified that maintenance on the valves is not in progress. (.Y BSEP-2/ ASSD-01 Page 117 of 128 Rev. O

TABLE 3 (Cont'd) j EMERETPDWER SYSTEN DC h' Safe Shutdown Component: 125Y DC Distribution Panel 2A Normal Power Supply: 125/250V DC Switchboard 2A Conpt. GJ6 Alternate Power Supply: N/A Location: Diesel Gdnerator Building - 4KV Cell 3 - E1. 38' Safe Shutdown Loads circuit sso Ind Ind . Number Train Congonent Description Open Ver Closed Ver "#^ I MAIN' A Incoming Feeder Breaker 9 1 A 4KV Emergency Bus El Alternate Control N/A Panel Circuit Breaker 2 A 4KY Emergency Bus E3 Normal Control N/A Power Circuit Breaker 3 A Diesel Generator No. 'l Alternate Power Supply For Annunciator, Start, And Load N/A Circuit Breaker R! 4 A Diesel Generator Wo. 3 Normal Power For Annunciator. Start, And Load Circuit N/A q Breaker Qri 7 A ESS Logic Cabinet H60 Circuit Breaker N/A 15 A 480V Substation E5 Alternate Control Power Circuit Breaker N/A l 16 A 480V Substation E7 Normal Control Power l g fg Circuit Breaker Non-Safe Shutdown Loadt. L1rcutt clearance Number Congonent Description Open issued 6 Diesel Generator Builtiing Emergency Lighting Contactor Supply Breaker 12 Hi-Water Level Water Jacket Isolation i Relays 14 4XV Emergency Bus E3 Test Cabinet Circuit i Breaker l 19 Flood Status {W c., i l BSEP-2/ASSD-01 Page 118 of 128 Rev. 0 ,,c-m..y-.- -.-.-m.

TABLE 3 (Ccnt'd) i: EMERGENGT POWER SYSTEM DC h Safe Shutdown Component: 125Y DC Distribution Panel 28 Normal Power Supply: 125/250V DC Switchboard 28 Cogt. GL6 . Alternate Power Supply: N/A Location: Diesel Generator Building - 4KY Cell 4 - El', 38' f Safe. Shutdown loads Circuit 55D Ind Ind Number Train Cogonent Description Open Yer Closed Ver MAIN B Incoming Feeder Breaker N/A 1 8 4KV Emergency Bus E2 Alternete sfA Control Power Circuit Breaker 2 B 4KV Emergency Bus E4 Normal Control nfA Power Circuit Breaker 3 8 Diesel Generator No. 2 Alterna+e Power Supply For Annunciator, Start, And k!/A Load Circuit Breaker 4 B Diesel Generator No. 4 Normal Power For Annunciator, Start And Load N/A Circuit Breaker R)3 1 6 B Remote Shutdown Panel RCIC Turbine EGM Control Box Circuit Breaker N/A 7 6 ESS Logic Cabinet H61 Circuit Breaker N/A 8 8 Remote Shutdown Panel Safety Relief gfg Valve Control Power Circuit Breaker 15 8 480V Substation E6 Alternate Control N// Power Circuit Breaker i 16 8 480Y Substation E8 Normal Control N/A Power Circuit Breaker j 1 Non-Safe Shutdown Loads circuit clearance Number Com on'ent Description Open Issued l 4 12 Hi-Wate-Level Jacket Isolation Relays l 1 t BSEP-2/ASSD.01 Page 119 of 128 Rev. 0

i TA8LE 3 (Cont'd) EMERGUICT7DWER SYSTEM DC (If Safe Shutdown Component: 125V DC Distribution Panel 2B Non-Safe Shutdown Loads (Cont'd) ci rcuit Glearance Number Component Description Open Issued 14 4KY Emergency Bus E4 Test Cabinet . Circuit Breaker 17 Diesel Generator Buildin Emergency Lighting Contactor Suppl Breaker 19 FIood Status 1 9 ,4 ( 51 l W i h BSEP-2/ASSD-01 Page 120 of 128 Rev. O

i i TABLE 3 (Cont'd) EMERGENGT F0WER SYSTEM DJ h Safe Shutdown Component: 125Y DC Distribution Panel 4A Normal Power Supply: 125/250V DC Switchboard 2A Coipt. GI6 Alternate Power Supply: N/A Location: Control Building - E1. 49' - Electronic Equipaent Room Safe Shutdown Loads Circuit 55D Ind Ind Number Train Component Description Open Ver Closed Vee MAIN A ' Incoming Feeder Breaker N/A 2 A E51-Yalves And Ell-Ster Circuit. N/A Circuit Breaker 3 A Ell-Relay Logic A Circuit Breaker N/A 4 A E21-Relay Logic Panel 2-H12-P626 Circuit Breaker N/A 11 A ADS Relay Logic A&B Control Panel N/A 2-H12-P628CgcuitBreaker g 12 A Inboard Isolation Yalve Logic Control gfg g Panel, T-H12-P627., Circuit Brea'ker 13 A HPCI Cont rol And Relay Logic Circuit N/A Brecker 17 A ESE logic Cabinet H58 N/A 19 A Trip Calibration Ca' binet AQ6 (CB-XU-63) Inverter 1 Supply Breaker N/A Non-Safe Shutdown Loads circuit clearance Number Cogonent Description Open Issued 1 1 Reactor Annunciator Logic Control Panel. 2-H12-P630, Circuit Breaker 5 Cubicles P001A, P002A, And P003A Circuit Breaker 6 RPS System Backup Scram Circuitry Circuit Breaker . {J) 7 Steam Leak Detection System Control Pane.1, 2-H12-P614, Circuit Breaker BSEP-2/ASSD-01 Page 121 of 128 Rev. O ~

TABLE 3 (Cont'd) e ' f s 08 EMERGENCY POWER SYSTEM DC Safe Shutdown Component: 125V DC Distribution Panel 4A Non-Safe Shutdown Loads (Cont'd) j circuit Clearance i 1 Nuigbj r Component Description Open Issued ?g Reactor Water Level B Unit Inverter Power Supply Circuit 3reaker i s UPS System Inverter 2A Indicating Lights Circuit Breaker 7 14 C51-TIP Control & Moniter Cabinet 2-H12-P607 15 Div. I Annun. XV-36 Logic (Alternate PowerSupply) 16 Div. I Annun. XV-44 Logic (Normal Power Supply) 18 Terminal Cab. XV-41 JKO h) 20 RFPT 2A Main Terminal Box EH Circuit l Breaker l 1 1 ) i BSEP-2/ ASS [i01 Page 122 of 128 Rev. O

i 1 TABLE 3 (Cont'd) EMEREllCT"FDWER SYSTEM DC "O Safe Shutdown Component: 125V DC Distribution' Panel 48 i-Normal Power Supply: 125/250V DC Switchboard 28 Cogt. GK6 Alternate Power Supply: N/A Location: Control Building - E1. 49' Electronic Equipment Room i Safe Shutdown Loads Circuit 550 Ind And i Number Train Cogonent Description Open Ver Closed Ver MAIN. 8 Incoming Feeder Breaker N/A l 3 8 Ell-Relay Logic-8 Circuit Breaker N/A l1 4-8 E21-Relay Logic Panel 2-H12-P627, afg Circuit Breaker 8 8 Control Power To Valves 2-E51-FD04, f 2-E51-F026, 2-E51-F054. Turbine N/A Supervisory (Control Panel 2-H12-P601) Lights And Inverter 2-E51-K603 i Circuit Breaker 1 9 8 RCIC Relay Logic 8. Remote Turbine i Trip. And EGM Control Box (Control N/A Panel 2-H12-P621) Circuit Brea'ker g j j 11 8 ADS Relay Logic A & 8 Control Panel, i 2-H12-P628. Circuit Breaker N/A 12 8 st>ored Isolation Valve Logic Control l Panel, 2-H12-P623. Circuit Breaker N/A I 16 8 ESS Logic Cabinet H59 N/A 19 8 Trip Calibration Cabinet AQ7 (C8-XU-64) gfg j Inverter 1 Supply Breaker [ l Non-Safe Shutdown i.oads Etreutc clearance l Number Cogonent Description 'Open Issued i 1 l Reactor Annunciator Logic Control Panel, 2-H12-P630. Circuit Breaker l 2 E51-Yalves And Ell-Meter Circuit, Circuit Breaker l hf 5 Cubicles P0018, P0028. And P0038 Circuit 3reaker BSEP-2/ASSD-01 Page 123 of 128 Rev. O

e TABLE 3 (Cont'd) EMERGENCY POWER SYSTEM DC A' Safe Shutdown Component: 125V DC Distribution Panel 4B Non-Safe Shutdown Loads (Cont'd) Gircuit clearance Number Component Description Open Issued 6 RPS System Backup Scram Circuitry Circuit Breaker 7 Steam Leak Detection System Control Panel. 2-H12-P614, Circuit Breaker 10 UPS System Inverter 2B Indicating Lights Circuit Breaker L3 Reactor Water Level C Unit Inverter Power Supply Circuit Breaker

  • 15 Div. II Annun. XV-43 Logic (Alternate Pwr. Supply) p 17 Div. II Annun. XU-45 Logic (Normal Pwr.

Supply) (> 18 Terminal Cab XU-42 J18 20 RFPT B Main Terminal Box EH Circuit Breaker (n;. BSEP-2/ASSD-01 Page 124 of 128 Rev. O

TABLE 3 (Cont'd) EMERGENCY POWR SYSTEM DC O Safe Shutdown Component: 125V DC Distribution Panel 12A ) Normal Power Supply: 125/250V DC Switchboard 2A Conpt. GJ4 Alternate Power Supply: N/A [ Location: Control Building - El. 49' - Electronic Equipe.pt Room Safe Shutdown Loads ~ Ind ' Ind Circuit .550 Number Train Component Description Open Yer Closed Ver N/A MAIN A Inco,aing Feeder ' Breaker 1 A Trip Calibration Cabinet AQ6 gfg (CB-XU-63) Inverter 2 Supply Breaker I Non-Safe Shutdown Loads clearance Gircuit Number Congonent Description Open Issued 3 B.0.P. Annunc. XU-35 Logic (Normal Pwr Supply) 4 BOP Annunciators XU-31 To XU-34 Logic Circuit Breaker (Normal) 5 Service Water Nuclear And Conventional Header Pressure Switches, 2-SW-PS-271 And 2-SW-PS-129 Circuit Breaker l 6 B,0.P. Annunc. Control Circuits (Normal f Supply) 3 Reactor Recire. Valve Sov.-832-V17 Division ! RPT Breaker Control Circuit 8 Breaker ) Primary Bus-Generator & Transf. Protect'n 9 Relay Pn1 HUS. 6, 7. & 8 11 SBGT System Train 2A Heat Detection Circuit Circuit Breaker 12 Suppression Pool 1 Inch CAD Inlet Valve 2-CAC-V160, Control Switch 2-CAC-CS-5030, And Drywell 1 Inch CAD Inlet Valve 2-CAC-V161, Control Switch 2-CAC-CS-5031, Circuit Breaker

h Rev. 0 BSEP-2/ASSD-01 Page 125 of 128

.A

TABLE 3 (Cont'd) IMERr2ENCY POWER SYSTEM DC p-Safe Shutdown Component: 125V DC Distribution Panel 12A Non-Safe Shutdown Loads (Cont'd) Circuit Clearance Number Component Description Open Issued 13 B.0.P. Annun. XV-46 Logic (Nornal Pwr. Supply) 14 Fire Protection Annunciator Logic Cabinet 2-CB-XU-71. Circuit Breaker 16 CAC Inboard LOCA Signal Trip DC Division I Circuit Breaker 17 CAC DC Division ! Isolation Override Switch, 2-CAC-CS-4337, Circuit Breaker 18 BOP Annunciator XU-52 Logic Circuit Breaker (Normal) g[ 19 Trip Calibration Cabinet A26 And 27 (CB-XU-65 And 66) Supply Breaker ?b:;' 20 Drywell Head Purge Exhaust Valve 2-CAC-Y49 Control Switch 2-CAC-CS-1541, Circuit Breater bk BSEP-2/ASSD-01 Page 126 of 128 Rev. O

TABLE 3 (Cont'd) p3 EMERGENCY POWER SYSTEM DC Safe Shutdown Component: 125V DC Distribution Panel 12B Normal Power Supply: 125/250V DC Switchboard F1 Compt. GL4 Alternate Power Supply: N/A Location: Control Building - El. 49' - Electronic Ecuipment Room Safe Shutdown loads Ci rcuit SSD I nd I nd Number Train Component Description Open Ver Closed Ver MAIN B Incoming Feeder Breaker y/A 1 B Trip Calibration Cabinet AQ7 (CB-XV-64) Inverter 2 Suoply Breaker N/A Non-Safe Shutdown Loads Ci rcuit Clearance Number Component Description Open issued t 3 B.O.P. Annunc. XV-35 Logic (Alternate Powe.r Supply) C@~~ 4 BOP Annunciators XV-31 To XU-34 Logic Circuit Breaker (Alternate). 7 Reactor Recire. Valve Sov-B32 V14 8 Division 11 RPT Breaker Control Circuit i Breaker l 9 Backup Bus Generator & Tranf. Protect'n i Relay Pn1 HJ5. 6. 7. A B 11 SBGT System Train 2B Heat Detection Circuit Circuit Breaker i 12 B.O.P. Annunc. Control Circuits (Alternate Supply) 13 Control Power For Non-Return Valve 2-EX-V12, 2-EX-V14, 2-EX-V20 And 2-EX-V24 Circuit Breaker 14 Control Power For Non-Return Valve 2-EX-V11, 2-EX-V13, 2-EX-V19 And 2-EX-V23 Circuit Breaker b 15 B.O.P. Annunc. XV-46 Logic (Alternate Pwr. Supply) BSEP-2/ASSD-01 Page 127 of 128 Rev. O

TABLE 3 (Cont'd) EMERGENCY F0WER SYSTEM DC (I[f Safe Shutdown Component: 125Y DC Distribution Panel 128 Non-Safe Shutdown loads (Cont'd) ci rcuit clearance Number Component Description Open Issued 16 Instrument Rack G31-ZOO 2-25 Annun Ckts.- 17 Service Water Nuclear & Conventional, d Heater Pressuce Switches 18 Power To Annunciator Logic Cabinet 2-XU-52 Circuit Breaker t 19 Trip Calibration Cab. RPS Chan. '31 & B2" XU-67 4 XU-68 i R ( ?b I ($$2 BSEP-2/ASSD-01 Page 128 of 128 Rev. O}}