Rev 0 to Alternative Safe Shutdown Procedure ASSD-03, Control Bldg 23 Ft Elevation Battery Room 2A
ML20205S277
Person / Time
Site: Brunswick Duke Energy icon.png
Issue date: 04/04/1988
From: Bishop E
CAROLINA POWER & LIGHT CO.
To:
Shared Package
ML20205K904 List: ... further results
References
ASSD-03, ASSD-3, NUDOCS 8811110006
Download: ML20205S277 (13)


Text

. _- _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ .

h ,

CAROLINA POWER & LIGHT COMPANY BRUNSWICK STEAM ELECTRIC PLANT UNIT 2 PROCEDURE TYPE: ALTERNATIVE SAFE SHUTDOWN PROCEDURE NUMER: ASSD-03 PROCEDURE TITLE: CONTROL BUILDING 23' ELEVATION h BATTERY ROOM 2A .

Rev. O R B.W j'

4/4/88

\Y ,,

q$N 4

ti i.

Ap,, roved By: b_ _

Date: Oill I ,,

General Manade[/Managergrations (LU fjjl110006001025 i p ADOCK 050003n4  ;  ;

PDR  ;

BSEP-2/ASSD-03 Page 1 of 13 Rev. O, l SSt t ilOLV6  !

LIST OF EFFECTIVE PAGES----

g.. . .

i ASS 0-03 Page(s) Revision, 0

1-13 M B.L I

i 1

I i

l I

! &v< ,

t i BSEP-2/ ASS')-03 Page 2 of 13 Rev. O

( __ _j

A. TITLE O Control Building 23' Elevation Battery Room 2A.

B. REFERENCES

1. Per 10CFR50 Appendix 'R' Sections III.G & L.
2. Per 10CFR50 Appendix 'R' Section III.J.

C. ENTRY CONDITION This procedure is entered from Alternative Safe Shutdown Index ASSD-01.

1. A fire has occurred in an area containing Alternative Safe Shutdown Train A equipment, Am
2. The Shift Foreman has detennined that the reactor is to be brought to Cold Shutdown using Alternative Safe Shutdown Train B.

The purpose of this procedure is to provide supplemental actions to be used concurrently with E0P's and other operations procedures to achieve and maintain Cold Shutdown coincident with or without a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> loss of g off-site power. R S.J D. OPERATOR ACTIONS

1. IFwhileexecutingthisprocedure,thefireis'$xtinguishedAND tee Shift Foreman detennines that no action wit 11n this procedure is required, THEN EXIT this procedure.
2. OBSERVE the follwing parameters on instruments indicated while performing actions to achieve and maintain cold shutdown.

Instrument Location 2-CAC-TR-778 Suppression Pool Water Temp. (Pt. 7) Remote Shutdown Panel 2-CAC-L1-3342 Torus Level Remote Shutdown Panel

2-C32-PI-3332 Reactor Pressure Remote Shutdown Panel
2-B21-L1-R604BX Reactor Water Level Remote Shutdown Panel 1

l

3. JF reactor building AND/OR diesel generator building entry is required to restore 3, monitor equipment THEN I
a. DISPATCH the following minimum manpow er for performance of this procedure:

+

Reactor Building - 2 Auxiliary Operatbrs

.,. Diesel Generator Building - 1 Auxiliary Operator BSEP-2/ASSD-03 Page 3 of 13 Rev. O a

b. OBTAIN the following keys from the Shift Foreman's Key Locker (1) ASSD Equipment Cabinet Key #148 (1) ASSD Flashlight Tool Box Key #160
c. OBTAIN Security Access Keys from SAS Security Officer located in the Control Room AND PROCURE the following equipment from the ASSD Tiiiiipment Cabinet:

For Reactor Building (2) Flashlights (2 Sound powered phones (2 Copies of this procedure (4 Remote Shutdown Keys, Serial T112 (2) Security Access Keys (2) Twenty-five foot sound powered phone extension cords For Diesel Generator Building (1) Flashlight (1) Copy of this procedure

.3 (1) Security Access Key 9 (14) Door Wedge Blocks

d. USE appropriate figures in this procedure to provide 9 access / egress routes, equ pment and comunication Q locations. R
4. PLACE Reactor Water Level ' NORMAL / LOCAL' switch, 2-B21-C5-3345 at the Remote Shutdown Panel, to the ' LOCAL' position to make level indicator 2-B21-L1-R604BX operable.
5. IF Diesel Generator operation is required, THEN BLOCK OPEN liTesel Generator Building doors, as indicated on Attachment 1, to establish ventilation for Diesel Generator operations.
6. IF RBCCW Heat Exchangers Service Water Inlet Valve, 2-SW-V106 U NNOT be operated from the RTGB, THEN Manually OPERATE 2-SW-V106.
7. IF Vital Header Cross-tie Valve, 2-5W-V118 CANNOT be operated Trom the RTGB, THEN Manually OPERATE 2-SW-Vil8.
8. IF operation of RHR Service Water System is required AND RHR

- Te~rvice Water Booster Pumps are NOT available, THEN RTFIR to OP-4.'4 i

l BSEP-2/ASSD-03 Page 4 of 13 Rev. O l

t _ _)

@ CAUTION A fire in Dattery Room 2A may prevent RCIC shutdown on high reactor vessel water level.

9. IF operation of RCIC Steam Supply Inboard Isolation Valve, TE51-F007 is required AND power is NOT available from MCC 2XC, THEN
a. PLACE the circuit breaker control switch in the OFF position for RCIC Steam Supply Inboard Isolation Valve, 2-E51-F007, at MCC 2XC compartment DS4.
b. PLACE the circuit breaker control switch in the ON position for RCIC Steam Supply Line Isolation VaWe, 2-E51-F007, ( ASSD FEED) at MCC 2XD compartment DY1.
c. IF 2-E51-F007 is required to be Open, THEN PLACE the ASSD Uylock Control Switch in the OPEN position, at MCC 2XD compartment DY1.
d. IF 2-E51-F007 is required to be Closed. THEN PLACE the MSD Keylock Control Switch in the CLOSE position, at MCC Qo 2XD~ compartment DY1.
10. IF operation of RCIC Turhine Exhaust Vacuum Breaker Valve, 9 Ft51-F062, is required AND power is NOT available from MCC 2XA, 4 THEN l  %
a. PLACE the circuit breaker control switch in the OFF position for RCIC Turbine Exhaust Vacuum Breaker Valve, 2-E51-F062, at MCC 2XA compartment DE4.
b. PLACE the circuit breaker control switch in the ON position for RCIC Turbine Vacuum Breaker Valve,-

2-E51-F062, ( ASSD FEED) at MCC 2XD compartment DW2.

c. IF 2-E51-F062 is required to be Open, THEN PLACE the ASSD Uylock Control Switch in the OPEN posTtion, at MCC 2XD campartment DW2.
d. IF2-E51-F062IsrequiredtobeClosed.THENPLACEthe MSD Keylock C6ntrol Switch in the CLOSE position, at MCC 2XD compartment DW2.

. 4 l

1 l

BSEP-2/ASSD-03 Page 5 of 13 Rev. O J

r - . _ _ .

11. IF operation of RHR Suction Isolation Valve, 2-E11-F009 is required

~h TRD power is NOT available from MCC 2XA, THEN

a. VERIFY OFF OR PLACE the circuit breaker control switch in the OFF posTtion for RHR Suction Isolation Valve, 2-E11-F009, at MCC 2XA compartment DH3.
b. PLACE the circuit breaker control switch in the ON position for RHR Suction Isolation Valve, 2-E11-7609, ,

( ASSD FEED) at MCC 2XD compartment DX5.

c. IF 2-E11-F009 is required to be Open, THEN PLACE the Uose/Off/Open ASSD Feed Kejlock Switch in the OPEN position, at MCC 2XD compartment DX5. ,
d. IF 2-E11-F009 is required to be Closed THEN PLACE the .

1Tose/Off/Open ASSD Feed Keylock Switch in the CLOSE position, at MCC 2XD compartment DX5.

12. WHEN the Shift Foreman determines:
a. Diesel Generator Building doors that were opened / blocked I open for Diesel Generator ventilation are no longer j required to be open, THEN RESTORE all Diesel Generator Building doors that were opened on Attachment 1 to the closed position.

t I& -

l Ind/Ver i b. Power is available from MCC 2XC fJr operation of RCIC 4 S(eam Supply Inboard Isolation Valve, 2-E51-F007. THEN (1) PLACE the circuit bra aker control switch in the ON position for ICIC Steam Supply Inboard IsolaEion Yalve, 2-E'A-F007, at MCC 2XC compartment DS4.

l

/
. tnt /Ver (2) PLACE the circuit breaker control switch in the OFF position for RCIC Steam Supply Line Isolation Valve, 2-E51-F007, ( ASSD FEED) at g

MCC 2XD compartment DY1.

I

/

Ind/Ver i

i

)

BSEP-2/ASSD-03 Page 6 of 13 Rev. 0 J

ij (3) PLACE the ASSD Keylock Control Switch in the

^)

'v' 0FF position, for RCIC Steam Supply Line Isolation Valve, E51-F007, at MCC 2XD compartment DY1.

/

Ind/Ver

c. Power is available from MCL 2XA for operation of RCIC Turbine Exhaust Vacuum Breaker Valve, 2-E51-F062, THEN (1) PLACE the circuit breaker control switch in the ON position for RCIC Turbine Exhaust Yaculiiii Breaker Valve, 2-E51-F062, at MCC 2XA compartment DE4.

/

Ind/Ver (2) PLACE the circuit breaker control switch in the OFF position for RCIC Turbine Vacuum Breaker Valve, 2-E51-F062, (ASSD FEED) at MCC 2XD compartment DW2.

/

Ind/Ver gg, (3) PLACE the ASSD Keylock Control Switch in the OFF position for RCIC Turbine Vacuum Breaker TaTve, 2-E51-F062, at MCC 2XD compartment DW2.

/

Ind/Ver

d. Power is available from MCC 2XA for operation of RHR

, Suction Isolation Valve, 2-E11-F009, THEN (1) PLACE the circuit breaker control switch in the ON position for RHR Suction Isolation valve 2-E11-F009, at MCC 2XA compartment OH3.

/

Ind/Ver 4

(2) PLACE the circuit breaker conirol switch in i the OFF position for RHR Suction isolation

! Valve, 2-E11-F009, (ASSD FEED) at MCC 2XD compartment DX5.

1 /

i Ind/Ver BSEP-2/ASSD-03' Page 7 of 13 Rev. 0 J

.(3) PLACE the Close/Off/Open ASSD Koylock Switch

'h. , in the OFF position for RHR $uction Isolation Valve, M 11-F009, at MCC 2XD compartment DX5.

/

Ind/Ver

e. Reactor Water Level indicator, 2-B21-LI-R604BX, is no longer required. THEN PLACE Reactor Water Level

' NORMAL / LOCAL' Switch, 2-821-CS-3345 at the Remote Shutdown Panel..to the ' NORMAL' position.

/

Ind/Ver

13. WHEN:
a. The fire is extinguished AND
b. All breakers AND/OR switches operated in this procedure are restored to their normal position AND
c. No actions within this procedure are required to achieve and maintain Cold Shutdown, THEN

, d. EXIT this procedure.

h Date/ Time Completed

, Performed By (Print) Initials 4:

l r

Reviewed By:  !

Shift Foreman

\

P 8

k i

BSEP-2/ASSD-03 Page 8 of 13 Rev. 0

merAn t-A*Nt*5t"AMN> gg j l

ro umr no.s ro v:ar w.I GEACTC) gof,,, Eh* 30'* 0.*

CEACf10

, Q Q EL . 50'- 0.*

~~ ......... ,......------ -

c------- - ------ -

j;q ~,

  • 11S V 0137. l " " *'

IU b '

00*H 'fg#{A'$

lf"'*# ,

00WN

,,r.,0 .. -

1 y 'f.9 3

Ay ,

,,f.

$1512 l ~~~Gy[p~g'3 g l CYR l l

l' 2-Mit =P620 ~ l C  !=Mi2 *!*]! ,

l . .

CONTMOL ,,,, I l-Mit=P014

\

j , , . , , ,

if M00. --

p i -

'l l (l l 4k 2-M/2 = P 614 ~

  • l' D l I= NI2 = P
l a.uis-ross i i i i l I lais-ress ' 'l g

' i l - -

EF" __

l issy 0127.

s,,, y of,7, PNL 4A g, y *., gs !N ##

1 70.' OIESEL GENEMATOM BUILDING, SERVICE WATEM CUIL0lNeoMEACTQM DUILDING AND THE EAST YARD K B.,

p CONTMOLLEO ACCESS EMEEECWAY_

(q:' 00en 123/230V OC I23/tSov OC SWITCHBOAR0 /8 4 ge,y =

= = $ WITCH 80AMD 20

- y __ u 9,

' =~ '

am o.p - f1, y*. , ll.*, , y n 0,<,.e et.

I. nO um 4-Q g

L

  • gr.
  • gr q w, 190lP90ff LOCKEA "

N ."" " N *llP= "'""" *""'l

^

C A T T CM A n64 R y &

DArr CHARetR \

srtM satrcuts q .f t

,/ staa suorcuts

,,, m We=A RA . pg N0

  • A UNIT t CARLt sArr. sArr. . UNIT l CABLE SPMtA0 entA
    • **- S!ntAo AntA l -

o T--- - '-

_,,- 2 123/230V OC EL. 23'-O*_ %I2S/250V CC

, sw/TCHs0AMD 2A) SWITCHs0Anu I A LEGEND

~ ~ ~ ACCESS /E0ntSs f PHONC JACM, TMAIN A CR R FIGURE 1

'm Control Building 23'0" and 49'0" Elevations Access / Egress l' and Sound Powered Phone Comunications BSEP-2/AS$0-03 Page 9 of 13 Rev. 0 a

N0DYN  !

UNIT 2 MEACTOM BUILDING l h ige r -- 6 C sft 6  :

l f

r , I ,,

ro e rnou - I ~ **

so'-o

  • es,ewruon I

jy/'s*o *o 'e*levarma 3

  1. "exa togap DRYWELL 2xatossi- = ,

=

. f,'\

M p~

w< - -

,U.,, )

.t..

r.$e, nsor  ;

MN0rt ] .

sMoroorn PAMgL W y, \ "1E l (g};

ro a rnou )s .'} a

%\ \\\$

so'-o* EltyArnw- lII i

\I l

Y  %

I

/

/ -':::::L 70 eFMou EL EVATION .I7'd-

~ / e a',

ygggy m'* MC02x0

-. - -- -gy .

ELEVATION 20'-0*

LEGEN0

~ ~ ~ ~ ACCES$/tGRESS f PHONE ./ACK, TRAIN A OR 8 e /$0 LATE SwirCM FIGURE 2 Unit 2 Reactor Building 20'-0" Elevation - Access / Egress and

("i Sound Powered Phone Conrunications Page 10 of 13 Rev. 0 BSEP-2/ ASS 0-03

..--_.._--____.J

g  :-

UNIT 2 REACTOR BUILDING NORTN l

d 2 til-F0608 (ELEY. 44 0")%* . -2= fit =F000A a qV (EL&, SS'=0")

M * ""

20'O fttv-~-

8

, f %r,0 ,.oe.,Fn0u,,,, egy l

= '

04YlrrLL l l

ga ,

/ ~

? & e= = ,/ _ n e.

2 -Sw V!06 - - e. ==

s . i r. -

TO & FROM N k 5 N

~ "

ELEYATION  !' -: I n I 2 sw- -

EL.50 4 nunsw r<iups V106 LENNO ummmmmmmmur-

- ~ ~ ACCESS /t0RtSt E VALVES FIGURE 3 Unit 2 Reactor Building 50'-0" Elevation - Access / Egress L.

BSEP-2/ASSD-03 page 11 of 33 g,y, g

uNtr 2 CEACTOM RUIL0 LNG noorn

~

So N

/ \

CMYWELL

\ /

~

7 0 e F n ont LLIVMmN 20' 0" A /

R S.c TO O FROM i ann nuts "

g%.3

/

f n n ELEVATION 20'-0" E L. 17'-0 * , , o.,

SEE DETAIL EL 9'-0" - *  % LA00ER

\\

' d s .,

% p~~%w

  • Lggggy GRATING "

/ J

- - - A CCESS/ EGRESS / yp n VALVES RHR HX' -

LLA00ER g.s w.Vili 2-SW Vili gg, (Appyox) +2'- 0

  • EL. (APPROX)~2 O ,.

EL . 9 '- 0 "

========r- -

FIGURE 4 Unit 2 Reactor Building -17' -0" Elevation - Access / Egress '

b B!EP-2/ ASS 0-03 Page 12 of 13 Rev. 0

-)

~

3 DIESEL GENERATOR VENTILATION i

(-) 1. OPEN/BLQCK OPEN doors identified on drawing below, EXCEPT doors #103, #104, #105.

2. BLOCK OPEN doors usihg. door wedge blocks.

,et at 10 3 IOS 10 6 10 7 IOS 109 11 0 111 11 2 ll3 ll4 lol 04 2

t" t"3/ "I-- F!

@; p a F" .-- f t",

pu l

g --

!. [

g. I.1 i-

. ct l a .Ii-i - T

<a 1

. che :s ,

b  !

1

!ia ('l1' !:i '(l'1' !i '(')j"5'l" R '

W i ,

s I (/n i s I w re I I I I w asl s R G..

10 2

  • s  !

l aaaas . . . . . P""" s .

?-------- "--------*--------*,--------l---------L--------$

EL. 2 3'-0"  !

l l

l l

i

3. WHEN the fire has been extinguished. OPEN doors #103, #104,
  1. 105, for additional ventilation.

l ATTACHMENT 1 Diesel Generator Building Door Position For

(,L' Diesel Cell Ventilation l

l BSEP-2/AS50 03 Page 13 of 13 Rev. O