- AVER AGE DAILY VNIT POWER LEVEL DOCKET NO. 50-260 UNIT Turkey Point 3 DATE 11/14/85 COMPLETED BY N.W. Grant TELEPHONE (305)S52-3675 October,1985 MONTH DAY AVER AGE DAILY POWER LEVEL (MWe Net) 10/ 1/85 681 10/ 2/85 681 10/ 3/85 676 10/ 4/85 676 10/ 5/85 676 10/ 6/85 676 10/ 7/85 670 10/ 8/85 630 10/ 9/85 682 10/10/85 682 10/11/85 631 10/12/85 335 10/13/85 671 10/14/85 676 10/15/85 328 10/16/85 -23 10/17/85 364 10/18/85 629 10/19/85 358 10/20/85 616 10/21/85 34 10/22/85 -1g 20/23/85 -3 10/24/85 -3 10/25/85 -3 10/26/85 _3 10/27/85 _3 10/28/85 _3 10/29/85 _3 10/30/85 -3 10/31/85 _3
( 8601080666 851030 Q PDR ADOCK 05000250 R PDR I lN l )
OPERATING DATA REPORT DOCKET NO 50 - 250 DATE 11/ 7/85 COMPLETED BY N. W. GRANT OPERATING STATUS TELEPHONE 305/552/3675
- 1. UNIT NAME: TURKEY POINT UNIT 3
- 2. REPORTING PERIOD: OCTOBER 1985
- 3. LICENSED THERMAL POWER (MWT): ______________
4.
2200 NAMEPLATE RATING (GROSS MWE): ______________ 760
- 5. DESIGN ELECTRICAL RATING (NET MWE): ________
6.
693 MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): ___ 700 JT . MAXIMUM DEPENDABLE CAPACITY (NET MWE): _____ 666 8.
IF CHANGES SINCE OCCUS IN LAST REPORT, CAPACITY GIVE RATINGS (ITEMS NUMBER 3 THROUGH 7)
REASONS:
- 9. POWER LEVEL TO WHICH RESTRICTED,__________________________________________________________
IF ANY (NET MWE) ________________________
- 10. REASONS FOR RESTRICTIONS, IF ANY:
MONTHLY -YTD- CUMULATIVE
- 11. HOURS IN REPORT PERIOD: _________________ 745 7296 113145.6
- 12. NUMBER OF HOURS REACTOR WAS CRITICAL _____ 451.0 4183.6 77856.4
- 13. REACTOR RESERVE SHUTDOWN HOURS __________
14.
0.0 0.0 844.4 HOURS GENERATOR ON-LINE _________________ 447.6 4032.0 77211.1
- 15. UNIT RESERVE. SHUTDOWN HOURS _____________ 0 0 121.8
- 16. GROSS THERMAL ENERGY GENERATED (MWH) ____ 906410 8547139 159676650
- 17. GROSS ELECTRICAL ENERGY GERERATED (MWH) _ 289540 2T86980 51042675
- 18. NET ELECTRICAL ENERGY GENERATED (MWH) 272373 2627000 48324206
~19.
UNIT SERVICE FACTOR _____________________ ___ 60.1 55.3 68.2
- 20. UNIT AVAILABILITY FACTOR ________________ 60.1 55.3 68.3
- 21. CAPACITY FACTOR (USING MDC NET) _________ 54.9 54.1 65.7
- 22. CAPACITY FACTOR (USING DER NET) _________ 52.8 52.0 61.6
- 23. UNIT FORCED OUTAGE RATE _________________ 39.9 14.0 6.8
- 24. SHUTDOWNS SCHEDULED OVER.NEXT 6 MONTHS :
- 25. IF SHUT-DOWN AT END OF REPORT PERICD, ESTIMATED DATE OF STARTUP: 11/ 6/85
1 of 2 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-389 -
UNIT NAME Turkey Pt. Unit #3 DATE 11 14 '15 REPORT MONill October, 1985 COtti,ETED BY Nu nrant TEL.EPHONE (30t)S57_3575 "i -
No Date i
5E 3 ij 3
h Ei 255 Licensee Event 5%
g 'g k? Cause & Corrective Attion to
$5 5 0 j di y Report a 'n 0 Prevent Recurrence b
15 851011 S 0.0 H 5 EB TRANSF Power was reduced to below 50% to take a startup transformer out of service for switchyard modifications.
The unit was then returned to full power operation.
16 851015 F 42.6 G 3 250-8S-032 HA RELAYX Protective relays tripped the generator resulting in a turbine /
reactor trip. The most probable cause of the relay actuation was accidental jarring of the relays.
The unit was taken to hot shutdown due to an AFW pump being out of service for maintenance. Upon completion of the root cause evaluation, the unit returned to full power operation.
I 2 3 4 i Forced Reaum: Method: Exhibit G - Instructions
% Stheduled A-lquipment Failure (Explain) 1 Manual for Preparation of Data R. Maintenance or Test 2 Manual Scram. Entry Sheets Ior Licensee C-Refueling 3 Automatic Scram. Event Report (LERI Fde tNURLG-D-Regulatory Restrictmn %Other i Explam) 016li I -Operator Trainmg & lxense I~sammation F- Administ rative ,
5 G Operational I e ror (liplatn) c _ 4e e neve.,..cl F stubit 1 - Same Source l9/77) Il-Other iI splam)
2 of 2 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. En_74n UNIT NAME _T_iJrkey Point Unit #3 DATE 11 14-85 REPORT MONIN ' 0ctober, 1985 COMPLETED BY n u r:,-a n t TELEPHONE @ }5523g5
. T -
g
=_ .. 3 -
" D e
~. Ie E gsy Licensee 5 **, g". Cause a Correttive i 5? 4 2sE Event u7 Action to 53 E j d5 j Report a iN G }qL Prevent Resurrence 6
17 851018 S 0.0 H 5 EB TRANSF Power was reduced to below 50% to take a startup transformer out of service for switchyard modifications.
The unit was then returned to full power operation.
18 851021 F 254.8 B 1 HC HTEXCH Following a power reduction for secondary chemistry control, the unit was shutdown to replace a. condenser bo >t seal and to align reactor coolant pump motors. Following repairs, the unit returned to full power operation on November 6,1985.
I 2 3 4 I Forced Reasim: Method: Exhibit G Instructiims
% Scheduled A Lympment Failure (Explain) 1 -Manual for Preparation of Data R. Maintenance or Test 2 Manual Scram. Entry Sheets for Licensee C-Refueling 3 Automatic Scram.
D Regulatory Restriction Event Rerort (LERI File int!RLG-
$0 her (Explain 1 0161I I Operator Training & LAenw I samination F-Atlmimstrative 9, %
G Operatomal I esur il splamt g_ t o e c o ve.,..cf I:sinbit 1 Same Simrce l's/ 77 ) Il Other il splami
SUMMARY
OF OPERATING EXPER.TEMCE DOCKET.NO. 50-250 UNIT Turkey Point Unit #3 _
DATE November 14, 1985 COMPLETED BY N. W. Grant TELEPHONE (305)SS2-3675 REPORT HONTH Jctober,1985 See the " unit shutdowns and power reductions" report.
. AVERAGE DAlt.Y UNIT POWF.R LEVEL DOCKETNO. 50-251 UNIT Turkey Point 4 DATE 11/14/85 N.W. Grant COMPLETED BY TELEPHONE (305)552-36/5 MONTH October.1985 DAY AVER ACE DAILY POWER LEVEL (MWe Net) 10/ 1/85 679 10/ 2/85 668 10/ 3/85 671 10/ 4/85 671 10/ 5/85 671 10/ 6/85 668 10/ 7/85 672 10/ 8/65 676 10/ 9/85 680 10/10/85 677 10/11/85 592 10/12/85 340 10/13/85 666 10/14/85 662 10/15/85 668 10/16/85 670 10/17/85 674 10/18/85 633 10/19/85 367 10/20/85 679 10/21/85 680 10/22/85 680 10/23/85 680 10/24/85 684 10/25/85 683 10/26/85 684 10/27/85 682 10/28/85 678 10/29/85 674 10/30/85 673 10/31/85 676 l-
OPERATING DATA REPORT D CKET NO 50 - 251 DATE 11/ 7/85 COMPLETED BY N. W. GRANT TELEPHONE 305/552/3675 OPERATING STATUS
- 1. UNIT NAME: TURKEY POINT UNIT 4
- 2. REPORTING PERIOD: OCTOBER 1985
- 3. LICENSED THERMAL POWER (MWT): ______________ 2200
- 4. NAMEPLATE RATING (GROSS MWE): ______________ 760
- 5. DESIGN ELECTRICAL RATING (NET MWE): ________ 693 6.
7.
MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): ___ 700 8.
MAXIMUM DEFENDABLE CAPACITY (NET MWE): _____ 666 IF CHANGES OCCUS IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7)
SINCE LAST REPORT, GIVE REAGONS:
- 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE)
- 10. REASONS FOR RESTRICTIONS, IF ANY: ________________________
MONTHLY -YTD- CUMULATIVE
- 11. HOURS IN REPORT PERIOD: _________________ 745 7296 106877.0
- 12. NUMBER OF HOURS REACTOR WAS CRITICAL _____ 745.0 6636.4 76354.7
- 13. REACTOR RESERVE SHUTDOWN HOURS __________ 0.0 0.0 166.6
- 14. HOURS GENERATOR ON-LINE _________________ 745.0 6587.2 73827.3
- 15. UNIT RESERVE SHUTDOWN HOURS _____________ 0 0 31.2
- 16. GROSS THERMAL ENERGY GENERATED (MWH) ____ 1582133 14133585 156263691
- 17. GROSS ELECTRICAL ENERGY GERERATED (MWH) _. 508845 4546575 49738972
- 18. NET ELECTRICAL ENERGY GENERATED (MWH) ___ 484462 4318829 47102110
- 19. UNIT SERVICE FACTOR _____________________ 100.0 90.3 69.1
- 20. UNIT AVAILABILITY FACTOR ________________ 100.0 90.3 69.1
- 21. CAPACITY FACTOR (USING MDC NET) _________ 97.6 88.9 67.8
- 22. CAPACITY FACTOR (USING DER NET) _________ 93.8 85.4 63.6
- 23. UNIT FORCED OUTAGE RATE _________________ 0 8.2 6.3 24.. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS :
REFUELING 1/86, 11 TO 12_ WEEKS _________________________________________
- 25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: ________
p..
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-251 .
UNIT NAME Turkey Pt. Unit #4 DATE 11-14-85 REPORT MONnt October 1985 COMPLETED BY M u nrant TELEPHONE Mn5}557_7c75
. % ~
= .. 3 .: s Nii 1)aic 1 -
5_5 2
3 Eb
.c 's oc Even' =7 h o
" A b**
Attion to
- iN 0 0
$I ic j di g Report sr Prevent Recurrence d
20 851011 S 0.0 H 5 EB TRANSF Power was reduced to below 50% to take a startup transformer out of service for scritchyard modifications.
The unit was then returned to full power operation.
21 851018 S 0.0 H 5 EB TRANSF Power was reduced to below 50% to take a startup transformar out of service for switchyard modifications The unit was then returned to full power operation.
I 2 3 4 F Forced Reason: Method: Exhibit G - Instructitms 5
Scheduled A-Lyuspment Failure (Explain) 1 Manual for Preparation of Data R.Mairtenance or Test 2 Manual Scram. Entry Sheets for Licensee C Refueling 3 Automatic Scram. Event Report (LER) File (NUREG-D-Regulatory Pestriction @-Other (Explain) 01611 1.-Operator Training & 1.acense Fsamination F. Administrative ,
5 G Operational I nor Ii xplam) s g.o ao 44 eve ,. .d Esinbit I Same Source t'8/ 77 ) Il-Ot her I E xplain) 1
SUIG1ARY OF OPERATINC EXPER.TEMCE DOCKET NO. 50-251 UNIT Turkey Point Unit #4 DATE November 14, 1985 COMPLETED BY N. W. Grant
-TELEPHONE (305)552-3675 REPORT MONTH October,1985 See the " unit shutdowns and power reductions" report.
=
I l
l u- .
. AVER AGE DAILY UNIT POWER LEVEL DOCKETNO.60-334 UNIT St. Lucie Unit 1 DATE 11/14/85 COMPLETED BY N.W. Grant TELEPHONE (305)S52-3675 MONTH October,1985 DAY AVERAGE DAILY POWER LEVEL (MWe Net) 10/ 1/85 812 10/ 2/85 813 10/ 3/85 812 10/ 4/85 809 10/ 5/85 810 10/ 6/S5 805 10/ 7/35 802 10/ 8/85 802 10/ 9/85 794 10/10/85 792 10/11/85 792 10/12/85 790 10/13/85 785 10/14/85 775 10/15/85 766 10/16/85 762 10/17/85 757 10/18/85 750 3 10/19/85 732 '
10/20/85 -1 i 10/21/85 -6 l 10/22/85 -3 10/23/85 -3 10/24/85 -3 10/25/85 -3 10/26/85 -3 10/27/85 -3 10/28/85 -3 10/29/85 -3 10/30/85 -3 10/31/85 -3 l
l l
u
OPERATING DATA REPORT DOCKET NO 50 - 335 DATE 11/ 7/85 COMPLETED BY N. W. GRANT TELEPHONE 305/552/3675 OPERATING STATUS "
- 1. UNIT NAME: ST. LUCIE UNIT 1
- 2. REPORTING PERIOD: OCTOBER 1985
- 3. LICENSED THERMAL POWER (MWT): ______________ 2700
- 4. NAMEPLATE RATING (GROSS MWE): ______________ 850
- 5. DESIGN ELECTRICAL RATING (NET MWE): ________ 830
- 6. MAXIMUM DEPENDABLE CAPACITY (GROSSs MWE): ___ 872
- 7. MAXIMUM DEPENDABLE CAPACITY (NET M4E) : _____ 827 8.
IF CHANGES OCCUS IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7)
SINCE LAST REPORT, GIVE REASONS:
~
~ ~
9.
P6U5R LEVEL
- 10. REASONS ~f6~EEiUU~E55TRICTE6[~iF FOR RESTRICTIONS, IF ANY: AUY~iU5T kEE5[_~~~(([_~~~~((_
MONTHLY -YTD- CUMULATIVE
- 11. HOURS IN REPORT PERIOD: _________________ 745 7296 77688.0
- 12. NUMBER OF HOURS REACTOR WAS CRITICAL _____ 458.3 7005.3 56026.6
- 13. REACTOR. RESERVE SHUTDOWN HOURS __________ 0.0 0.0 205.3
- 14. HOURS GENERATOR ON-LINE _________________ 457.8 7001.8 55735.3
- 15. UNIT RESERVE SHUTDOWN HOURS ;____. ,______ 0 0 39.3
- 16. GROSS T8ERMAL ENERGY GENERATED (MWH) ____ 1214386 18656593 140794129
- 17. GROSS ELECTRICAL ENERGY-GERERATED (MWH) _ 380220 6167990 46026645
- 18. NET ELECTRICAL ENERGY GENERATED (MWH) ___ 357920 5852546 43414894 i 19. UNIT SERVICE FACTOR _____________________ 61.4 96.0 71.7
- 20. UNIT AVAILABILITY FACTOR _________________ 61.4 96.0 71.8
- 21. CAPACITY FACTOR (USING MDC NET) _________ 58.1 97.2 70.2
- 22. CAPACITY FACTOR (USING DER NET) _________ 57.9 96.6 68.7
- 23. UNIT FORCED OUTAGE RATE _______,__________ O .1 4.2
- 24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS :
- 25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: 12/22/85
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-33 r; UNIT N AME st- 1 incia finit #1 DATE 11-!A 95 REPORT MONTil nc+nhor 1485 TELEPHONE fanqiEq?_167; e.
- E c N. .. Date
. 3E 3 j E5 Licensee ,E*, {". Cause & Corrective i 3g i 2s& Event
{? Action to
- $: 5 j p, g Report 8 mO g{ Prevent Recurrence 6
03 851020 S 286.2 C 1 RC FUELXX Unit #1 was shutdown for refueling and scheduled maintenance.
I 2 3 4 F. Forced Reason: Method: Exhibit G Instructisms N Scheduled A-Equipment Failure (Explain) 1 Manual for Preparation of Data B-Maintenance of Test 2-Manual Scram. Entry Sheets for Licensee C Refueling 3 Automatic Scram. Event Report (LER) File (NUREG-D-Regulator) Restriction $0ther (Explain) 0161)
I.-Operator Training & Ucense Fxamination F Administrative ,
5 G Operational I iror Iliplain t s . /.o ao Movc.,. .ct E stubit I - Same Source 19/77) Il-Os her iI:splain )
SUMMARY
OF OPERATING EXPERIENCE DOCKET NO. 50-335 UNIT St. Lucie Unit #1 DATE November 14, 1985
-COMPLETED BY N. W. Grant TELEPHONE (305) 552-3675 REPORT MONTH nntnhor. 14R5 Unit #1 was shutdown .for refueling and scheduled maintenance.
In accordance with requirements of NUREG-0737 Item II.K.3.3, there were no challenges to PORV or safety valves during the report month.
. AYERAGE DAILY UNIT POWER LEVEL DOCKETNO. 50-389 tmlir St. I ncio Unit 2 DATE ll /14 / A6 COMPLETED BY fl.J. Grant TELEPHONE (305)552-3676 October,1985 MONTH DAY AVER AGE DAILY POWER LEVEL IMWe Net) 10/ 1/85 840 10/ 2/85 840 10/ 3/85 812 10/ 4/85 802 10/ 5/85 850 10/ 6/85 839 10/ 7/85 797 10/ 8/85 788 10/ 9/85 849 10/10/85 84g 10/11/85 349 10/12/85 848 10/13/85 347 10/14/85 g45 10/15/85 345 10/16/85 845 10/17/85 846 10/18/85 g44 10/19/85 843 10/20/85 845 10/21/85 g47 10/22/85 849 10/23/85 g49 10/24/85 846 10/25/85 846 10/26/85 847 10/27/85 g47 10/28/85 g49 10/29/85 s47 10/30/85 547 10/31/85 845
OPERATING DATA REPORT DOCKET NO 50 - 389 DATE 11/ 7/85 COMPLETED BY 'N. W. GRANT OPERATING STATUS TELEPHONE 305/552/3675
- 1. UNIT NAME: ST. LUCIE UNIT 2 i
- 2. REPORTING PERIOD: OCTOBER 1985
- 3. LICENSED THERMAL POWER (MWT):
4 ______________ 2700 NAMEPLATE RATING (GROSS MWE): ______________ 850
- 5. DESIGN ELECTRICAL RATING (NET MWE):
- 6. ________ 830 MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): ___ 882 7.
MAXIMUM DEPENDABLE CAPACITY (NET MWE): _____ 837 8.
IF CHANGES SINCE OCCUS IN LAST REPORT, CAPACITY GIVE RATINGS (ITEMS NUMBER 3 THROUGH 7)
REASONS:
- 9. POWER LEVEL TO WHICH RESTRICTED,__________________________________________________________
IF ANY (NET MWE) ________________________
- 10. REASONS FOR RESTRICTIONS,_IF ANY:
MONTHLY -YTD- CUMULATIVE
- 11. HOURS IN REPORT PERIOD: _________________ 745 7296
- 12. 19585.0 NUMBER OF HOURS REACTOR WAS CRITICAL _____ 745.0 6051'.6 16657.8 13.
- 14. REACTOR RESERVE _ SHUTDOWN HOURS _________ 0.0 0.0 0.0
- 15. HOURS GENERATOR ON-LINE __________________ 745.0 5990.3 16190.9
- 16. UNIT RESERVE SHUTDOWN HOURS _____________ 0 0 0 GROSS THERMAL ENERGY GENERATED (MWH) 1986668 15611074.
____ 40969639
- 17. GROSS' ELECTRICAL ENERGY GERERATED (MWH) _ 659510 5227050 13676750
- 18. NET ELECTRICAL ENERGY GENERATED (MWH) 625794 4942540 12904952 19.
UNIT SERVICE FACTOR _____________________ ___ 100.0 82.1 82.7
- 20. UNIT AVAILABILITY FACTOR ________________ 100.0 82.1 i
- 21. CAPACITY FACTOR (USING MDC NET) _________ 82.7 l R2 2. 100.4 82.4 -82.4 CAPACITY FACTOR (USING DER NET) ______ 101.2 82.4
- 22. 81.3 UNIT FORCED OUTAGE RATE __________________ __ 0 14.9 11.2
- 24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS :
REFUELING, 2/86-7 WEEKS ___________________________________________
- 25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
L
DOCKET NO.
- 9 '
UNIT SHUTDOWNS AND POWER REDUCTIONS UNIT NAME St_Iticie tinit #2 DATE 11 la RR COMPLETED BY Mu nrant REPORT MOND{ Octab$M985 TELEPHONE IanRiRR?_1474 jg 3 Eh Licensee ,E g . Cause & Corrective 1)Jle Ni i .
i 3g il 2s& Event 37 .
Action to F j= 5 jisg Repor e in U g Prevent Recurrence 6
Unit #2 had no shutdowns or significant power reductions.
3 i 2 3 4 F Forced Reason : Method: Exhibit G -Instructions 5
St hed uled A Equipment Failure (Explain) 1 Manual for Preparation of Data B Maintenance or Test 2-Manual Scram. Entry Sheets for Licensee C Refueling 3 Automatic Scram. Event Repori I LE R) File (NUREG-I) Regulatory Restriction 3-Oiher (Explairi) 016I) 1 Operator Training & Ixense rsamination F Administrative M~ C'*"*" "" 5 G Operational I sent (tiplain) 4_ toao Mow.i. .et Estubit I Same Source 19/77) Il-Ot her ( E uplain )
SUMMARY
OF OPERATING EXPER.TENCE DOCKET .NO. 50-389 UNIT St. Lucie Unit #2 -
DATE November 14, 1985 COMPLETED BY N. W. Grant TELEPHONE (305) 552-3675 REPORT MONTH nr+nhor l anc; Unit #2 operated at essentially full power and had no unit shutdowns or significant power reductions.
In accordance with requirements of Technical Specificaton 6.9.1.6, there were no challenges to PORV or safety valves during the repor.t month.
i
g P.O. BOX 029100 MI AMI, F L 33102 et
^^'
Whalva Rhi J' ,
- k. - -.
sueesrmW+ 5 FLORIDA POWER & LIGHT COMPANY November 14, 1985 L-85-434 Director, Office of Resource Management U.S. Nuclear Regulatory Commission Washington, D. C. 20555
Dear Sir:
Attached are the October 1985 Operating Status Reports and Operating Summary Reports for Turkey Point Units No. 3 and 4 and St. Lucie Units No. I and 2.
Very truly yours,
/ , YJ.W.WJi
&<A W s, Jr.
V Group JV e President Nuclear Energy JWW/NWG: mis Attachment cc: Dr. 3. Nelson Grace Harold F. Reis, Esquire PNS-LI-85-391/1 Y