- _

,c-

public service company of Cesarado
  • 16805 Road 19 1/2, Platteville, Colorado 80651-9298 s

January 4, 1982 Fort St. Vrain Unit No. 1

  • A P-82001 #

g A RECEIVED E JAN 1'11982 >

Mr. John T. Collins, Regional Administrator Region IV unmanarme N,mais m a O' Nuclear Regulatory Commission  %

611 Ryan Plaza Drive /

6 Suite-1000 TG' Arlington, Texas 76011

Reference:

Facility Operating License No. DPR-34 Docket No. 50-267

Dear Mr. Collins:

Enclosed please find a copy of Reportable Occurrence Report No. 50-267/81-073, ; inal, submitted per the requirements of Technical Specification AC 7.5.2(b)1.and AC 7.5.2(b)2.

Also, please find enclosed one copy of the Licensee Event Report for Reportable Occurrence Report No. 50-267/81-073.

Very truly yours,

<- Wauk Don Warembourg #

Manager, Nuclear Production DW/cis Enclosure cc: Director, MIPC B201130031 820104 . 7 PDR S ADOCK 05000267 PDR, (t

I

_ _ _ _ __ --_.-- - - J

. St REPORT DATE: January 4, 1982 REPORTABLE OCCURRENCE 81-073 ISSUE 0

- 0CCURRENCE DATE: December 8.-1981 Page 1 of 4-FORT ST. VRAIN NUCLEAR GENERATING STATION PUBLIC SERVICE COMPANY OF COLORADO 16805 WELO COUNTY ROAD 19 1/2 PLATTEVILLE, COLORADO - 80651-9298 REPORT NO. 50-267/81-073/03-L-0 Final IDENTIFICATION OF OCCURRENCE:

While performing routine surveillance calibration testing with the

!. reactor shutdown, the " circulator 1A bearing drain pressure low"

! switch (PDIS-21321) was found to be out of tolerance per the limits specified in LCO 4.4.1, Table 4.4-3.

This condition is reportable per Fort St. Vrain Technical Specification AC 7.5.2(b)1 and AC 7.5.2(b)2, because. reactor operation had taken place since the last successful surveillance l

calibration.

EVENT DESCRIPTION:

On December 8, 1981, while the reactor was shutdown and cooled down,

~

instrument personnel performed the helium circulator drain pressure calibration check. This surveillance is required at each refueling period; however, due to a lengthy shutdown for a. major. system modification, the surveillance was initiated at this time also.

There are twelve helium circulator bearing drain pressure low switches, three per circulator. When two of the three switches for a circulator operate, the circulator will trip. The LCO 4.4.1 limit for the switch trip settings is greater than or equal to 5 psid per Table 4.4-3, item 5. The results of the surveillance performed on December 8, 1981, for Loop 1 are listed in Table 1.

The surveillance requirer each switch to close at 6.5 1 1 psid.

PDIS-21321 for "A" circuistor was found to close at 0.0 psid. The remaining two channels on the 1A circulator were coerable per the Technical Specificatinns.

CAUSE DESCRIPTION:

Upon investigation of the switch internals, it was found that the low pressure trip contacts had a dirt and oil accumulation. This buildup prevented the contact from operating at the desired setpoint of 6.5 il psid.

l ... - .

i .

a

. , , , _ _ , , _ __ , _ _ ____._,__.__m.m._____ ____._

-:-~ 4 6 REPORTABLE OCCURRENCE 81-073 ISSUE O

{-

.Page 2 of 4 ,

4 7-CORRECTIVE' ACTION:

The switch internals were thoroughly cleaned and checked. -The switch was then re-adjusted to the correct trip setting o f. 6.5 psid. The l_

switch was-retested and found_to operate correctly.

No further correcti_ve action is anticipated or reoutred.

l-4 4

f w -

\

TABLE 1 SURVEII1ANG REQUIREMENT SR 5. 4.1. 3.5. c-R LOOP 1 RESULTS 8-81 4

REQUI RED PIESSURE VOLTIEn:R TRIP SETTING AS FDIND AS LEFT CI RCULATOR SUIT 01 READING (PSID) (PS ID) (PSID)

PDIS-21323 0 6.5 + 1.0 6.5 6.5 1A P DIS-21321 0 6.5 + 1.0 0.0 O _

6.5 PDIS-21319 0 6.5 + 1.0 6.5 6.5 PDIS-21325 0 6.5 + 1.0 6.5 6.5 gGA

%EE mn w -4 IB P bis-2132 7 0 6.5 t 1.0 9.0 b 6.5 o

$5 m

a PDIS-21329 0 6. 5 + 1. 0 6.5 6.5 R M

k

@ Denotes switch which was out o f to le ran ce. 5 m

@ Switch out of tolerance in mre conservative direction. y

o "w

. REPORTABLE.0CCURRENCE 81-073 ISSUE 0 l Page 4 of 4 4

4 I

Prepared By: 1.tet k b v Cwen J, fjayton Q Technicar Services Technician Reviewed By: d Charles Fulle'r

Engineering-Supervisor s

Reviewed By: [</ [bd

.l Edwin D. Hill - (/ _'

Station Manager .

Approved By: , d 7V Dori Waremoourg #

j Manager, Nuclear Production I

F