CATEGORY1REGULAYINFORMATION DISTRIBUTIO YSTEM(RIDS),'1ACCESSION NBR:9712150403 DOC.DATE:

97/12/09NOTARIZED:

NODOCKETFACXL:50-.315 DonaldC.CookNuclearPowerPlant,Unit1,IndianaM0500031550-31bDonaldC.CookNuclearPowerPlant,Unit2,IndianaM05000316AUTH.NAMEAUTHORAFFILIATION FITZPATRICK,E.E IndianaMichiganPowerCo.RECIP.NAME RECIPIENT AFFILIATION"

SUBJECT:

NPDESnoncompliance notification:on 971108plantpersonnel chlorination syswasshutdown971108at9:00amduetovalvelineuperrormadeduringstartupofcontinuous chlorination aftershutdown.Continuuous chlorination resumed971108.DISTRIBUTXON CODE:IE23DCOPIESRECEIVED:LTR ENCLSIZE:TITLE:Environmental EventReport(perTechSpecs)NOTES:RECIPIENT IDCODE/NAME PD3-3PDCOPIESLTTRENCL11RECIPXENT IDCODE/NAME HICKMAN,J COPIESLTTRENCL11INTERN.FXLECNTER01RGN3EXTERNAL:

NOAC111111OGC/HDS2NRCPDR1111DUENNOTETOALL"RIDS"RECIPIENTS:

PLEASEHELPUSTOREDUCEWASTE.TOHAVEYOURNAMEORORGANIZATION REMOVEDFROMDISTRIBUTION LISTSORREDUCETHENUMBEROFCOPIESRECEIVEDBYYOUORYOURORGANIZATION, CONTACTTHEDOCUMENTCONTROLDESK(DCD)ONEXTENSION 415-2083TOTALNUMBEROFCOPIESREQUIRED:

LTTR7ENCL7 0~~

IndianaMichiganPowerCompany500CircleDriveBuchanan, Ml491071395~sINOMN/lNICMGANPQWKRDecember9,1997DocketNos:50-31550-316U.S.NuclearRegulatory Commission ATTN:DocumentControlDeskMailStop0-P1-17Washington, D.C.20555AEP:NRC:1208WGentlemen:

DonaldC.CookNuclearPlantUnits1and2CHLORINATED WATERDISCHARGE NPDESNOTIFICATION Theattachednotification's forwarded foryourinformation

'pursuant toCookNuclearPlant'sAppendixB(Environmental) technical specifications.

Thesubjectconcernstheinadvertent discharge ofchloiinated waterwithoutperforming requiredsamplingandanalysis, andtheactions'aken tomitigatethesituation.

Shouldyouhaveanyquestions orconcernsregarding thisnotification, pleasecontactJamesT.Weberat616/697-5075.

Sincerely, ZP~y~E.E.Fitzpatrick VicePresident

/vlbAttachment cc:A.A.BlindA.B.BeachMDEQ-DW&RPDNRCResidentInspector J.A.Abramson97i2l50403 97i209PDRADQCK05000M5S..PDR-QQQQ32llllllllllll IIllilIJI Iglllgg ATTACHMENT TOAEP:NRC:1208W NPDESNOTIFICATION AmericanElectricPorCookNuclearPlantOneCookPlaceBridgman, Ml491066164655901 ANKRICAMKLECTRlCPOMMERMr.Frederick MorleyPlainwell DistrictOffice,SWQDMichiganDepartment ofEnvironmental Quality1342M-89West,SuiteBPlainwell, Michigan49080November12,1997

Subject:

DonaldC.CookNuclearPlantNationalPollutant Discharge Elimination SystemPermitNo.MI0005827

DearMr.Morley:

Thisnotification ismadepursuanttoCookNuclearPlant'sNPDESPermitMI0005827, PartII,A.5.OnNovember8,1997,duringcontinuous chlorination oftheServiceWaterSystems,plantpersonnel inadvertently discharged aportionofchlorinated ServiceWatertoOutfall002forapproximately ninehourswithoutperforming therequiredsamplingandanalysisforTotalResidualOxidant.Thesesamplesweremissedduetoavalvelineuperrormadeduringthestartupofcontinuous chlorination afterashortshutdownforgeneralmaintenance ontheCirculating WaterSystem.Shortlyafterthelineupwascorrected, asamplewastakenfromtheOutfall002discharge samplepointat10:15a.m.onNovember8,1997.Thesamplemeasured0.07ppmTotalResidualOxidant(TRO),whichexceededthe0.036ppmmaximumdischarge limit.Thecondition wasdiscovered duringatourbyplantpersonnel atwhichpointthechlorination systemwasshutdownNovember8,1997at-09:00a.m.Shortlyafterthediscovery, thevalvewasrepositioned topreventdischarge fromOutfall002anddirectalltheServiceWatertotheOutfall001,wherecirculating waterdilutionispresent.Continuous chlorination resumedNovember8,1997at09:45a.m.Abriefingwasheldbytheplantpersonnel involvedwithchlorination toemphasize theimportance ofcheckingtheCirculating WaterSystemvalvelineuppriortocommencing chlorination asrequiredintheirprocedure.

Thechlorination procedure includesstepstoensurethatpropervalvelineupshavebeenperformed toavoidNPDESexceedences.

Mr.FredMorleyPage2November12,1997TheServiceWaterSystemflowshavebeencalculated tobeapproximately 24.MGDperunit.Thisisaslightportionofthenormalcirculating waterflowof1415MGDforOutfall002.Thisdischarge causednodetrimental effectstotheenvironment duetothesmalldischarge flowandthelargedischarge piping(18'iax0.5mileslong).Normalwatercolumndemandforchlorinewouldhavereducedtheconcentration to<.001ppmbythetimetheflowreachedLakeMichigan.

Pleasecontactmeat(616)465-5901, ext1153,withanyquestions youhave.Sincerely, JohnGarisonEnvironmental Compliance Supervisor

'r.FredMorleyPage3November12,1997IcertifyunderpenaltyoflawthatIhavepersonally examinedandamfamiliarwiththeinformation submitted onthisandallattacheddocuments; andbasedonmyinquiryofthoseindividuals immediately responsible forobtaining theinformation, Ibelievethesubmitted information istrue,accurateandcomplete.

Iamawarethattherearesignificant penalties forsubmitting falseinformation, including thepossibility offineandimprisonment.

J.R.SamponPlantManager