Text

ACCELERATED DISTRIBUTION DEMONS TION SYSTEM REGULATE .'NFORMATION DISTRIBUT10 SYSTEM (RIDS) r ACCESSION NBR:9206170006 DOC.DATE: 92/06/10 NOTARIZED: NO DOCKET FACIL:50-315 Donald C. Cook Nuclear Power Plant, Unit 1, Indiana M 05000315 50-316" Donald C. Cook Nuclear Power Plant, Unit 2, Indiana M 05000316 AUTH.AAME AUTHOR AFFILIATION BAKER,D.'L. Indiana Michigan Power Co. (formerly Indiana & Michigan Ele RECIP.NAME RECIPIENT AFFILIATION MORLEY;F. -

Michigan, State of R

SUBJECT:

NPDES noncompliance notification:on 920606,grab sample of Outfall 002 circulating water discharge indicated total I residual chlorine above timits.Caused by manfunctioning evc water flow meter. Flow meter will be replaced. D DISTRIBUTION CODE: C001D COPIES RECEIVED:LTR r ENCL d SIKE:

TITLE: Licensing Submittal: Environmental Rept Amdt & Related Correspondence NOTES:

/

RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL D PD3-1 LA PD3-1 PD STANGFJ D INTERNAL: NRR/DET/ESGB 8D OGC/HDS2 OC/LFMB REG -F.D " 0 RGN3 DRSS/RPB EXTERNAL EG&G SIMPSON F F NRC PDR NSIC D

D D

NOTE TO ALL "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASfEI CONTACT THE DOCUMENT CONTROL DESK, ROOM P 1-37 (EXT. 20079) TO ELIMINATEYOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED: LTTR 14 ENCL

)l Indiana Michigan~

Power Company One Summit Square P.O. 8ox 60

~

Fort Wayne, IN 46801 219 425 2111 INDMNA NICHIGAN Mr. Fred Morley, District Supervisor POWER Surface Water Quality Division Michigan Department of Natura3. Resources 621 North 10th Street P. 0 Box 355 Plainwell, MI 49080 June 10, 1992

Dear Mr. Morley:

RE: Cook Nuc3.ear Plant NPDES Permit No. MI 005827 This notification is provided pursuant to PART II, Section A.S. of NPDES Permit No. MI0005827. On June 6, 1992, at 1350 hours0.0156 days <br />0.375 hours <br />0.00223 weeks <br />5.13675e-4 months <br /> EDT, duping intermittent chlorination of the plant service water systems, a grab sample of Outfall 002, circulating water discharge was analyzed for total residual chlorine (TRC).

The analysis'ndicated a TRC concentration of 0.76 mg/l.

The sodium hypochlorite flow to the systems was immediately reduced. At 1404 hours0.0163 days <br />0.39 hours <br />0.00232 weeks <br />5.34222e-4 months <br />, a grab sample analysis indicated the concentration of, TRC had decreased to 0.22 mg/l. At 1414 hours0.0164 days <br />0.393 hours <br />0.00234 weeks <br />5.38027e-4 months <br />, the TRC concentration had decreased to 0.03 mg/l.

The daily maximum value for TRC during the time of chlorination was 0.18 mg/l.

'\

A malfunctioning non-essential service water flow meter has been identified as a contributing factor to the event. The flow meter is scheduled for replacement prior to resumption of chlorination activities on the non-essential service water systems.

By copy of this letter, the Nuclear Regulatory Commission is notified pursuant to thc requirements of Appendix B, Part II, Nonradiological, Environmental Protection Plan, Section 3~20 Very truly yours, Donald L. Baker Environmental Affairs Director DLB/sdb/022 c: MRC Document Contro3." i A. B. Davis NRC> Region III J. A. Isom NRR Resident Inspector jp t

920b17000b 920b10 PDR ADOCK 05000315, ~g .i )I El ki ~

',8,, , PDR

0 gh Q k

~ f' d N

June 10, 1992 Fred Morley, District Supervisor Page Two I certify under penalty of law that I have personally examined and am familiar with the information submitted on this and all attached documents; and based on my inquiry of those individuals immediately responsible for obtaining the information, I believe the submitted information is true, accurate and complete. I .am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment.