ML17325A981

From kanterella
Jump to navigation Jump to search
NPDES Noncompliance Notification:On 880919,water Makeup Prefilter Backwash Sample Exceeded Limitations.Caused by High Solids in Intake from Lake Michigan.Plant Personnel Reminded About Need to Evaluate & Rept Analyses Promptly
ML17325A981
Person / Time
Site: Cook  
Issue date: 10/05/1988
From: Menge R
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: Zugger P
MICHIGAN, STATE OF
References
NUDOCS 8810260395
Download: ML17325A981 (2)


Text

REGULAT

. r'NFORMATION DISTRIBUTION STEM (RIDS)

.ACCESSION NBR: 8810260395 DOC. DATE: 88/10/05 NOTARIZED:

NO DOCKET ¹ FACIL: 50-315 Donald C.

Cook Nuclear Poeer Plant'nit ii Indiana 8.

05000315 50-316 Donald C.

Cook Nuclear Poeer Planti Unit 2i Indiana 5

05000316 AUTH. NAME AUTHOR AFFILIATION MENGEi R. C.,

Indiana Michigan Power Co.

(formerly Indiana h Michigan Ele RECIP. NAME RECIPIENT AFFILIATION ZUGGER~ P. D.

Michigani State of

SUBJECT:

NPDES noncompliance notification: on 880919'ater makeup pref ilter backeash sample exceeded limitations.

DISTRIBUTION CODE:

IE23D COPIES RECEIVED: LTR ENCL SIZE:

TITLE: Environmental Event. Report (per Tech Specs)

NOTES:

RECIPIENT ID CODE/NAME PD3-1 LA" "

SCOTT. W INTERNAL: AEOD/DSP/TPAB NRR/DEST/*DE 8H NRR/DREP/EPB 10 NRR/PMAS/ ILRB12 RACT RE F

RGN2/DRSS/EPRPB EXTERNAL:

LPDR NSIC COPIES LTTR ENCL RECIPIENT ID CODE/NAME PD3-1 PD AEOD/PTB NRR/DOE*/EAB 11 NRR/DRFP/RPB 10 NRR/PMAS/PTSB12 OGC/HDS1 RGN3 FILE 01 NRC PDR COPIES LTTR ENCL TOTAL NUMBER OF COPIES REQUIRED:

LTTR 19 ENCL

Indiana Michigan Power Company One Summit Squ'.O.

Box 60 Fort Wayne. IM 46601 219 425 2111 PIIZOR?TY IIOUTXNG I

DP Paul D. Zugger, Executive Secretary Michigan Water Resources Commission Stevens T. Mason Building, Box 30026 Lansing, Michigan 48909 INDMNA NICHIGAN FII.

POWER October 5, 1988

Dear Mr. Zugger:

RE:

Donald C.

Cook Nuclear Plant NPDES Permit No. MI 0005827 Prefilter Backwash Limitations Richard C. Menge Senior Vice President 219 425 2103 A

sample taken on September 19, 1988 of the water makeup prefilter backwash (Outfall OOF) indicated a

suspended solids concentration (TSS) of 284 mg/l.

Also the average TSS for outfall OOF during September was 112 mg/1.

The operating log of the prefilter unit showed normal operation.

High solids in the intake from Lake Michigan appear to have caused the problem.

Rough lake conditions were noted at that time and have persisted to the present time.

There was an inadvertent delay in the plant's reporting procedure when the plant did not communicate the analytical test results to Environmental Affairs.

Plant personnel involved in this reporting procedure have been reminded about the need to evaluate and report analyses promptly.

By copy of this

letter, the Nuclear Regulatory Commission is notified pursuant to the requirements of Appendix B, Part II, Nonradiological Environmental Protection
Plan, Section 3.2.

Very truly yours, W~~ d.

Richard C. Menge Senior Vice President IAwU IAYiA OOQ.

OO wO COlA COO IAXC Cr U RD OA WcX O

COA COQ C0 RCM/df c:

Valdas Adamkus - USEPA, Region V

A. B. Davis'""NRC, Region III Fred Morley - MDNR, Plainwell CT i1 1888 I certify under penalty of law that I have personally examined and am familiar. with the information submitted on this and all attached documents; and based on my inquiry of those individuals immediately responsible for obtaining

'the information, I

believe the submitted information is

true, accurate and complete.

I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment.

Richard C. Menge