NPDES Noncompliance Notification:On 920624,grab Sample of Outfall 002 Circulating Water Discharge Indicated TRC Concentration of 0.33 mg/1.Caused by Flow Balance Between Plant Sys.Unit 1 in Shutdown Condition
ML17329A548
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 06/29/1992
From: Baker D
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: Morley F
MICHIGAN, STATE OF
References
NUDOCS 9207070236
Download: ML17329A548 (4)


Text

ACCELERATED DISTRIBUTION DEMONMlWTION SYSTEM REGULAT INFORMATION DISTRIBUTIO ZSTEM (RIDS)

ACCESSION NBR:9207070236 DOC.DATE: 92/06/29 NOTARIZED:

NO DOCKET ¹ FACIL:,59-315 Donald C.

Cook Nuclear Power Plant, Unit 1, Indiana M

05000315 5'5-316 Donald C.

Cook Nuclear Power Plant, Unit 2, Indiana M

05000316 AUTH.NAME AUTHOR AFFILIATION BAKER,D.L.

Indiana Michigan Power Co. (formerly Indiana

& Michigan Ele RECIP.NAME RECIPIENT AFFILIATION MORLEY,F.

Michigan, State of

SUBJECT:

NPDES noncompliance notification:on 920624,grab sample of Outfall 002 circulating water discharge indicated TRC concentration of 0.33 mg/1.Caused by flow balance between plant sys.Unit 1 in shutdown condition.

DISTRIBUTION CODE:

C001D COPIES RECEIVED:LTR ENCL SIZE:

TITLE: Licensing Submittal: Environmental Rept Amdt

& Related Correspondence

/

NOTES:

RECIPIENT ID CODE/NAME PD3-1 LA STANG,J INTERNAL: NRR/DET/ESGB 8D OGC/HDS2 RGN3 DRSS/RPB EXTERNAL: EG&G SIMPSONiF NSIC COPIES LTTR ENCL RECIPIENT ID CODE/NAME PD3-1 PD OC/LFMB LE NRC PDR COPIES LTTR ENCL D

D D

NOTE TO ALL"RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WAS'ONTACI'HEDOCUMENT CONTROL DESK, ROOM Pl-37 (EXT. 20079) TO ELIMINATEYOUR NAMEFROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

D D

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 14 ENCL

indiana Michigan Power Company One Summit Squar P.O. Box 60 Fort Wayne. IN 46801 219 425 2111 kW

~

INDIANA NICHIGAN POWER Mr. Fred Morley, District Supervisor Surface Water Quality Division Michigan Department of Natural Resources 621 North 10th Street P.

O.

Box 355 Plainwell, MI 49080 June 29, 1992

Dear Mr. Morley:

RE:

Cook Nuclear Plant NPDES Permit No. MI005827 On June 24, 1992, at 0905 EDT, during intermittent chlorination of the plant service water

systems, a

grab sample of Outfall 002, circulating water discharge was analyzed for total residual chlorine (TRC).

The analysis indicated a

TRC concentration of

0. 33 mg/1.

The sodium hypochlorite flow to the systems was immediately reduced.

At 0945 hours0.0109 days <br />0.263 hours <br />0.00156 weeks <br />3.595725e-4 months <br />, a grab sample analysis indicated the concentration of TRC had decreased to 0.15 mg/l.

The daily value for TRC during the time of chlorination was 0.19 mg/l.

The flow balance between plant systems has been identified as a contributing factor to the event.

Presently, Unit One is shutdown for a refueling

outage, while Unit Two is in the process of increasing power after refueling outage.

Chlorine demands may have fluctuated due to varying service water systems flow conditions.

By copy of this

letter, thc Nuclear Regulatory Commission is notified pursuant to the requirements.of.Appendix. B, Part II, Nonradiological, Environmental Protection
Plan, Section 3.2.

Very truly yours'~edCX Donald L. Baker Environmental Affairs Director DLB/sdb/051 c:

MRC Document Control A. B. Davis NRC, Region III J.

A. Isom NRR Resident Inspector l

920707023b 920b29 PDR ADDCK 050003i5 S,'

PDR y<P

June 29, 1992 Fred Morley, District Supervisor Page Two I certify under penalty of law. that I have personally examined and am familiar with the information submitted on this and all attached documents; and based on my inquiry of those individuals immediately responsible for obtaining the information, I

believe the submitted information is

true, accurate and complete.

I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment.

A-'mX~

Donald L. Baicer