ML20216H200: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot insert)
 
(StriderTol Bot change)
 
Line 2: Line 2:
| number = ML20216H200
| number = ML20216H200
| issue date = 06/24/1987
| issue date = 06/24/1987
| title = Responds to NRC 870528 Ltr Re Violation Noted in Insp Rept 50-353/87-04.Corrective Action:Presently Installed Relief Valves Inventoried & Added to Long Term Maint Program.Const Procedure Re Installation of Relief Valves Revised
| title = Responds to NRC Re Violation Noted in Insp Rept 50-353/87-04.Corrective Action:Presently Installed Relief Valves Inventoried & Added to Long Term Maint Program.Const Procedure Re Installation of Relief Valves Revised
| author name = Kowalski S
| author name = Kowalski S
| author affiliation = PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
| author affiliation = PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
Line 11: Line 11:
| contact person =  
| contact person =  
| document report number = NUDOCS 8707010350
| document report number = NUDOCS 8707010350
| title reference date = 05-28-1987
| document type = CORRESPONDENCE-LETTERS, INCOMING CORRESPONDENCE, UTILITY TO NRC
| document type = CORRESPONDENCE-LETTERS, INCOMING CORRESPONDENCE, UTILITY TO NRC
| page count = 2
| page count = 2

Latest revision as of 06:22, 21 March 2021

Responds to NRC Re Violation Noted in Insp Rept 50-353/87-04.Corrective Action:Presently Installed Relief Valves Inventoried & Added to Long Term Maint Program.Const Procedure Re Installation of Relief Valves Revised
ML20216H200
Person / Time
Site: Limerick Constellation icon.png
Issue date: 06/24/1987
From: Kowalski S
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
NUDOCS 8707010350
Download: ML20216H200 (2)


Text

. _ _

s . , -

'PHILADELPHI A' ELECTRIC COM PANY 2301 MARKET STREET 2876097250 li P.O. BOX 8699 PHILADELPHI A PA.19101

,,,,,,,e,x,.

mm aw= WN 24 BW VICE PRESIDENT spesinsa none ano assmanen -

United States Nuclear Regulatory Commission Attn: Document Control Desk l Washington, DC 20555

Subject:

USNRC Region 1 Letter Dated May 28, 1987 Re: Site Inspection of March 30 to May 10, 1987 Inspection Report No. 50-353/87-04

-Limerick Generating Station, Unit 2 1

File: QUAL 1-2-2 (353/87-04)

Gentlemen:

In response to the subject letter regarding the item identified during the subject inspection of construction activities authorized by NRC License No. 4 CPPR-107 we' transmit herewith the following:

i Attachment I - Response to Appendix A Should you have any questions concerning this item, we would be pleased (

~l to discuss them with you.

Sincerely, l

p j.

JMC/ pc ' l 1

Attachment .

Copy to: United States Nuclear Regulatory Commission Of fice of Inspection & Enforcement, Region 1 l 631 Park Avenue King of Prussia, PA 19406 R. Gramm, USNRC Resident Inspector 8707010350 DR 870624 ADOCK 05000353 PDR flI J

I

. . . ^

'T i I

r  !

Attachment I Response to Appendix A - Item A 2876097250 i L

i 4

Violation 10 CFR 50, Appendix B Criterion XIII and the Limerick Preliminary Safety Analysis Report Appendix D.4.9.1 require that measures be j established to prevent degradation of the quality of equipment below that required by the applicable equipment specifications.

Further, it is required that written instructions be prepared to ,

govern'the preservation of equipment prior to and after  !

installation. i Contrary to the above, on March 30, 1987, no written procedure existed to provide requirements for relief valve protection. The lack of adequate protection resulted in a breiten lockwire on the I blowdown adjustment ring access plugs on relief valve PSV '

2F055A.

Response

Relief valve PSV-51-2F0055A with the broken seal wire has been identified on a nonconformance report for re-verification of its setting. The recheck of settings will be accomplished in accordance with project procedures. The presently installed relief valves are being inventoried, protected as necessary and added to the Long Term Maintenance (LTM) Program.

To prevent recurrences of broken seal wires, the construction  !

procedure regarding installation of relief valves has been revised to require protection to be provided as part of the installation process. Also, the LTM procedure has been revised  ;

to include the relief valves, as they are installed.

1l I

JMC/pc I 1/1 6/22/87 353/87-04