ML20236F345 | 29 June 1998 | NPDES Noncompliance Notification:On 980615,sample Was Taken & Result Reported That Fecal Coliform Result Was 900 MPN/100 Ml.Result Exceeded Daily Max Limitations.Effluent Was Sampled Again on 980622 & Results Are Expected on 980701 | |
ML20112K016 | 18 June 1996 | NPDES Noncompliance Notification:On 960520,BOD5 Results of Sample Taken from Sewage Treatment Plant Effluent Exceeded Daily Max Limitation.Cause of Event Investigated & Unknown. Plant Operations During Period Not Changed | |
ML20078F548 | 30 January 1995 | NPDES Noncompliance Rept Notification:On 950111,approx 2,500 Gallons of Suspected Low Concentration Propylene Glycol Solution Discharged to Site Outfall 002 | |
ML20072S375 | 25 July 1994 | NPDES Noncompliance Notification:On 940720,plant Intake Embayment Instrumentation Probe Found to Be Not Working. Caused by Saltwater Leakage & Subsequent Damage to Measuring Probe Internals.Equipment Replaced on 940722 | |
ML20072S344 | 12 July 1994 | NPDES Noncompliance Notification:On 940706,salinity Meter Found Out of Svc During Surveillance of Effluent Monitoring for Intake Embayment.Caused by Water Leak.Current Monitoring Equipment Being Replaced | |
ML20072S360 | 7 June 1994 | NPDES Noncompliance Notification:On 940601,plant Intake Embayment Instrumentation Oxygen Probe & Data Recorder Found Not to Be Working.Caused by Corroded Internal Connectors & Replacement Tape Cassette Failure,Respectively | |
ML20064G431 | 3 March 1994 | NPDES Noncompliance Notification:On 940225,grease & Oil Analysis at 08:00 Was 39.1 Mg/L.Caused by Pavement Runoff Due to Intense Rainfall.Resampling Results Were 0.3 Mg/L | |
ML20063B823 | 7 January 1994 | NPDES Noncompliance Notification:On 940104,plant Intake Embayment Dissolved Oxygen Instrumentation Found Damaged. Caused by Failed Oxygen Probe.Probe Repaired | |
ML20058F241 | 2 December 1993 | NPDES Noncompliance Notification:On 931021,trailer That Houses Continuous Monitoring Equipment Removed,Resulting in Failure to Perform Continuous Monitoring of Intake Water. Continuous Monitoring Equipment Returned to Svc on 931117 | |
ML20101S930 | 14 July 1992 | NPDES Noncompliance Notification:On 920608,sample Analysis for Fecal Coliform Indicated Concentration of 900 MPN/100 Mi Greater than Max NPDES Limit of 400 MPN/100 Mi.Cause Not Determined.Concentration of Chlorine Increased | |
ML20091L030 | 23 December 1991 | NPDES Noncompliance Notification:On 911216,sample Analysis of Fecal Coliform Indicated Concentration Greater than 1600 mpn/100 Ml Sample,Exceeding Limit.Caused by Sodium Hypochlorite Pump Problems.Chlorine Concentration Increased | |
ML20091L034 | 13 December 1991 | NPDES Noncompliance Notification:On 911209,fecal Coliform Analysis Indicated Concentration Greater than 1600 mpn/100 Ml,Exceeding Limit.Caused by Improper Residual Chlorine Analysis.Test Kit Comparator Replaced | |
ML20091L051 | 30 October 1991 | NPDES Noncompliance Notification:On 911022,during Electrical Outage No Residual Chlorine Could Be Identified in Routine Weekly Sample.Fecal Coliform Analysis Yielded Concentration Greater That Daily Max Limit.Faulty Breaker Opened Manually | |
ML20091L061 | 10 January 1990 | NPDES Noncompliance Notification:On 891218,auxiliary Boiler Blew Down Releasing Approx 6,000 Gallons Auxiliary Boiler Water Into Chesapeake Bay.Monthly Average of 30 Mg/Liter Was Exceeded | |
ML20091L085 | 19 April 1989 | NPDES Noncompliance Notification:On 890412,electrical Control Relay Did Not Energize Which Controls Operation of Wet Well Pumps Via Air Compressor & Pressure Bubbler Sys. Engineering Dept Designing Back Up Control Sys | |
ML20247G425 | 16 March 1989 | NPDES Noncompliance Notification:On 890223,large Number of Fish Impinged Affecting Two Traveling Screens & Requiring Shutdown of Circulating Water Pumps.No Fish Kills Observed. Caused by Winds Blowing Toward Intake Area | |
ML20091L072 | 16 March 1989 | NPDES Noncompliance Notification:On 890313,during Cleanup of Overflowing Floor Drains Due to Main Drain Header Being Clogged,Cleaners Dumped Buckets of Waste Water Outside Storm Drain.Caused by Lack of Awareness of NPDES Requirements | |
ML20091L102 | 8 March 1988 | NPDES Noncompliance Notification:On 880307,temp Increase Across Condensers Was Experienced for Outfall 001.Caused by Mechanical Failure Causing Shut Down of Circulating Water Pump.Incident Regarded as Uncontrollable.No Action Taken | |
ML20091L111 | 21 October 1987 | NPDES Noncompliance Notification:On 871011,increase in Temp to 12.1 F Was Reached on Condensers.On 871012,increase in Temp to 12.3 Was Reached on Condensers.Caused by Reduced Flow of Cooling Water Through Condensers | |
ML20129E689 | 22 April 1985 | Nonroutine Radiological Environ Operating Rept.During Mar 1985,oyster Samples Showed Presence of Ag-110m.Caused by Natural Tendency of Oysters to Concentrate Environ Silver | |
ML20107F963 | 28 September 1984 | NPDES Noncompliance Notification:On 840828,reactor & Turbine Manually Tripped Due to Max Influx of Fish Blanketing Screen.Caused by Severe Anoxic Conditions.Biofouling Task Force Working to Improve Screen Performance | Biofouling |
ML20091L131 | 28 June 1984 | NPDES Noncompliance Notification:On 840620,Outfall 101 Sanitary Waste Experienced Noncompliance Re five-day Biochemical Oxygen Demand.On 840625,sample Indicating Level of 57.7 mg/1 Was Read,Exceeding Daily Max of 45 mg/1 | |
ML20091L142 | 24 April 1984 | NPDES Noncompliance Notification:On 840130 & 31,effluent Ph Analysis from Outfall 101 (Sewage Treatment Plant) Showed Values Below NPDES of 6 for 48 H.Lime Additions Were Made to Increase Ph.Emphasized Proper Disposal of Liquid Wastes | |
ML20087P610 | 2 April 1984 | Forwards NPDES Noncompliance Notification:On 840329,violent Storm Caused Grass & Other Debris to Be Swept by Waves & High Winds Into Water Boxes,Restricting Flow of Cooling Water & Increasing Temp.Debris Cleared & Temp Decreased | High winds |
ML20081D367 | 30 September 1983 | NPDES Noncompliance Notification:On 830919,reactor & Turbine Manually Tripped Due to Fish Kill in Intake Embayment Which Clogged Travelling Screens.Caused by Upwelling of Low Dissolved Oxygen Waters.Task Force Established | |
ML20091L147 | 22 June 1983 | NPDES Noncompliance Notification:On 830621,Monitoring Point 101 Experienced Total Residual Chlorine of 2 Ppm.Pump Was Vented & Returned to Svc.Due to Infrequent & Unpredictability of Event,No Action Deemed Necessary | |
ML20076J042 | 24 May 1983 | NPDES Noncompliance Notification:On 830520,during Receipt of Load of Bulk Aqueous Ammonia,Storage Tank Overflowed & 50-100 Gallons of Ammonia Solution Entered Outfall 002. Caused by Improper Attention During Chemical Transfer | |
ML20073H440 | 29 March 1983 | NPDES Noncompliance Notification:On 830325,temp Limit for Condensers Exceeded for Two Consecutive Hours.Low Tide & Severe Wave Action Due to High Winds Sweeping Debris Into Water Boxes.Debris Removed | High winds |
ML20073H477 | 29 March 1983 | Corrected NPDES Noncompliance Notification:On 821203,weekly Coliform Analysis from Monitoring Point 101 of Outfall 001 Showed Concentration Greater than 1,609 mpn/100 Ml.On 821212,effluent Chlorine Analysis Not Performed | |
ML20079N429 | 15 February 1983 | NPDES Noncompliance Notification:On 830211,temp Increased Across Condensers for Outfall 001.Caused by Restricted Cooling Water Flow Due to Greases & Other Debris Broken Loose by Severe Weather.Debris Removed | |
ML20091L153 | 9 February 1983 | NPDES Noncompliance Notification:On 830126,results Indicated Coliform Concentrations to Be 109 MPN/100 Ml,Exceeding Limit of 70 MPN/100 Ml.On 830201,suspended Solids Limitations Had Value of 46.6 Mg/L.Raw Sewage Pumps Were Left on Manual | |
ML20091L158 | 24 January 1983 | NPDES Noncompliance Notification:On 830112,Outfall 101, Monitoring Point 101 Experienced Total Residual Chlorine of 3 Ppm.Caused by Failure of Pump Used to Add Dechlorinating Agent.Spare Pumps on Site Allowed Rapid Corrective Action | |
ML20070Q514 | 11 January 1983 | NPDES Noncompliance Notifications:Over Two 12 H Periods,Ph Values Over Specs While Releasing 45,000 Gallons Max.On 821203,coliform Analysis Revealed Concentration Above Spec. on 821212,chlorine Analysis Not Performed | Grab sample |
ML20091L170 | 22 November 1982 | NPDES Noncompliance Notification:On 821015,component Yeilded Oil & Grease & Suspended Solids Higher than Permit Restrictions.Incident Possibly Caused by Auxiliary Bldg Drain Problem.Temporary Analysis Program Implemented | |
ML20091L176 | 15 September 1982 | NPDES Noncompliance Notification:On 820831-0901,approx 6,800 Gallons of 5.9 Ph Water Was Discharged Via Outfall 104 to Chesapeake Bay.Caused by Improper Valve Closure on Inlet of Discharge Tank.Preventive Maint Schedule Implemented | |
ML20091L188 | 21 July 1982 | NPDES Noncompliance Notification:On 820602,weekly Coliform Analysis from Outfall 101 Revealed Concentration of 79 Mpn/ 100 Ml.Apparent Cause Unknown & Because of Above Suggested Scenario,Cannot Be Ascertained.Operator Reinstructed | |
ML20091L211 | 25 February 1982 | NPDES Noncompliance Notification:On 820106,backup Sample Confirmed Ph of 9.1.Caused by High Ammonia Concentration in Yard Oil Interceptor.No Direct Cause Could Be Found. Investigation Continuing | |
ML20091L196 | 25 February 1982 | NPDES Noncompliance Notification:On 820219 Coliform Results from 820217 Sample Found to Be 160 mpn/100 Ml.Caused by Contaminated Sodium Thiosulfate Chemical Addition Tank. Condition Corrected | |
ML20091L218 | 28 August 1981 | NPDES Noncompliance Notification:On 810810,operator Discovered Leakage Past Drain Valve for 12 Waste Neutralization Tank (Wnt).Caused by Damaged Seat of Wnt Drain Valve.Valve Replaced | |
ML20091L221 | 24 July 1981 | NPDES Noncompliance Notification:On 810605,weekly Coliform Analysis Showed Concentration Greater than 1609 mpn/100 Ml. Caused by Contaminated Sodium Thiosulfate Containers Used for Dechlorination.Housekeeping Frequency Increased | |
ML20091L228 | 24 July 1981 | NPDES Noncompliance Notification:During Month of June,No Radioactive Releases Were Accomplished Through Outfall 105B, Miscellaneous Waste Monitor Tank | |
ML20091L229 | 8 July 1981 | NPDES Noncompliance Notification:On 810702,influent Sump to Site Sewage Treatment Plant Overflowed,Dumping Raw Sewage to Storm Drain.Caused by Removal of One Lift Pump from Svc. Proper Care Will Be Exercised When Performing Maint | |
ML20091L251 | 12 May 1981 | NPDES Noncompliance Notification:On 810423,outside Operator Discovered Drain Valve for 12 Waste Neutralizing Tank (Wnt) Open.Caused by Operator Failure to Follow Procedures. Operators Involved Received Appropriate Disciplinary Action | |
ML20091L264 | 9 March 1981 | NPDES Noncompliance Notification:On 810206,10,13 & 28, Coliform Readings Were 278 mpn/100 ml,918 mpn/100 ml,1609 mpn/100 Ml & 542 mpn/100 Ml,Respectively.Caused by High Flow Experienced by Sewage Treatment Plant | |
ML20091L277 | 24 February 1981 | NPDES Noncompliance Notification:On 810228,effluent Sample Contained 75.9 Mg/L Suspended Solids.On 810110,13 & 28, Coliform Readings Were 1609 mpn/100 ml,1180 mpn/100 Ml & 1609 mpn/100 Ml,Respectively | |
ML20091L287 | 4 February 1981 | NPDES Noncompliance Notification:On 811012,free Available Chlorine Determined to Be .7 mg/1.On 811121,recorded Reading of 1.5 Mg/L Free Available Chlorine.On 811029,determined Coliform Reading of 345 MPN/100 Ml | |
ML20091L293 | 2 February 1981 | NPDES Noncompliance Notification:On 801029,results from Sample Drawn for Routine Weekly Coliform Analysis Indicated Concentration of 345 mpn/100 Ml.Caused by High Flow to Plant Soon After Start of Refueling Outage | |
ML20091L300 | 8 December 1980 | NPDES Noncompliance Notification:On 801202,sample Drawn for Routine Weekly Coliform Analysis Indicated (on 801204) Concentration of Greater than 2,000 mpn/100 Ml.Caused by Unusually High Flow to Plant.Chlorine Tank Was Drained |