y'AG

~

B ALTIMORE G AS /sND ELECTRIC COMP ANY P.O BOX 14 7 5 D A LTIM O R C. M A R Y L A N D 212 o 3 HUCLE AR POWLR DEPARTMENT CALVERT CLIF F $ NUCL E A R PonER PL ANT LV59Y. MARYLAND 20657 July 2h, 1981 State of Mary 1.tnd Office of Environmental Programs Waste Management and Enforcement Program Taves State Office Building Annapolis, Maryland 21h01 Attention:

Mr. Raymond E. Riggin Be: Maryland State Discharce Permit No. Th-DP-0187 A (I.'PDES No. PD 0002399)

Dear Mr. Riggin:

On June 5,1981, veekly colifom an'slysis showed a concentration of

>1609 mpn/100 ml.

This result is above the 70 rpn/100 ml pemitted by the reference permit. The cause has been determined to be conted-nation in the sodium thioculfate containers used for dechlorination.

A coliform test was perfom,:d on the sodium thiosulfate containers a.i the results indicated high colifom concentrations; the containers er.i hoses were cleaned, chlorinated and refilled for service.

To correct this situation, housekeeping frequency has been increased.

On June 2h,1981, weekly colifom analysis showed a concentration of 228 mpn/100 m1, again above the allowable limit.

An inspection of the system showed solida carryover into the chlorinc contact tank. n.e

- chlorine contact tank was drained and cleaned.

To correct this situa-i or..

the chlorine contact tank vill be inspected for possib1c contaninatic.

whenever normal effluent surveillance is performed.

Cincerely yours, 114 L. B. Russe]l Plant Superintendent JES/feb (q

Jn T L. 6 (?.

f JJ5 920127 M21 920116 PDR ADOCK 05000317 S

PDR