, - _ _ _ _ _ _ _

e

  1. 9 4

i l

BALTIMORE G AS AND ELECTRIC COMPANY P.O. D O X 14 7 5 B ALTIMOR E. M AR YL AN D 212o3 1

HUCLEAR POWER DEPARTMENT C ALVENT CLIF PS NUCL L AR POWER PL ANT LulpV, MARYLAND 20$$1 Februsry 25, 1982 Division of Severage Inspection and Compliance Program Office of Environmental Programs, Room 2Ab 201 West Preston Street Baltimore, Maryland 21201 Attention: Mr. Ronald Parise Re: Maryland State Discharge Permit No. Th-TP-0187A and NFDES Permit No. MD 0002399

Dear Mr. Parice:

At 10A0 hours on February 19, 1982, the coliform results from the Wednesday, Febtsary IT,1982, sample were analyzed and found to be 160 cpn/100 ni, above the compliance limit of 70 upn/100 ml.

This condition existed until 1515 hours0.0175 days <br />0.421 hours <br />0.0025 weeks <br />5.764575e-4 months <br /> on Monday February 22, 1982, when the coliform was found to be kh apn/100 m1.

A report of this incident was verba13y transmitted to your office on February 19, 1982.

The noncompliance resulted from a contaminated sodium thiosulfate chemical addition tank. This condition has been corrected.

- Very truly yours, M

L. B. Russell Plant Superintendent LBR/RES/feb 9201270309 920116 PDR ADOCK 05000317

.S PDR b....

.