Text
- y.
~
B ALTIMORE G AS AND ELECTRIC COMP ANY P.O. BOX 1476 B ALTIMOR E M A R Y L A N D 212 0?
NUcLt AR FowtR htPARTMENT tALythT C Lir s t nGCL ri.a poe t h PL at!t ib'88t. MAPTLAND I;ll?
June 28, 1984 Office of Environmental Programs Wauti Management Administration 201 West Preston Street Baltitiote, Maryland 21201.
Attention: Mr. Barry Schmidt Ret Marfland State 01 harge Formit ho 79-LP-487 had NPDES Nimit No. MD.
0002399
- i "cht Mr. Schmidt:
' On June 20, 1984 outfall 101 sanitary vaste, expurienced u aon-compliance with respect to the five-day biochemical oxygen demand.
Dr.' June.!.)
'984 the semple was read indicating a level of; 37 7, mg/1, 01ch exceeds av.
daily mar,imum of 45 mg/1. The plant influent BOD vaa ;i9 mg/l vnich.ii three tir"rjour normal.
Air to the aeration tank was increased to raise thrt dissolved oxypynLlevel, and the polymer injection was increased to imorovn'tl.t clarity of the settling tanks.
This non-compliance was reported via telephor.a n your office June 25, 1984.
Should you have any questiens regardiv.g this inforr.ation, p'c 'se feel f ree to call.
Very truly yours,
%f L..B-Russell Plant Superintendent LBR/ bad i