,, - - - - _ _ _ - _ _. - - - - _ _ -

  • ",h.

~g n

/,

g i

I o., _ 1 ;-

l lI,k I.'I' ; M C,14 ti (3,\\ 13,\\ N ti - K i. E C T 41 C t '. O I,1 i 2,*', i 1 Y t

l' o, 0 0 % 111s OAl.fif40 HC, M A l t L, A N D 2'203

{

NptiS e.k r o mf R MPA RTwitif c s '. 71. m T c L a r t & '.U CL E A U Po n E m Pt. A 4 *e*

.,r tute,wAtert. Awe 706 U Dert,nber 8, 1930 s

i

'i

- St at e af N ryland Of f ice of Environraent al Progr mc Waste P nancNnt and Enf ort:e wie nt Program i

Tases State Of fice Building Annapoll s, Maryland 21'401 Attentiont

'f r ; P, Wiggtatun Concieu n:

On U-2-80 a suple was drawn f or the routine weekly coli f orm a nalye,is On IM40 the result s f rcm this test indicated a concentration of M Dei n.p'r/100 el.

This is a viciation of section 1.c. of the if aryland l

St a te Discha rge pertai t. #74-DP-0187A f or Calver t Cliffs Nuclear Power P 's a n '.. Notification of this occurrence was trade t y plant personnel to Mr. P. Viggint on a s per sect ion 11.B.2 of the, pe rmit.

This is the required written report.

d The event wat believed to be caused by n unusually high flow to the

' plant. This flow surge substantially inct'ased the flow in the chlorine 4

contact tank, which, in turn, reduced the t.me from chlorination to dechlorinatien.

This contact time was too shot

  • to provide effective

- di sinfec t ion.

To correct thic situation, the chloriae contact tank vas-drained and cleaned and the ch'

'_ne concentration increased.

The flow path from the wet well into the plant was adjusted to allow the sarges to be absorbed to prevent recurrence.

Additionally, plant p e; tonnel are investigating the possibility of inc reasi ng the surge cenacity as a facility change.

Very truly yours, g