On October 29, 1980 a semple vas diavn for the routine weekly colifom anal.y si s.
The results from this tect indicated a concentration of 3h? mpn/100 ml.
Pem.t requirement to 70 mpn/100 m1 maximum. This is
'~a, violation of section..e of the Maryland State Discharse Pemit No.- TSDP-016TA for Calvert Cliffs Nuclear Power Plant.
Q.) eveut'vaa telieved to be caused by an unusually hi;h flow-to the t
plent socn seter the'sttitt of a refueling outage at-the plant.
This surge substantially increasel the f.'ov in.the chlorine contact tank, which, in turn, reduced lthe chlori-
- ontact time.. This contact time y
vas' too short to provide. effectivt sinfection.
it To correct 'this situation, the chlorine concentration was increased in the contact tank. N flow path from the vet vell into the plant was adjus+ed to allev the - uurges-to be absorbed to prevent recurrence.
Very truly yours >
L. B. Russell Plant Superintendent l
' JR S:GE3: Tcb lt A