. _ _ _ - _ _ _ _ _ _ __

I*ETER E. KATZ Baltimore Gas and Electric Company Plant General Manager Calvert Cliffs Nuclear Power Plant Calvert Cliffs Nuclear Power Plant 1650 Calvert Cliffs Parkway Lusby, Maryland 20657 410 495-4101 A

June 18,1996 U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

Document Control Desk l

SUBJECT:

Calvert Cliffs Nuclear Power Plant Unit Nos. ! & 2: Docket Nos. 50-317 & 50-318 Violation of NPDES Permit No. MD0002399 In accordance with Section 3.2 of Appendix B, " Environmental Protection Plan (Non-Radiological)

Technical Specifications," Attachment (1) is provided reporting a recent violation of the National Pollution Discharge Elimination System Permit for the Calvert Cliffs Nuclear Power Plant.

Should you have questions regarding this matter, we will be pleased to discuss them with you.

Very truly yours,

.A A PEK/RCG/bjd Attachment cc:

D. A. Brune, Esquire T. T. Martin, NRC J. E. Silberg, Esquire Resident inspector, NRC Director, Project Directorate I-1, NRC R. I. McLean, DNR A. W. Dromerick, NRC J. II. Walter, PSC 9606210182 960618 PDR ADOCK 05000317 S

PDR 310004

(

f.

PETER E. KATz Baltimore Gas and Electric Company Plant General Manager Calven Cliffs Nuclear Power Plant Calvert Cliffs Nuclear Power Plant 1650 Calvert Cliffs Parkway Lusby, Maryland 20657 410 495 4 101 June 6,1996 i

Jack Bowen Maryland Department of the Environment inspection and Compliance Program 2500 Broening Highway Baltimore, Maryland 21224

Dear Mr. Bowen:

RE: NPDES Permit Special Conditions A.3 Noncompliance May 20,1996 NPDES Discharoe Permit MD0002399A. State Permit 92-DP-0187A On Ma[20,1996 at 8:00 AM, a sample was taken from the Sewage Treatment Plant effluent to perform the weekly analysis as required by the Calvert Cliffs Nuclear Power Plant Site NPDES Permit. On June 5,1996 at 10:15 AM the laboratory reported that the BOD result was 65 mg/l, this exceeds the Daily 3

Maximum Limitation of 45 mg/l. No impact upon receiving water was observed as a result of this event.

All other analysis results were well within limits.

The duration of this noncompliance is not known but could not have been longer than 8 days. A weekly sample was pulled on May 28,1996 and the analysis result reported on June 5,1996 at 10:15 AM was 5 mg/l. Wlth the additional samples taken during May the Monthly Average Effluent Limit was not exceeded.

The cadse of this event was investigated and is unknown. Plant operations were not changed during this period, and all other analysis results were normal.

If you have any questions regarding this information, please contact Brenda D. Nuse at (410) 495-4913.

Sincerel,

PEK/BDN 4

(

cc:

W. W. Baines til L. Shultz J.F. Stine