a S ALTIMORE G AS AND ELECTRIC COMPANY P. O. B O X 1475 B A LTIMOR E.

M A R YL AN D 212o3 NUCLE AR POWER DEPARTMENT CALVERT CLIFFS NUCLEA R PO*ER PLANT LUSEY, M A RYLAND 20657 February 15, 1983 Office of Environmental Programs Waste Management Administration 201 West Preston Street Baltimore, Maryland 21201 Attention:

Mr. Ronald Parise Re: Maryland State Discharge Permit No. 74-DP-0187 and NPDES Permit No. MD 0002399

Dear Mr. Parise:

A non-compliance with respect to temperature increase across the condensers of Unit 2 was experienced for outfall 001 on February 11,19S3.

The 12*FoT limitation was exceeded for about one hour, reaching a recorded high of 13.1*F.

Immediately power was reduced and eventually lowered to 40*6 to allow water boxes to be cleaned.

The cause of the problem was that grasses and other debris, broken loose by the severe wave action, had restricted cooling water flow.

Once this matter was removed, the temperature change returned to within the allowed range.

This is regarded as an uncontrollable, weather-related anomaly, and no other corrective action is planned.

Should you have questions regarding this information, please feel free to call.

Very truly yours, l

i l

L. B. Russell Plant Superintendent LBR/EME/fcb cc:

U. S. Nuclear Regulatory Commission l

8303030681 830215 PDR ADOCK 05000318 S

PDR