Rev 0 to Alternative Safe Shutdown Procedure ASSD-27, Diesel Generator Bldg 1 Ft Elevation Diesel Generator 3 4 Day Storage Tank Room
ML20205S621
Person / Time
Site: Brunswick  Duke Energy icon.png
Issue date: 04/04/1988
From: Bishop E
CAROLINA POWER & LIGHT CO.
To:
Shared Package
ML20205K904 List: ... further results
References
ASSD-27, NUDOCS 8811110118
Download: ML20205S621 (12)


Text

__. _ _ _ _ _ _

fM F CAROLINA POWER & LIGHT COMPANY BRUNSWICK STEAM ELECTRIC PLANT UNIT 1 PROCEDURE TYPE: ALTERNATIVE SAFE SHUTDOWN PROCEDURE NUMBER: ASS 0-27 PROCEDURE TITLE: DIESEL GENERATOR BUIL0ltG l' ELEVATION R 8.1 OlESEL GENERATOR NO. 3 FOUR DAY STORAGE TANK ROOM Rev. O l 4/4/88 forgo}f,fgg we \#2f(,$,5p***"

ggit it D"31,,e '# he e;et.s v ,g,;#t iNE ,eteve 91 As U i Approved Oy: N A f Date: 4!/0 TS/

GeneraTTnager anager'-ype rations / (

(

BSEP-1/AS50-27 Page 1 o' 12 Rev, 0 89111'0110 001025 PDR ADOCK 05000324 P PDR i ,

LIST OF EFFECTIVE PAGES ASS _D-27 P_a3 M Revision, 1-12 0 K B.L l

i BSEP-1/ ASS 0-27 Page 2 of 12 Rev. 0 l

{

l

r I

A. lillE_

Diesel Generator Building l' Elevation Diesel Generator No. 3 Four Day Storage Tank Room B. REFERENCES ,

1. Per 10CFRSO Appendix "R" Sections !!!.G & L.
2. Per 10CFR50 Appendix "R" Section !!!.J.

C. ENTRY CONDITION This procedure is entered from Alternative Safe Shutdown Index ASSD-01,

1. A fire has occurred in an area containing Alternative Safe ,

Shutdown Train A equipment,  !

.A_N,0,

2. The Shift Foreman has determined that the reactor is to be brought to Cold Shutdown using Alternative Safe Shutdown i Train B.  ;

The purpose of this procedure is to provide supplemental actions to be.- ,

used concurrently with E0Ps and other operations procedures to achieve and R8.1 maintain Cold shutdown coincident with or without a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> loss of off-site power.

D. OPERATOR ACTIONS  ;

1. IF while executing this procedure, the fire is extingui Ehed AND tWe Shift Foreman determines that no action within this' ,

procedure is required, THEN EXIT this procedure, ,

2. OBSERVE the following parameters on instruments indicated while i performing actioris to achieve and maintain cold shutdown.

I nstrument Location 1-CAC-TR-778 Suppression Pool Water Temp. (Pt. 7) Remote Shutdrwn Panel [

1-CAC-L1-3342 Torus Level Remote Shutdown Panel i 1-C32-PI-3332 Reactor Pressure Remote Shutdown Panel 1-821-LI-R6i'4BX Reactor Water Level Remote Shutdown Panel i

3. E reactor building entry is required to restore O_R, monitor i equipment, THEN  :  ;
a. DISPATCH the following minimum manpower for performance of this procedure:

! i Reactor Building ' Auxiliary Operators

(.

BSEP-1/ASSD-27 Page 3 of 12 Rev. O

% _b. OBTAIN the following keys from the Shift Foreman's Key Locker (1) ASSD Eouipment Cabinet Key #148 (1) ASSD Flashlight Tool Box Key #150

~~ -

c. OBTAIN Security Access Keys from SAS Security Officer located in the Control Room AND PROCURE the following equipment from the ASSD Equipment Cabinet.

For Reactor _ Building _

(2) Flashlights

2) Sound powered phones 7 ((2) Twenty-five foot sound powered phone extension cerds (2) Copies of this procedure (4) Remote Shutdown Key:, Serial T112 (2) Security Access Keys
d. USE appropriate figures in this procedure to provide access / egress routes, equipment and communication locations. g g,l
4. _P_ LACE Reactor Water Level "NORMAL / LOCAL" switch,1-821-CS-3345 at the Remote Shutdown Panel, to the "LOCAL" position to make level indicator 1-B21-LI-R604BX operabic.
5. IF RBCCW Heat Exchangers Service Water inled Yalve,1-SW-V106 UNNOT be operated from the RTGB, THEN Manu(lly OPERATE TTQW106.

l 6. IF Vital Header Cross-tie Valve,1-SW-V11B CANNOT be operated l TFom the RTGB, THEN Manually OPERATE 1-SW-VT18,

7. IF operation of RHR Service Water System is required AND RHR Tervice Water Booster Pumps are NOT_ available, THEN itTFTR to OP-43.

r

8. IF operation of RCIC Steam Supply Inboard Isolation Valve.

T E51-F007 is required AND power is NOT available frc.n MCC IXC, 1 HEN

a. PLACE the circuit breaker control switch in the OFF position for Rr,1C Steam Supply Inboard Isolation Valve,1-E51-F007, at MCC IXC comp rtment 054.

s.'

BSEP-1/ ASS 0-27 Page 4 of 12 Rev. O

~

b. PLACE the circuit breaker control switch in the ON

' position for RCIC Steam Supply line Isolation VaTve, 1-E51-F007, (ASSD FEED) at.MCC 1XD compartment DY1.

c. IF 1-E51-F007 is required to be Open. THEN PLACE the ESD Keylock Control Switch in the OPEN' position, at MCC 1XD compartment DY1. l i
d. IF 1-E51-F007 is required to be Clusmi, WN PLACE the g MSD Keylock Control Switch in the CLDSE" phstiton, at MCC IXD compartment DY1.
9. IF operation of RCIC Turbine Exhaust Vacuum Breaker Valve, i T~E51-F062 is required AND_ power is NOT available from MCC IXA,  :'

THEN

a. PLACE the circuit breaker control switch in the OFF i position for RCIC Turbine Exhaust Vacuum Breaker Valve,1-E51-F062, at MCC 1XA compartment DE4  :
b. PLACE the circuit breaker control switch in the ON  !

position for RCIC Turbine Vacuum Breaker Valve, - [

1-E51-F062, ( ASSD FEED) at MCC 1XD compartment DW2.

c. IF 1-E51-F062 is required to be Open THEN_ PLACE -the ESD Keylock Control Switch in the OPEN_ position, at g 8,j MCC IXD compartment DW2. ,

1

d. IF 1-E51-F062 is required to be Closed, THE_N_ PLACE the ESD Keylock Control Switch in the CLOSE_ position, at
  • MCC 1XD compartment DW .  ;
10. IF operation of Shutdown Cooling Inboard Suction Throttle L W1ve,1-E11-F009 is required AND_ power is NOT available from MCC 1XA, THEN
a. VERIFY OFF OR PLACE the circuit breaker control switch in the NT Suction 7Iir%sition for Shutdown at ottle Valve,1-E11-F009, Cooling MCC IXAInboard compartment DH3.
b. PLACE the circuit breaker control switch in the ON position for RHR Suction Isolation Valve, 1-E11-7609,

( ASSD FEED) at MCC IXD compartmet DX5.

c. IF 1-E11-F0D9 is required to be Open, THEN PLACE the Mose/Off/Open ASSD Feed Keylock Switch in the OPEN position, at MCC IXD compartment DX5.

s.

BSEP-1/ASSD-27 Page 5 of 12 Rev. O

[

d. IF 1-E11-F009 is required to be Closed THEN PLACE the 7.Tose/Off/Open ASSO Feed Keylock Switch in the CLOSE_  !'

position, at MCC IX0 compartment DX5.

ils WHEN Shift Foreman determines: i

a. Power is available from MCC IXC for operation of RCIC Steam Supply Inboard Isolation Valve,1-E51-F007. THEN (1) PLACE the circuit breaker control switch in the ON position for RCIC Steam Supply Inboard Tsolation Valve,1-E51-F007, at MCC 1XC compartment 0S4

/ -

Ind/Ver ,

(2) PLACE the circuit breaker control switch  !

in the OFF position for RCIC Steam Supply i Line is M tion Valve, 1-E51-F007, (ASSO i FEED) at MCC IXD compartment DY1.  :

/

Ind/Ver g 3,1 7

., t (3) PLACE the ASSO Keylock Control Swl'.uh in the OFF position, for RCIC Steam Supply Linel Tolation Valve, 1-E51-F007, at MCC i IXD compartment DY1.

I

/

l Ind/ Var

! b. Power is available from MCC IXA for operation of RCIC [

Turbine Exhaust Vacuum Breaker Valve, 1-E51-F062, M i (1) PLACE the circuit breaker control switch f in the ON position for RCIC Turbine  ;

Exhaust'Tacuum Breaker Valve,1-E51-F062, l at MCC IXA compartment DE4 l r

/. [:

I nd e --

I (2) PLACE the circuit breaker control switch

' in the OFF position for RCIC N rbine i Vacuum Breaker Valve,1-E51-F062, ( ASSD  !

FEED) at MCC IX0 compartment DW2 .

t

/ . s hd/Ver t

r BSEP-1/ASSD-27 Page 6 of 12 Rev. O f

6 l

(3) PLACE the ASSO Keylock Control Switch in the OFF_ position for RCIC Turbine Vacuum a Breaker Valve,1-E51-F062, at MCC IXD compartment OW2.

/

R /Ver

c. Power is available from MCC 1XA for operation of Sh*Jtdown Cooling Inboard Suction Throttle Valve, 1-E11-F009, THEN (1) PLACE the cirev;t breaker control switch in the ON position for Shutdown Ccoling Inboard 7uction Throttle Valve, 1-E11-F009, at MCC IXA compartment DH3.

/

Ind/Ver (2) PLACE the circuit breaker control switch in the OFF position for RHR Suction Isolation Valve,1-E11-F009, ( AS50 FEED) at MCC 1X0 compartment OX5.

/ R B.i Ind/Ver (3) PLACE the Close/Of f/Open ASSO Xeylock Switch in the OFF position for RHR Suction Isolation Valve,1-E11-F009, at MCC 1XD compartment DX5.

/

Ind/Ver

d. Reactor Water level indicator,1-821-L1-R604BX, is no longer required T_ HEN PLACE Reactor Water Level "NORMAL / LOCAL" Switch, 1-821-C5-3345 at the Remote Shutdown Panel, to the "NOR?4AL" position.

/

Ind/Ver

12. WHEN:

a., The fire has been extinguished AND

b. All breakers, AND/OR_ switches operated in this procedure are restored to their normal position AND BSEP-1/ ASS 0-27 Page 7 of 12 Rev. O
c. No actions within this procedure are required to y u achieve or maintain Cold Shutdown,_THE_N
d. EXIT.this procedurs.

Date/ Time Completed __ _

Performed By (Print) Initials t,

t, Reviewed By:

Shift Foreman R 8.:

i

l. .

BSEP-1/ASSD-27 Page 8 of 12 Rev. O

CONTROL= = . =

BUIL DING an FS >-

ro UHIr No.2 ro e.u,7 uo.,

nEAC ron _sp ea_ c5 so'-o, ntACron stos. Et so.o.-

g e 1 - - - - m &~w~1T T, , , , y xw,_ .,-rrrr3k_.--------1 ItsVoisi w ]

pogu 12s V 0/57 e PNL 48

~

l cowy ro PNL 3B ,,

c x:eI ,,To,. w

[7[

q I ia j

^- ' J '"V

+

y

/*H12 P622 s  !=Hl! 9623 l

}- l

- M I I

~~

I 1 Qt l= Hit P6/ 7 ' l f ,,.

',, / l E

  • HIE *E0EE " l H12*P614 Y-t i r i' i l ~-

CoMTMol pooW l

I I I if d

l 17 '

th

  • og 2 Mit=P6/4 l

' }

5 l f.gf .p l l l'2 I - .H12-P622 0  !

y4;g.pgg3 l i i 9 l

r7 r- r
I ib y 9, \ i I  ::

k O

-)

%'-l g m

12S V olS T.

Q er.4_r m ,,.(

5 Li2SV olST.

PflL 4A o e PNL 3 A g(, 4g _ g ro:oltstL GtHtMAroM BUILolNG, seMVICE warts sulloING, MEKToM GUILolNG ANo g g, g ru t E s s T rA n o ., __

glQy rnon tp_ Access __88tCKE MA1

- ^ m, its/2sov oC its/230v oC

~ $wirCH90ARo 28 s Wi rCH80A Ro lB ^ m, >=

== - M

  • e.

m e,"

  • W r i

!"O,W(L.

'W 9 ' '

~

u .8 gg ys.g n l f' 4,=0 I

49-0 ,sA l\ .

" n

" " ~

og A,$$0 8(I- 8,dhI (7JIMNT LOOLER

";P" ~ """

if W rCnts ,/ st a TCnts f WS A gA pg W8*A UNIr ! CABLt - *^tt sArt UNIT I CABLE stMtso Ants

    • ** sentAo A*cs T- . .

125/2sov oC %Its/2sov OC 1

swlTCHooAno 2A) y,2)*-( swlrCueoano I A LEGENo

- ~ ~ ACCESS /ECMEss f PM0kt JACK, TRAIM A OR 3 F_lGURE 1 Control Building 23'0" and 49'0" Elevations Access / Egress and Sound Powered Phone Comunications BSEP-1/ASSO-27 Page 9 of 12 Rev. O

I UNIT I MEACTOM BUILDING _

1 i z ~%a w lf

\

FMON CONT W 9UILCING MCESS

)

94tt2t1mLY \

  1. % ~

fo & FAICH -

\ - l s o '- o - -

<r0 a nou EL E VA TIC M - - h$ /

/ ?0'-0* Rivert0N

' ~~'## # #E V

\

QRYWELL f A IXS(03Z1- =h V }pl.'

4 I

j

_ *f -

~~MCClx0A NCCIND =- / \

lh ,a, 3g* MCCIXA NCC Ix0GM y/-

) y r

g//e k .CAC-Sv.Ittst m/

l ixa-a --

7 mi.CA C.,y. as u nS0' i MMOTE A \ =

fd

,\

g\.

)

l t-  ? na

ro e in0s ..n

-[:))

80'-0' 8"##~

1 I

/

To a r#0N / -

8 C-l,, [ MCClx0}

I CL E VA TION 17'd*-

a= . MCC IXC 4

- n a K ,J-- -

EL EVATION 20'- 0

  • LEGEND

~ ~ ~ ~ ACCESS / EGMts3 f PHONC JACK, TMAIN A OM 8 e ISCL Aff $ WITCH FIGURE 2 Unit 1 Reactor Building 20'-0" Elevation - Access / Egress and Sound Powered Phone Comunications

\

BSEP-1/ ASS 0-27 Page 10 of 12 Rev. 0

?

k

UNIT 1 REACTOR BUILDING

~s "

N0 NTH h A t-Ell-F0688 " U $l +

(ELEV. 45'0") 1 I= j =

l s t-Ell-F068A d: (ELEV. 55' 0")

r0 a Fnou  ?! -,_{ sn~7 l{,,o , ,go ,

20' 0"EL EVAT/0N-45 m 20 *-0"EL E VAT /0N e _u.~

- l _

= 1 DRYWELL l

.l -

j .-

c= ,

I SW-V105 # ~ - - * - - " '

\ [ -*-- f l SW-Vlot Q - ,- g r- -

RB.

70 .

ELEVATION

-lY'"'("+I v ++

r1 l'

' ^ '

' A 20*-0 }

I sw / EL. 50'-07 nunsw ruurs V106 LEGEND

~ ~ ~ ACCESS /ECnESS E VALVES FIGURE 3 Unit 1 Reactor Poilding 50'-0" Elevation - Access / Egress BSEP-1/ ASS 0-27 Page 11 of 12 Sev. O

UNIT / CE-CTO,? BUIL 0tNg corra l

On W CLL '

\ /

nun pours - + -

% / g,, e- ** hm!S

--nCIC rust u nnet noeg E

)

/ \

fg'g{ $G', " CC ';

  • A0 3 .I 7 *. 0*_

i-arco ou *cor "

,w__---

(Lterreciss'.0* y s TO O FROM ELEVATION 20** 0* _[ (saccco nnn ovuos I

g .o..

j , ..

s _ _ 7_ .

N' q

%N LA00fR y l-i l -t 40 t* e Jaariva

( I

(

's k e

GMA TING " -

i ,N r MMM MX'

/ h' a . s a . vois tL tar **Cs)-t'.0*

L t. s a - vti r EL.(APPA ur)+1' 0*

CETAll A J (EL. 9'- 0*) cgg ,Q FIGURE 4 Unit 1 Reactor Building -17'-0" Elevation - Access / Egress l

BSEP-1/ ASS 0-27 Page 12 of 12 Rev. O