IR 05000255/2017007

From kanterella
Jump to navigation Jump to search
NRC Design Bases Assurance Inspection (Teams) Inspection Report 05000255/2017007 (DRS-J.Benjamin)
ML17363A435
Person / Time
Site: Palisades 
Issue date: 12/29/2017
From: Jeffers M
NRC/RGN-III/DRS/EB2
To: Arnone C
Entergy Nuclear Operations
References
IR 2017007
Preceding documents:
Download: ML17363A435 (26)


Text

December 29, 2017

SUBJECT:

PALISADES NUCLEAR PLANTNRC DESIGN BASES ASSURANCE INSPECTION (TEAMS) INSPECTION REPORT 05000255/2017007

Dear Mr. Arnone:

On November 17, 2017, the U.S. Nuclear Regulatory Commission (NRC) completed a Triennial Baseline Design Bases Assurance Inspection (Teams) at your Palisades Nuclear Plant. The enclosed report documents the results of this inspection, which were discussed on November 17, 2017, with Mr. D. Corbin, and other members of your staff.

Two NRC-identified findings of very-low safety significance were identified and one Unresolved Issue. The findings involved violations of NRC requirements. However, because of their very-low safety significance, and because the issues were entered into your Corrective Action Program, the NRC is treating the issues as Non-Cited Violations in accordance with Section 2.3.2 of the NRC Enforcement Policy.

If you contest the violations or significance of these Non-Cited Violations, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555 0001; with copies to the Regional Administrator, Region III; the Director, Office of Enforcement; and the NRC resident inspector at the Palisades Nuclear Plant.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with 10 CFR 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely,

/RA/

Mark Jeffers, Chief Engineering Branch 2 Division of Reactor Safety Docket No. 50-255 License No. DPR-20 Enclosure:

IR 05000255/2017007 cc: Distribution via LISTSERV

SUMMARY

Inspection Report 05000255/2017007, 10/30/2017-11/17/2017; Palisades Nuclear Plant;

Design Bases Assurance Inspection (Teams).

The inspection was a 2-week onsite baseline inspection that focused on the design of components and modifications to mitigating systems. The inspection was conducted by regional engineering inspectors and two consultants. The inspection team identified two findings of very-low safety significance (Green) associated with Non-Cited Violation (NCVs) of U.S. Nuclear Regulatory Commission (NRC) regulations. The significance of inspection findings is indicated by their color (i.e., Green, White, Yellow, and Red) and determined using Inspection Manual Chapter 0609, Significance Determination Process, dated April 29, 2015.

Cross-cutting aspects are determined using Inspection Manual Chapter 0310, Aspects Within the Cross-Cutting Areas, dated December 4, 2014. All violations of NRC requirements are dispositioned in accordance with the NRCs Enforcement Policy, dated November 1, 2016. The NRC's program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, Reactor Oversight Process, Revision 6, dated July 201

NRC-Identified

and Self-Revealed Findings

Cornerstone: Mitigating Systems

Green.

The team identified a finding of very-low safety significance (Green) and an associated NCV of Title 10 of the Code of Federal Regulations, Part 50, Appendix B,

Criterion XI, Test Control, for the failure to periodically test the emergency diesel generators (EDGs) capability to start and accelerate all of the sequenced loads within the applicable design voltage and frequency transient and recovery limits. Specifically,

EDG testing activities did not demonstrate that all of the EDG auto-sequenced loads started and accelerated within the applicable voltage and frequency limits during start-up and recovery. In addition, the licensee did not perform adequate post-modification testing after replacing the EDG governor controller system or voltage regulators.

The licensee captured these issues in their Corrective Action Program as Condition Report (CR) 2017-05265 and CR 2017-05283, and performed an operability evaluation which reasonably determined the affected structures, systems, and components were operable.

The performance deficiency was determined to be more-than-minor because it was associated with the Mitigating Systems cornerstone attribute of equipment performance and affected the cornerstone objective of ensuring the availability, reliability, and capability of mitigating systems that respond to initiating events to prevent undesirable consequences. The finding screened as of very-low safety significance (Green)because it did not result in the loss of operability or functionality of mitigating systems.

Specifically, the licensee evaluated the most recent voltage and frequency data from the last EDG output breaker tests in which the data recorder was left running after the output breaker shut and reasonably determined that the EDGs and the affected loads were operable. The team did not identify a cross-cutting aspect associated with this finding because it was not confirmed to reflect current performance due to the age of the performance deficiency. Specifically, the associated testing procedures were established more than 3 years ago. (Section 1R21.3.b(1))

Cornerstone: Barrier Integrity

Green.

The inspectors identified a finding of low safety significance (Green) and an associated potential NCV of Title 10 of the Code of Federal Regulations, Part 50,

Appendix B, Criterion III, Design Control, for failure to meet Updated Final Safety Analysis Report requirements for containment spray piping supports, specifically straps.

Specifically, the inspectors identified that Calculation No. EA-SP-03369-02, Revision 0, used inelastic acceptance limits for the pipe straps which connect the pipe to the pipe support, in order to demonstrate Class I compliance which was not in accordance with the design and licensing basis specification. The license entered the issue into their Corrective Action Program as CR-PLP-2017-05246, Spray Pipe Support, dated November 14, 2017. The licensee performed an analysis to establish reasonable assurance of operability and the inspectors with support from the Office from the Nuclear Reactor Regulation reviewed this operability and no performance deficiencies were identified.

The performance deficiency was determined to be more-than-minor because it was associated with the Barrier Integrity Cornerstone attribute of design control and adversely affected the cornerstone objective to provide reasonable assurance that physical design barriers (fuel cladding, reactor coolant system, and containment) protect the public from radionuclide releases caused by accidents or events. This finding is of very-low safety significance (Green) because there was no actual reactor containment barrier degradation. The inspectors did not identify a cross-cutting aspect associated with this finding because this was a legacy design issue; and therefore, was not reflective of current performance. (Section 1R21.5.b(1))

REPORT DETAILS

REACTOR SAFETY

Cornerstone: Initiating Events, Mitigating Systems, and Barrier Integrity

1R21 Design Bases Assurance Inspection (Teams)

.1 Introduction

The objective of the design bases assurance inspection is to verify that design bases have been correctly implemented for the selected risk significant components and modifications, and that operating procedures and operator actions are consistent with design and licensing bases. As plants age, their design bases may be difficult to determine and an important design feature may be altered or disabled during a modification. The inspection also monitors the implementation of modifications to structures, systems, and components as modifications to one system may also affect the design bases and functioning of interfacing systems as well as introduce the potential for common cause failures. The Probabilistic Risk Assessment model assumes the capability of safety systems and components to perform their intended safety function successfully. This inspectable area verifies aspects of the Initiating Events, Mitigating Systems, and Barrier Integrity cornerstones for which there are no indicators to measure performance.

Specific documents reviewed during the inspection are listed in the Attachment to the report.

.2 Inspection Sample Selection Process

The team initially selected samples that were more safety-significant for shutdown conditions based upon the companys public announcement to permanently shutdown in the fall of 2018. Components related to the spent fuel pool cooling water system, spent fuel pool reactivity control components, and control room emergency ventilation systems were therefore initially chosen.

The licensee made the decision to not shutdown in 2018, but rather continue operations until the spring of 2022 several weeks before the inspection was scheduled to start.

Based upon this information, the team selected additional, more traditional, risk significant components based upon the risk insights of the licensees Probabilistic Risk Assessment model, and the Palisades Nuclear Standardized Plant Analysis Risk model with the assistance of a U.S. Nuclear Regulatory Commission (NRC) Region III senior risk analyst. The team selected both the loss of off-site power (LOOP) and steam generator tube rupture events to refine the final component selection, including the large early release frequency (LERF) component selection.

The team also used additional component information such as a margin assessment in the selection process. This design margin assessment considered original design reductions caused by design modifications, power uprates, or reductions due to degraded material condition. Equipment reliability issues were also considered in the selection of components for detailed review. These included items such as performance test results, significant corrective actions, repeated maintenance activities, Maintenance Rule (a)(1) status, components requiring an operability evaluation, system health reports, and NRC resident inspector input of problem areas/equipment. Consideration was also given to the uniqueness and complexity of the design, operating experience, and the available defense in depth margins. A summary of the reviews performed and the specific inspection findings identified are included in the following sections of the report.

The team also identified modifications for review with a focus on modifications implemented within the last 3 years. In addition, the inspectors selected procedures and operating experience issues associated with the selected components and other risk informed factors.

This inspection constituted 21 samples (10 components with 1 component associated with LERF implications, 6 modifications, and 5 operating experience) as defined in Inspection Procedure 71111.21M-02.01. The team applied approximately 80 percent inspection effort on the traditional risk-significant component, operating experience, and modification samples. The remaining approximate 20 percent effort was used to review the original shutdown component selection.

.3 Component Design

a. Inspection Scope

The team reviewed the Updated Final Safety Analysis Report (UFSAR), Technical Specifications, design basis documents, drawings, calculations and other available design basis information, to determine the performance requirements of the selected components. The team used applicable industry standards, such as the American Society of Mechanical Engineers Code, Institute of Electrical and Electronics Engineers (IEEE) Standards, and the National Electric Code, to evaluate acceptability of the systems design. The NRC also evaluated licensee actions, if any, taken in response to NRC issued operating experience, such as Bulletins, Generic Letters, Regulatory Issue Summaries, and Information Notices. The review was to verify that the selected components would function as designed when required and support proper operation of the associated systems. The attributes that were needed for a component to perform its required function included process medium, energy sources, control systems, operator actions, and heat removal. The attributes to verify that the component condition and tested capability was consistent with the design bases and was appropriate may have included installed configuration, system operation, detailed design, system testing, equipment and environmental qualification, equipment protection, component inputs and outputs, operating experience, and component degradation.

For each of the components selected, the inspectors reviewed the maintenance history, preventive maintenance activities, system health reports, operating experience-related information, vendor manuals, electrical and mechanical drawings, operating procedures, and licensees Corrective Action Program (CAP) documents. Field walkdowns were conducted for all accessible components selected to assess material condition, including age-related degradation, configuration, potential vulnerability to hazards, and consistency between the as-built condition and the design. In addition, the team interviewed licensee personnel from multiple disciplines such as operations, engineering, and maintenance. Other attributes reviewed are included as part of the scope for each individual component.

The following 10 components (samples), including a component with LERF implications, were reviewed:

Emergency Diesel Generator (EDG) Fuel Oil Transfer Pump (MDP 18A): The team reviewed drawings and calculations associated with pump motor cable sizing, voltage drop during degraded voltage conditions, and total current drawn by the motor compared to the ampacity of the feeder cables. The team also, reviewed the maximum short circuit current available at the feeder breaker and verified that the breaker interrupting capacity was not exceeded. The team also, reviewed the vendor manual of the pump motor to compare recommended maintenance versus the licensees actual maintenance activities. The team reviewed calculations for hydraulic performance, net positive suction head (NPSH), required total developed head, pump vibration analysis, pump run-out conditions, potential for vortex formation and loss of suction at the suction source. Seismic design documentation was reviewed to verify pump design was consistent with limiting seismic design conditions. The team also reviewed diesel fuel oil storage requirements for transient and accident conditions.

Condensate Storage Tank (CST): The team reviewed seismic and tornado missile calculations, drawings, and operating procedures associated with the CST. The inspectors assessed the stress analysis for portions of the auxiliary feedwater piping that is connected to the CST. The inspectors assessed the tank's volume, capacity, levels, and setpoints with respect to auxiliary feedwater (AFW) pump suction requirements.

CST Level Transmitters (LT021/22): The team reviewed the schematic and instrument loop diagrams of the level transmitters, their setting sheets, power supply requirements, calibration data and heat trace requirements of the instrument tubing. The team reviewed the operation of the level transmitters during freezing conditions concurrent with a loss of offsite power or a station black out, since the heat tracings were powered from nonsafety-related sources.

The team reviewed the trip circuitry of the AFW pumps on low suction pressure and verified that the low suction pressure switch settings were adequately coordinated with the AFW pump NPSH requirements.

Positive Displacement Pump (MDP 55A): The team reviewed the electrical schematic and wiring drawings of the pump motor, name plate data, and minimum voltage requirements compared to the minimum available voltage during degraded voltage conditions. The team also reviewed the feeder cable size compared to the pump motor ampacity requirements. The team verified that the motor name plate data was correctly translated in the electrical load flow, short circuit and voltage drop calculations. Also, the feeder breaker interrupting capacity was verified to be above the maximum short circuit current available at the breaker and the breaker control components. The team reviewed calculations for hydraulic performance, NPSH, required total developed head and pump run-out conditions. Seismic design documentation was reviewed to verify that the pump design was consistent with limiting seismic design conditions.

Test results were reviewed to verify acceptance criteria were met and performance degradation would be identified, taking into account set-point tolerances and instrument inaccuracies.

2400 VAC Safeguard Transformer: The team reviewed loading calculations to determine whether the capacity of the transformer was adequate to supply worst-case loading. Voltage calculations and operating procedures were reviewed to determine whether transformer taps and administrative controls for switchyard voltage were adequate to assure the availability of offsite power during accident conditions. Procedures for preventive maintenance, inspection, and testing were reviewed to compare maintenance practices against industry and vendor guidance.

2400 VAC Safeguard Bus: The team reviewed calculations for electrical distribution, system load flow/voltage drop, short-circuit, and electrical protection to verify that bus capacity and voltages remained within the minimum acceptable limits. The protective device settings and circuit breaker ratings were reviewed to ensure adequate selective protection coordination of connected equipment during worst-case short circuit conditions. The team verified that degraded and loss of voltage relays and associated time delays were set in accordance with calculations, and that associated calibration procedures were consistent with calculation assumptions, associated time delays, and set point accuracy calculations. The team evaluated selected portions of the licensee response to NRC Generic Letter 2006-02, Grid Reliability and the Impact on Plant Risk and the Operability of Offsite Power, dated February 1, 2006. The team reviewed the stations interface and coordination with the transmission system operator for plant voltage requirements and notification set points. The team reviewed the 125VDC voltage drop calculations to ensure that the EDG breaker controls would have adequate voltage to operate during a LOOP event. The EDG loading calculations were reviewed to determine whether the capacity of the EDGs was adequate to supply worst case accident loads. The last EDG LOOP/loss-of-coolant accident (LOCA) surveillance tests were reviewed to ensure that the voltage and frequency dips and recovery were within the design limits.

Train A Main Steam Isolation Valve (CV-0510)LERF Sample: The inspectors reviewed Inservice Testing (IST) stroke time data and Air Operated Valve Program requirements to ensure valve performance was being appropriately monitored.

The inspectors reviewed the main steam piping from steam generator A to the containment penetration pipe stress analysis. The team reviewed open and closing force calculations to assess the main steam isolation valves capability to function as described in the UFSAR under all bounding conditions. The team reviewed power and control wiring diagrams to assess the control and actuation schemes adequacy. This review constituted one component sample with LERF implications.

AFW Suction Line Low Pressure Switch (PS 0741): The team reviewed the instrument loop and power supply drawings, pressure switch set points and calibration data. The team also, reviewed the AFW pumps low suction pressure trip circuitry and verified that the settings were adequately coordinated to ensure that the AFW pumps had adequate NPSH under design basis conditions.

A Train Spent Fuel Pool Cooling Water Pump: The team reviewed calculations for required hydraulic performance, NPSH, required total developed head, pump vibration analysis, pump run-out conditions, potential for vortex formation, loss of suction at the suction source and alternate means of fuel pool purification with a floating skimmer. Seismic design documentation was reviewed to verify pump design was consistent with design based seismic conditions.

A Train Control Room Recirculation Ventilation Dampers: The team reviewed calculations for load flow/voltage drop and short-circuit to verify that bus capacity and voltages remained within minimum acceptable limits. The protective device settings and circuit breaker ratings were reviewed to ensure adequate selective protection coordination of connected components during worst-case short circuit conditions.

b. Findings

(1) Failure to Periodically Test the Emergency Diesel Generators Capacity to Start and Accelerate Design Basis Sequenced Loads
Introduction:

The team identified a finding of very-low safety significance (Green)and an associated Non-Cited Violation (NCV) of Title 10 of the Code of Federal Regulations (CFR), Part 50, Appendix B, Criterion XI, Test Control, for the failure to periodically test the EDGs capability to start and accelerate all of the sequenced loads within the applicable design voltage and frequency transient and recovery limits. Specifically, EDG testing activities did not demonstrate that all of the EDG auto-sequenced loads started and accelerated within the applicable voltage and frequency limits during start-up and recovery. In addition, the licensee did not perform adequate post-modification testing after replacing the EDG governor controller system or voltage regulators.

Description:

The UFSAR, Section 8.1.1, Design Basis, states in part that the engineered safeguards electrical system is intended to meet all the other requirements identified in IEEE 308-1978. The IEEE 308-1978, Section 7.4, Periodic Equipment Tests, states that Tests shall be performed at scheduled intervals to

(1) Detect the deterioration of the system towards an unacceptable condition.
(2) Demonstrate that standby power equipment and other components that are not exercised during normal operation of station are operable. The UFSAR, Section 8.4.1.3, Design Basis, states that the recovery time for the EDG voltage to return to 90 percent of rated voltage after application of each load step is less than 3 seconds. The UFSAR, Sections 5.1.3.8 and 5.1.3.9, for Criterion 17 and 18, states that the onsite power system can be periodically tested to assure that they are operable and functional.

The licensee is not committed to NRC Regulatory Guides (RGs) 1.108 and 1.9, however these RGs describe an acceptable approach to test the diesels generator.

Position C.2.a.2 of RG 1.108 states that testing of diesel generator units during the Plant Preoperational Test Program and at least once every 18 months should demonstrate proper operation for design-accident-loading-sequence to design-load requirements and verify that voltage and frequency are maintained within required limits. Position C.4 of RG 1.9 stated, in part, that at no time during the loading sequence should the frequency and voltage decrease to less than 95 percent of nominal and 75 percent of nominal respectively. It also stated that Frequency should be restored to within 2 percent of nominal, and voltage should be restored to within 10 percent of nominal within 60 percent of each load-sequence time interval. The licensee did not provide the team an acceptable alternative to the requirements stated in the above RGs, but rather do not evaluate or review the voltage and frequency responses obtained during the RT-8C or RT-8D surveillances. Therefore, if left uncorrected, the governor or voltage regulator control system could, due to aging, drift from the original settings and not allow the EDG to recover quick enough after large load sequencing and have the potential of loads overlapping during application to the EDG.

The team noted the following deficiencies related to the EDG periodic testing:

The licensee, in surveillance procedures RT-8C and RT-8D, are only evaluating the steady-state voltage and frequency at the EDG terminals after the load sequencing is complete. However, section 6.3 of the test procedure verifies that the EDG successfully supports the sequenced starting of the engineered safeguards equipment, but only refers to Attachment 5 which only verifies the measured times for the sequence timers.

When the electronic governor or electronic voltage regulator are replaced or otherwise adversely affected during maintenance activities, the licensee tunes the new device using an approximate approach in an unloading condition which yield a gross setting.

The license entered the issue into their CAP CR 2017-05265 and CR 2017-05283. The licensee identified that historic LOOP/LOCA frequency and voltage trace data was available based upon the frequency and voltage recorders continuing to run during EDG output break time testing. The licensee analyzed the last EDG LOOP/LOCA traces and determined that the EDGs were currently operable. At the end of the inspection, the licensee was in the process of developing the corrective action to restore compliance.

Analysis:

The team determined that the failure to periodically test the EDG capacity to start and accelerate all of the sequenced loads within the applicable voltage and frequency limits was contrary to 10 CFR Part 50, Appendix B, Criterion XI, Test Control, and was a performance deficiency. The performance deficiency was determined to be more than minor because it was associated with the Mitigating Systems cornerstone attribute of equipment performance and affected the cornerstone objective of ensuring the availability, reliability, and capability of mitigating systems to respond to initiating events to prevent undesirable consequences. Specifically, the failure to test the EDGs capacity to start and accelerate all of the sequenced loads within the applicable limits periodically to identify degradation and following maintenance activities were the EDGs frequency and voltage responses could be impacted did not ensure availability, reliability, and capability of components supplied by the EDGs to perform their intended safety function.

The team determined the finding could be evaluated using the Significance Determination Process in accordance with Inspection Manual Chapter (IMC) 0609, Significance Determination Process, Attachment 0609.04, Initial Characterization of Findings, issued on June 19, 2012. Because the finding impacted the Mitigating Systems and Barrier Integrity cornerstones, the team screened the finding through IMC 0609 Appendix A, The Significance Determination Process for Findings At-Power, issued on June 19, 2012, using Exhibit 2, Mitigating Systems Screening Questions.

The finding screened as of very-low safety significance (Green) because it did not result in the loss of operability or functionality of mitigating systems. Specifically, the licensee evaluated the most recent voltage and frequency data from the last EDG output breaker tests in which the data recorder was left running after the output breaker shut and reasonably determined that the EDGs and the affected loads were operable.

The team did not identify a cross-cutting aspect associated with this finding because the performance deficiency was not reflective of current performance due to the age of the issue. Specifically, the associated testing procedures were established more than 3 years ago.

Enforcement:

Title 10 CFR Part 50, Appendix B, Criterion XI, Test Control, requires, in part, that a test program be established to assure that all testing required to demonstrate that structures, systems, and components will perform satisfactorily in service is identified and performed in accordance with written test procedures which incorporate the requirements and acceptance limits contained in applicable design documents. It also stated that test results shall be documented and evaluated to assure that test requirements have been satisfied.

The UFSAR, Section 8.1.1, Design Basis, states in part that the engineered safeguards electrical system is intended to meet all the other requirements identified in IEEE 308-1978. The IEEE 308-1978, Section 7.4, Periodic Equipment Tests, states that Tests shall be performed at scheduled intervals to

(1) Detect the deterioration of the system towards an unacceptable condition.
(2) Demonstrate that standby power equipment and other components that are not exercised during normal operation of station are operable.

Contrary to the above, as of November 15, 2017, the licensee failed to establish a testing program to demonstrate that the EDGs could start and accelerate their sequenced loads within the applicable voltage and frequency acceptance limits periodically as required by IEEE 308-1978 and following maintenance activities that could adversely affect EDG frequency and voltage response (e.g. governor and voltage regulator maintenance activities.) The licensee is still evaluating its planned corrective actions, however, the team determined that the continued non-compliance does not present an immediate safety concern because the licensee reasonably determined the affected systems, structures, and components remained operable.

Because this violation was of very-low safety significance and was entered into the licensees CAP as CR-PLP-2017-05265 and CR-PLP-2017-05283, this violation is being treated as an NCV, consistent with Section 2.3.2 of the NRC Enforcement Policy.

(NCV 05000255/2017007-01; Failure to Periodically Test the Emergency Diesel Generators Capacity to Start and Accelerate Design Basis Sequenced Loads)

.4 Mitigating System Modifications

a. Inspection Scope

The team reviewed five permanent plant modifications. This review included in-plant walkdowns for accessible portions of the modified structures, systems, and components.

The team reviewed the modifications to verify that the design bases, licensing bases, and performance capability of the components had not been degraded through modifications. The modifications were selected based upon risk significance, safety significance, and complexity. The team reviewed the modifications selected to determine if:

the supporting design and licensing basis documentation was updated;

the changes were in accordance with the specified design requirements; the procedures and training plans affected by the modification have been adequately updated;

the test documentation as required by the applicable test programs has been updated; and

post-modification testing adequately verified system operability and/or functionality.

The team also used applicable industry standards to evaluate acceptability of the modifications. The modifications listed below were reviewed as part of this inspection effort:

Engineering Change (EC) 0000058140; Install Permanent Shielding on Letdown Heat Exchanger;

EC 0000058141; Install Shielding on Pressurizer Surge Line E-50A Platform;

EC 0000056644; Supplemental Diesel Generator Fuel Oil Tank to Comply with Michigan Fire Code;

EC 0000048188; FLEX EC#21 - Turbine Driven AFW System FLEX Upgrades;

EC 0000055367; Install Larger Size Power Cables between EX-04 (SU1-2) and 2400 VAC Buses 1C and 1D; and

EC 0000071766;52-389, Replace Control Transformer on CV-1510 MSIV Bypass Valve.

b. Findings

No findings were identified.

.5 Operating Experience

a. Inspection Scope

The team reviewed five operating experience issues (samples) to ensure that generic concerns had been adequately evaluated and addressed by the licensee. The operating experience issues listed below were reviewed as part of this inspection:

Point Beach Containment Dome Truss License Amendment Request 278, Risk-Informed Approach To Resolve Construction Truss Design Code Non-Conformances; March 31, 2017;

CR-PLP-2014-04976; C and D Batteries Part 21 Separator Misalignment LCR, KCR, and LCY Batteries;

NCV 05000285/2012011-04; Inadequate Design Basis Documentation;

NRC Information Notice 2012-06; Design Vulnerability in Electric Power Systems; and

NRC Regulatory Information Summary 2011-012, Adequacy of Station Electrical Distribution System Voltages.

b. Findings

(1) Containment Spray Pipe Support Strap Deficiencies
Introduction:

The inspectors identified a finding of low safety significance (Green) and an associated potential NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for failure to meet UFSAR requirements for containment spray (CS) piping supports, specifically straps. Specifically, the strap (connection between pipe and support) design of CS pipe supports HC44-R884, HC44-R884.1, HC44-R884.2, HC44-R884.3, HC44-R884.4, HC44-R884.5 and HC44-R884.9 did not comply with UFSAR Section 5.10.1.2 and Specification No. C-173(Q) requirements.

Description:

The CS system per UFSAR, Section 6.2.1, has the following safety-related design basis functions: The function of the CS system is to limit the containment building pressure rise and reduce the airborne radioactivity in containment by providing a means for spraying the containment atmosphere after occurrence of a LOCA or a main steam line break. The CS piping and pipe supports were designed to Class I requirements as described in UFSAR, Section 5.10.1.2, titled CP Co Design Class 1 Pipe Supports and Specification No. C-173(Q), Technical Requirements for the Analysis and Design of Safety-Related Pipe Supports, Revision 6. This specification was classified as safety-related. Calculation No. EA-SP-03369-02, Containment Spray System Pipe Supports, Revision 0 evaluated CS pipe supports HC44-R884, HC44-R884.1, HC44-R884.2, HC44-R884.3, HC44-R884.4, HC44-R884.5 and HC44-R884.9 in accordance with Class I requirements for all design basis loading.

The pipe supports were analyzed to withstand applied stress due to dead loads, live loads, seismic loads, and thermal loads. The inspectors identified that in Calculation No. EA-SP-03369-02, Revision 0, the licensee used inelastic acceptance limits for the pipe straps which connect the pipe to the pipe support, in order to demonstrate Class I compliance which was not in accordance with the design and licensing basis. The Class I requirements were based on UFSAR, Section 5.10.1.2, and Specification No. C-173(Q). The UFSAR, Section 5.10.1.2, does not specify the use of inelastic capacity for the straps which are considered catalog items. The capacity is based on a specified load capacity which is based on the strap maintaining its structural integrity with no permanent or plastic deformation allowed when subjected to the design loading.

Specification No. C-173(Q) delineated requirements consistent with UFSAR, Section 5.10.1.2. The inspectors determined the use of an inelastic acceptance limits for pipe support straps did not meet Class I requirements. The license entered the issue into their CAP as CR-PLP-2017-05246, Spray Pipe Support, dated November 14, 2017. The licensee performed an analysis to establish reasonable assurance of operability and the inspectors with support from the Office from the Nuclear Reactor Regulation.

Analysis:

The inspectors determined the licensees failure to meet Class I requirements for the CS pipe supports HC44-R884, HC44-R884.1, HC44-R884.2, HC44-R884.3, HC44-R884.4, HC44-R884.5 and HC44-R884.9 was contrary to 10 CFR Part 50, Appendix B, Criterion III, Design Control, and was a performance deficiency. The finding was determined to be more than minor because the finding was associated with the Barrier Integrity Cornerstone attribute of design control and adversely affected the cornerstone objective to provide reasonable assurance that physical design barriers (fuel cladding, reactor coolant system, and containment) protect the public from radionuclide releases caused by accidents or events. Specifically, failure to comply with Class I requirements did not ensure the Pipe Supports HC44-R884, HC44-R884.1, HC44-R884.2, HC44-R884.3, HC44-R884.4, HC44-R884.5 and HC44-R884.9 would function during a Class I design basis event and would adversely affect the CS piping system and containment barrier. The inspectors determined the finding could be evaluated using the SDP in accordance with IMC 0609, Appendix A, The Significance Determination Process for Findings At-Power, dated June 19, 2012, Exhibit 3, Barrier Integrity Screening Questions, for the Barrier Integrity cornerstone (Reactor Containment). The inspector answered no to the Barrier Integrity questions for Reactor Containment. The finding screened as having very-low safety significance (Green).

The inspectors determined there was no cross-cutting aspect associated with this finding because the deficiency was a legacy design calculational issue and, therefore, was not indicative of licensees current performance.

Enforcement:

Title 10 CFR Part 50, Appendix B, Criterion III, Design Control, requires, in part, that measures be established to ensure the applicable regulatory requirements and the design basis are correctly translated into specifications, drawings, procedures, and instructions. The design control measures shall provide for verifying or checking the adequacy of design.

Contrary to the above, as of November 14, 2017, the design control measures failed to conform to Class I requirements and also failed to verify the adequacy of the design.

Specifically, Calculation No. EA-SP-03369-02, Revision 0, failed to verify the adequacy of the design for the CS pipe supports HC44-R884, HC44-R884.1, HC44-R884.2, HC44-R884.3, HC44-R884.4, HC44-R884.5 and HC44-R884.9 to ensure it met the Class I requirements. Because this violation was of very-low safety significance (Green)and it was entered into the licensees CAP as CR-PLP-2017-05246, this violation is being treated as a NCV, consistent with Section 2.3.2 of the NRC Enforcement Policy.

(NCV 05000255/2017007-02; Containment Spray Pipe Support Strap Deficiencies)

(2) Containment Dome Truss Analysis
Introduction:

The inspectors identified an unresolved item (URI) concerning the analysis that demonstrated the design adequacy of the containment dome truss under design and licensing basis loading conditions.

Description:

The dome truss system was originally designed to support the containment liner plate and wet concrete during the construction of the containment dome (i.e., the liner plate initially acted as a form and the truss supported the form). After the concrete cured, the dome truss system was lowered away from the liner and was used to support the safety injection tanks (SITs) and CS system piping and their associated supports.

The CS and SIT systems are both safety-related which were required to be evaluated for seismic loads (self-weight and externally applied loads). The dome truss system would have also been required to be evaluated for seismic loads.

The UFSAR, Section 6.1, described the safety-related design function of the SIT system was to prevent fuel and cladding damage that could interfere with adequate emergency core cooling, and to limit the cladding-water reaction to less than approximately 1 percent for all break sizes in the primary system piping up to and including the double-ended rupture of the largest primary coolant pipe, for any break location, and for the applicable break time. Also, the SIT system also functions to provide rapid injection of large quantities of borated water for added shutdown capability during rapid cooldown of the primary system caused by a rupture of a main steam line.

UFSAR Section 6.2.1 described the safety-related design function of the CS system was to limit the containment building pressure rise and reduce the airborne radioactivity in containment by providing a means for spraying the containment atmosphere after occurrence of a LOCA or a main steam line break.

The inspectors requested the design basis analysis of the dome truss system that considers the LOCA loading on the dome truss system as well as the seismic loading due to the applied design loads from the CS and SIT system. During the time of the inspection, the licensee was unable to locate the dome truss analysis.

In response to the inspectors concern, the licensee entered the issue into their CAP as CR 2017-05016, Dome Trusses, dated November 1, 2017. The licensee is investigating the containment dome truss analysis further with the vendor of the dome truss system.

This issue is a URI pending additional inspector review of the design basis analysis for the containment dome truss system. (URI 05000255/2017007-03; Containment Dome Truss Analysis)

.6 Operating Procedure Accident Scenarios

a. Inspection Scope

The team performed a detailed reviewed of the procedures listed below. The procedures were compared to UFSAR, design assumptions, and training materials to assess their consistency. The following operating procedures were reviewed in detail:

4.48, Time Critical Action/Time Sensitive Action Program Standard, Revision 6;

EOP TCA, EOP Time Critical/Time Sensitive Operator Action Basis, Revision 2;

SOP 22, Emergency Diesel Generators, Revision 74;

AOP 41, Alternate Safe Shutdown Procedure, Revision 3; and

AOP Supplement 8, Operation of Panels EC-150/EC-150A, Revision 0.

For the procedures listed, time dependent operator actions were reviewed for adequacy.

This review included walk downs of in-plant actions with a licensed operator. In addition, the team evaluated operations interfaces with other departments such as engineering.

The following operator actions were reviewed:

Time critical operator actions to switch Control Room HVAC to Emergency Mode

b. Findings

No findings identified.

OTHER ACTIVITIES

4OA2 Identification and Resolution of Problems

.1 Review of Items Entered Into the Corrective Action Program

a. Inspection Scope

The team reviewed a sample of problems identified by the licensee associated with the selected samples and that were entered into the CAP. The team reviewed these issues to verify an appropriate threshold for identifying issues and to evaluate the effectiveness of corrective actions related to design issues. In addition, corrective action documents written on issues identified during the inspection were reviewed to verify adequate problem identification and incorporation of the problem into the CAP. The specific corrective action documents sampled and reviewed by the team are listed in the attachment to this report.

The team also selected seven issues identified during previous component design basis inspections to verify that the concerns were adequately evaluated and corrective actions were identified and implemented to resolve the concern, as necessary. The following issues were reviewed:

NCV 05000255/2014008-02, Undersized Supply Cables from Startup Transformer to 2400V Buses;

NCV 05000255/2014008-03, Undersized Motors;

NCV 05000255/2014008-05, Lack of Analysis for Electrical Containment Penetration Protection;

NCV 05000255/2014008-04, Failure to Ensure that 480VAC System Voltages do not exceed Equipment Ratings;

NCV 05000255/2014008-09, Failure to Include the Degraded Voltage Channel Time Delay in Technical Specification Surveillance Requirements;

NCV 05000255/2014008-10, Failure to include the Degraded Voltage Time Delay in TS Surveillance Requirements; and

NCV 05000255/2014008-13, Non-conservative Surveillance for Emergency Diesel Generator Largest Load Reject Test.

b. Findings

No findings were identified.

4OA6 Management Meetings

.1 Interim Meeting Summary

On November 16, 2017, the team presented the preliminary inspection results to Mr. J. Hardy and other members of the licensee staff. The licensee acknowledged the issues presented. The team confirmed that several documents reviewed were considered proprietary and were handled in accordance with the NRC policy related to proprietary information.

.2

Exit Meeting Summary

On November 17, 2017, the team presented the inspection results to Mr. D. Corbin and other members of the licensee staff. The licensee acknowledged the issues presented.

The team asked the licensee whether any materials examined during the inspection should be considered proprietary. Several documents reviewed by the team were considered proprietary information and were either returned to the licensee or handled in accordance with NRC policy on proprietary information.

ATTACHMENT:

SUPPLEMENTAL INFORMATION

KEY POINTS OF CONTACT

Licensee

C. Arnone, Vice President
D. Corbon, General Manager Plant Operations
O. Gustafson, Regulatory Assurance and Performance Improvement Director
K. OConnor, Engineering Director
J. Hardy, Regulatory Assurance Director
B. Sova, Design Engineering Manager
B. Baker, Maintenance Manager

U.S. Nuclear Regulatory Commission

M. Jeffers, Branch Chief
J. Benjamin, Senior Reactor Inspector

LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED

Opened and Close

05000255/2017007-01 NCV Failure to Periodically Test the Emergency Diesel Generators Capacity to Start and Accelerate Design Basis Sequenced Loads (1R21.3.b(1))
05000255/2017007-02 NCV Containment Spray Pipe Support Strap Deficiencies (1R21.5.b(1))

Open

05000255/2017007-03 URI Containment Dome Truss Analysis (1R21.5.b(2))

Discussed

None

LIST OF DOCUMENTS REVIEWED