Finding | |
|---|---|
| Title | Undersized Motors |
| Description | The inspectors identified a finding of very low safety significance and associated NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the licensees failure to ensure electric motors are sized in accordance with the design basis, as discussed in Palisades FSAR Section 6.2.3.1. Specifically, the horsepower ratings of certain motors are less than power demands of their driven equipment, and they were not analyzed to ensure overheating would not occur. The licensee entered this finding into their Correction Action Program with a recommended action to analyze the effect of the condition, and has verified the operability of the motors. This performance deficiency was determined to be more than minor, because it impacted the Design Control attribute of the Reactor Safety, Mitigating Systems Cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, motors serving loads with power demands in excess of the motor horsepower ratings were not analyzed to ensure that motor damage would not occur. The inspectors determined the finding was of very low safety significance (Green) because the SSC maintained its operability and functionality. This finding had a crosscutting aspect in the area of Human Performance, associated with the Design Margin component, because the licensee failed to ensure that equipment is operated within design margins, and margins are carefully guarded and changed only through a systematic and rigorous process. |
| Site: | Palisades |
|---|---|
| Report | IR 05000255/2014008 Section 1R21 |
| Date counted | Dec 31, 2014 (2014Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | A Stone C Baron C Brown C Zoia H Leake J Corujo-Sandin L Rodriguez S Sheldon |
| Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
| CCA | H.6, Design Margins |
| INPO aspect | WP.2 |
| ' | |
Finding - Palisades - IR 05000255/2014008 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Palisades) @ 2014Q4
Self-Identified List (Palisades)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||