SUBJECT:
PALISADES NUCLEAR PLANT - INTEGRATED INSPECTION REPORT 05000255/2022001
Dear Mr. Corbin:
On March 31, 2022, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Palisades Nuclear Plant and discussed the results of this inspection with you and other members of your staff. The results of this inspection are documented in the enclosed report.
No findings or violations of more than minor significance were identified during this inspection.
This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.
Sincerely, Billy C. Dickson, Jr., Chief Branch 2 Division of Reactor Projects Docket No. 05000255 License No. DPR-20
Enclosure:
As stated
Inspection Report
Docket Number:
05000255
License Number:
Report Number:
Enterprise Identifier:
I-2022-001-0065
Licensee:
Entergy Nuclear Operations, Inc.
Facility:
Palisades Nuclear Plant
Location:
Covert, MI
Inspection Dates:
January 01, 2022 to March 31, 2022
Inspectors:
J. Havertape, Reliability and Risk Analyst
P. Laflamme, Senior Resident Inspector
J. Mancuso, Acting Senior Resident Inspector
C. St. Peters, Resident Inspector
Approved By:
Billy C. Dickson, Jr., Chief
Branch 2
Division of Reactor Projects
SUMMARY
The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting an integrated inspection at Palisades Nuclear Plant, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.
List of Findings and Violations
No findings or violations of more than minor significance were identified.
Additional Tracking Items
None.
PLANT STATUS
The plant began the inspection period at full power and remained at or near full power for the entire inspection period.
INSPECTION SCOPES
Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors performed activities described in IMC 2515, Appendix D, Plant Status, observed risk significant activities, and completed on-site portions of IPs. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.
REACTOR SAFETY
71111.01 - Adverse Weather Protection
Impending Severe Weather Sample (IP Section 03.02) (1 Sample)
- (1) The inspectors evaluated the adequacy of the overall preparations to protect risk significant systems from impending severe weather during a winter storm warning with predicted heavy snow on February 1, 2022.
71111.04 - Equipment Alignment
Partial Walkdown Sample (IP Section 03.01) (4 Samples)
The inspectors evaluated system configurations during partial walkdowns of the following systems/trains:
- (1) Component cooling water (CCW) right train on January 3 and 4, 2022
- (2) Emergency diesel generator (EDG) 1-1 on January 18 and 19, 2022
- (3) Auxiliary feedwater (AFW) right train on February 4 through 9, 2022
- (4) Service water system right train on March 2 through March 23, 2022.
Complete Walkdown Sample (IP Section 03.02) (1 Sample)
- (1) The inspectors evaluated system configurations during a complete walkdown of the left train service water system on March 3 through March 23, 2022.
71111.05 - Fire Protection
Fire Area Walkdown and Inspection Sample (IP Section 03.01) (5 Samples)
The inspectors evaluated the implementation of the fire protection program by conducting a walkdown and performing a review to verify program compliance, equipment functionality, material condition, and operational readiness of the following fire areas:
- (1) Fire Area 26: Southwest Cable Penetration, elev. 590' and 607', on January 5-6, 2022
- (2) Fire Area 9: Screenhouse/ Intake Structure, elev. 590', on January 3-4, 2022
- (3) Fire Area 4: 1C 2.4KV Switchgear Room, elev. 590', on January 14, 2022
- (4) Fire Area 5 & 7: 1-1 Diesel Generator and Fuel Oil Day Tank Rooms, elev. 590', on January 19, 2022
- (5) Fire Area 24: Auxiliary Feedwater Pump Room, elev. 571' on January 31, 2022
71111.11Q - Licensed Operator Requalification Program and Licensed Operator Performance
Licensed Operator Performance in the Actual Plant/Main Control Room (IP Section 03.01) (1 Sample)
- (1) The inspectors observed and evaluated licensed operator performance in the Control Room during a downpower to support planned AFW testing on February 15, 2022.
Licensed Operator Requalification Training/Examinations (IP Section 03.02) (2 Samples)
- (1) The inspectors observed and evaluated SES-410 Rev.1 "LOR Simulator Exam Scenario" on February 1, 2022.
- (2) The inspectors observed and evaluated PSLEG-LOR-21F-07 "SM Choice" on February 17, 2022.
71111.12 - Maintenance Effectiveness
Maintenance Effectiveness (IP Section 03.01) (2 Samples)
The inspectors evaluated the effectiveness of maintenance to ensure the following structures, systems, and components (SSCs) remain capable of performing their intended function:
- (1) Service Water System on January 11, 2022
- (2) Control Rod Drive System on January 6, 2022
71111.13 - Maintenance Risk Assessments and Emergent Work Control
Risk Assessment and Management Sample (IP Section 03.01) (4 Samples)
The inspectors evaluated the accuracy and completeness of risk assessments for the following planned and emergent work activities to ensure configuration changes and appropriate work controls were addressed:
- (1) Elevated risk due to RR-9K main steam line calibration, on January 13, 2022
- (2) Protected equipment walkdown due to maintenance risk for 1-1 EDG out of service for scheduled maintenance, on February 7, 2022
- (3) Yellow risk due to QO-1 and M-1005 "SUPPLEMENT DIESEL GENERATOR 1-3" out of service, on March 16, 2022
- (4) Emergent work related to A main feed pump gland seal steam leak, on March 21, 2022
71111.15 - Operability Determinations and Functionality Assessments
Operability Determination or Functionality Assessment (IP Section 03.01) (3 Samples)
The inspectors evaluated the licensee's justifications and actions associated with the following operability determinations and functionality assessments:
- (1) Plant Process Computer evaluation on January 24, 2022
- (2) Evaluation of an incorrect indication during valve stroke for CWRT recirculation pump on February 28, 2022 (3)1-1 EDG fuel line support stud failure past operability evaluation on March 7, 2022
71111.18 - Plant Modifications
Temporary Modifications and/or Permanent Modifications (IP Section 03.01 and/or 03.02) (2 Samples)
The inspectors evaluated the following temporary or permanent modifications:
- (1) Engineering Change (EC) 76688: Engineering Safeguards Cooler Fan Modification on January 7, 2022
- (2) Service water supply to fire protection system modification with jockey pump removed from service on February 9, 2022
71111.19 - Post-Maintenance Testing
Post-Maintenance Test Sample (IP Section 03.01) (5 Samples)
The inspectors evaluated the following post-maintenance testing activities to verify system operability and/or functionality:
- (1) SOP-22 run of the 1-2 EDG following replacement of the fuel oil relief RV-1486, on January 18, 2022
- (2) QO-15 run of CCW pump P-52B following planned maintenance, on January 26, 2022
- (3) MO-7A-1 run of the 1-1 EDG following planned maintenance, on February 7, 2022
- (4) SOP-22 run of the 1-1 EDG following emergent work, on February 8, 2022
- (5) Plant Process Computer card replacement on March 22, 2022
71111.22 - Surveillance Testing
The inspectors evaluated the following surveillance testing activities to verify system operability and/or functionality:
Surveillance Tests (other) (IP Section 03.01) (6 Samples)
- (2) QO-14B; Service Water Pump P-7B test, on January 21, 2022
- (3) QO-21C; P-8C AFW pump test, on January 24, 2022
- (4) QO-5; Valve Test Procedure on February 15, 2022
- (5) QO-21B; P-8B AFW Pump Test on February 16, 2022
- (6) MO-7A-1; Monthly EDG 1-1 run, on March 18, 2022
Inservice Testing (IP Section 03.01) (1 Sample)
- (1) QO-19B P-66B HPSI and Engineered Safety Systems check valve operability inservice test, on January 20, 2022
71114.06 - Drill Evaluation
Drill/Training Evolution Observation (IP Section 03.02) (1 Sample)
The inspectors evaluated:
- (1) Phase 1 training drill on March 2,
OTHER ACTIVITIES - BASELINE
===71151 - Performance Indicator Verification The inspectors verified licensee performance indicators submittals listed below:
IE01: Unplanned Scrams per 7000 Critical Hours Sample (IP Section 02.01)===
- (1) Unit 1 (January 1, 2021 - December 31, 2021)
IE04: Unplanned Scrams with Complications (USwC) Sample (IP Section 02.03) (1 Sample)
- (1) Unit 1 (January 1, 2021 - December 31, 2021)
MS08: Heat Removal Systems (IP Section 02.07) (1 Sample)
- (1) Unit 1 (January 1, 2021 - December 31, 2021)
INSPECTION RESULTS
No findings were identified.
EXIT MEETINGS AND DEBRIEFS
The inspectors verified no proprietary information was retained or documented in this report.
On March 31, 2022, the inspectors presented the integrated inspection results to Mr. D. Corbin, Site Vice President, and other members of the licensee staff.
DOCUMENTS REVIEWED
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
Acts of Nature
Procedures
EN-FAP-EP-010
Severe Weather Response
Corrective Action
Documents
Resulting from
Inspection
CR-PLP-2018-
2315
NRC Questioned Presence of Water Coming Out of Conduit
in the NW Corner of EESG Room Near the Sump Pumps
05/04/2018
M-209, Sheet 2
Piping and Instrument Diagram - Component Cooling
System
Drawings
M-209, Sheet 3
Piping and Instrument Diagram - Component Cooling
System
Miscellaneous
DBD-1.02
Design Basis Document for Service Water System
SOP-12
14, Checklist 12.5, Auxiliary Feedwater System
Checklist (Except K-8 Steam Supply)
SOP-15
Service Water System
SOP-16
2, Checklist 16, Component Cooling System
Checklist
Procedures
SOP-22,
Diesel Generators System Checklist
CR-PLP-2022-
00007
Union Upstream of MV-FO703 Diesel Fire Pump P-41FO
Inlet has Evidence of Fuel Oil Leakage
01/03/2022
Corrective Action
Documents
CR-PLP-2022-
00009
Difference in Levels of Fuel Oil Present in Fuel Oil Filters for
Two Diesel Fire Pumps, P-9B and P-41
01/03/2022
Pre-Fire Plan 24
Auxiliary Feedwater Pumps Room / Elevation 571'
Pre-Fire Plan 26
Southwest Cable Penetration Room, Elevation 590' and 607'
Pre-Fire Plan 4,
34, 35, & 36
1-C Switchgear Room and Manhole 1, 2, & 3, Elevation 590',
Rooms 116A, 190, 191, & 192
Pre-Fire Plan 9
Screen House/Intake Structure, Rooms 136 and 136A,
Elevation 590'
Fire Plans
Pre-Fire Plans 5
& 7
Diesel Generator 1-1 and Fuel Oil Day Tank Room,
Elevation 590', Rooms 116 & 146
Miscellaneous
Fire Drill Scenario
2-002
Announced Drill: 590' Turbine Truck Bay
03/17/2022
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
Procedures
AOP Supplement
Fire Response Strategies, Fire Zone 26
PSLEG-LOR-
SM Choice
2/17/2022
Procedures
SES-410
LOR Simulator Exam Scenario
CR-PLP-2019-
2860
CRD-23, Control Rod Drive Mechanism
07/24/2019
CR-PLP-2019-
2861
CRD-14, Control Rod Drive Mechanism
07/24/2019
CR-PLP-2019-
04616
CRD-33 Secondary Position Indication (SPI)
11/20/2019
CR-PLP-2020-
04174
Control Rod Drive No. 3 Maintenance Rule Evaluation
11/05/2020
CR-PLP-2020-
275
Maintenance Rule Evaluation for Control Rod Drive No. 2
11/05/2020
Corrective Action
Documents
CR-PLP-2022-
238
Maintenance Rule Evaluation for the 2021 Condition of
CRD-23
2/01/2022
PLP-RPT-12-
00026
Maintenance Rule Scoping Document - Non-Critical Service
Water
Engineering
Evaluations
PLP-RPT-12-
00026
Maintenance Rule Scoping Document - Critical Service
Water
PLP-RPT-12-
00026,
CRD Maintenance Rule Scoping Document
System Health
Report
Control Rod Drive System
04/01/2020 -
06/30/2020
System Health
Report
Control Rod Drive System
10/01/2019 -
2/31/2019
System Health
Report
Control Rod Drive System
04/01/2021 -
06/30/2021
System Health
Report
Control Rod Drive System
10/01/2020 -
2/31/2020
Miscellaneous
System Health
Report
PLP, Unit 1, CSW - Critical Service Water
04/01/2021 -
06/30/2021
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
System Health
Report
PLP, Unit 1, CSW - Critical Service Water
10/01/2020 -
2/31/2020
System Health
Report
PLP, Unit 1, CSW - Critical Service Water
04/01/2020 -
06/30/2020
System Health
Report
PLP, Unit 1, UHS - Ultimate Heat Sink
04/01/2021 -
06/30/2021
System Health
Report
PLP, Unit 1, UHS - Ultimate Heat Sink
10/01/2020 -
2/31/2020
System Health
Report
PLP, Unit 1, UHS - Ultimate Heat Sink
04/01/2020 -
06/30/2020
Maintenance Configuration Control
08/31/2020
MSE-E-12
Permanent Maintenance Procedure Cable Terminations
Procedures
WI-SPS-E-02
Insulation Resistance Testing of Electrical Equipment
10/18/2020
Work Orders
00533513-05
CRDM Fan V-49A Tripped, Electrical Post-Maintenance Test
10/18/2020
Procedures
SOP-12
Feedwater System
2935792-01
RR-9K-Mainsteam Line Monitor RIA-2323 & RIA-2324
Calibration
01/13/2022
Work Orders
2991330-01
QO-1 Safety Injection Actuation System Test
03/16/2022
CR-PLP-2003-
08105
Bolt Found Sheered Off on Emergency Diesel Generator 1-1
2/07/2003
CR-PLP-2016-
00572
During the Performance of WO-52521845-01, K-6A 4 Cycle
Auxiliary System Maintenance, One of the Two Cylinder 2L
Fuel Tube-to-Head Clamping Studs Yield Before Torque was
Achieved
2/02/2016
CR-PLP-2022-
00097
Multiple Points on MC-1000, Palisades Plant Computer
System (PPC) went Invalid for 1 Minute and 6 Seconds
2/15/2022
CR-PLP-2022-
00154
PPC was Lost and Data on the PPC Went Invalid
01/22/2022
CR-PLP-2022-
00158
Multiple PPC Points Were Identified to Spike Simultaneously
01/23/2022
CR-PLP-2022-
283
After K-6A, Emergency Diesel Generator 1-1 was Secured
Following a MO-7A-1 Diesel Run, NPOs Found a Sheared
Stud on the Ground
2/07/2022
Corrective Action
Documents
CR-PLP-2022-
EK-3327 SOE Node Trouble
2/12/2022
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
00312
CR-PLP-2022-
00336
MC-1000-SPI, Secondary Computer Alarm EK-0971
2/16/2022
CR-PLP-2022-
00365
Some of the Main Turbine/Generator/Exciter Inputs to the
PPC Went Invalid
2/19/2022
CR-PLP-2022-
00371
Noticed HB_PWR_STEADY on PPC Momentarily go Invalid
2/20/2022
CR-PLP-2022-
00418
Incorrect Indication During Valve Stroke for CWRT Recirc
Pump
2/28/2022
CR-PLP-2022-
00478
There was a Temporary Loss of Some PPC Indications and
the CTCS System Rebooted
03/09/2022
DBD-2.05
Reactor Protective System Safety Injection Signal
Anticipated Transient Without SCRAM
Miscellaneous
DBD-2.06
Control Rod Drive System (CRD)
Operability
Evaluations
CR-PLP-2022-
283
Past Operability Evaluation in Accordance with EN-LI-108
03/10/2022
Operability Determination Process
Procedures
SOP-34,
PPC Operability Check
CR-PLP-2021-
2828
As Found Wiring Did Not Match the Wiring Drawing
E0007-SH-77
11/03/2021
Corrective Action
Documents
CR-PLP-2022-
00316
Service Water Booster Pump P-25B Discharge
2/14/2022
E-279
Schematic Diagram, Engineered Safeguards Room Coolers
M-213
Piping & Instrument Diagram Service Water, Screen
Structure and Chlorinator
M-216
Piping & Instrument Diagram Fire Protection System
Drawings
VEN-E7, Sheet
Wiring Diagram; MCC 1 52-133 Engineered Safeguards
Room Cooler V27C
Base EC to Replace MCC Breaker Buckets on
MCC 1, 2, 7, 8
Engineering
Changes
Correction of DWG E-279 Error as Described in
03/25/2019
Miscellaneous
DBD-1.02
Design Basis Document for Service Water System
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
Field Change
Request Number
91577
Correct Latent Drawing Error on E0077 Reference
FSAR 9.6.2.3
FSAR Chapter 9 Auxiliary Systems System Operation
EN-DC-115-01
Industry Standard Design Process
Maintenance Configuration Control
11/05/2021
MSE-E-12
Terminal Lug/Connector Installation Data Sheet
11/03/2021
SOP-21
Fire Protection System
SOP-21
Supply Fire Header Pressure with Service Water Booster
Pump
Procedures
SPS-E-11
480 Volt Breaker Inspection and Repair
11/03/2021
Work Orders
500202-04
V-27C Engineering Safeguards Room Cooler Fan
11/02/2021
CR-PLP-2022-
213
Plant Process Computer Automatic Reboot
01/29/2022
CR-PLP-2022-
241
EK-0971 SPI Trouble Alarms
2/01/2022
CR-PLP-2022-
288
Processor Card Would Not Communicate with the PPC
2/08/2022
Corrective Action
Documents
CR-PLP-2022-
00302
Received EK-0971, SPI Trouble, Unexpectedly
2/10/2022
SOP-22
Diesel Generator Log Sheet
Procedures
SOP-22,
Diesel Generator Log Sheet
00550301-01
K-6A; Replace Dirty Air Filters - VLC
2/07/2022
00550301-02
K-6A, Air Intake Filter; PMT (Ops): Replace Element
2/07/2022
00566208-01
F-91; Oil Leak from Filter Lid at Start of Run
2/07/2022
00566208-02
F-91; Lid Leaking - (Ops) PMT
2/07/2022
00567101-01
P-52B; Replace Inboard (Coupling End) Oiler
01/26/2022
00570091-01
RV-1486; Replace Valve
01/08/2022
00570091-02
RV-1486; PMT
01/07/2022
Work Orders
00570091-03
RV-1486; Adjust Fuel Oil Relief Valve
01/08/2022
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
2939019-01
EEQ Maintenance - Component Cooling, EMA-1208, P52B
Motor
01/26/2022
2939019-02
EEQ Maintenance - Component Cooling, EMA-1208, P-52B
Motor PMT
01/26/2022
2979625-02
P-52B, PMT (Ops): Pump Bearing Oil Change (OPS553)
01/26/2022
2988018-01
QO-15B, Inservice Test Procedure - Component Cooling
Pump P-52B
01/26/2022
2988475-01
MO-7A-1X-D/G 1-1 Emergency Diesel Generator Fuel Oil
Transfer Test
2/07/2022
546447-02
P/S-MC1000-01; Field Adjust Power Supply Voltage
2/17/2021
573330-01
MC-001C, J-451-A2 (MX01-16) Instrumentation and Control
01/26/2022
573330-06
MC-1000, PPC, Changing Time for PPC Node
2/14/2022
574259-01
K-6A, 1-1 EDG; Repair Broken Bolt
2/08/2022
MO-7A-1
Emergency Diesel Generator 1-1
104
QO-14
Inservice Test Procedure - Service Water Pumps
Procedures
QO-19
Inservice Test Procedure - HPSI Pumps and ESS Check
Valve Operability Test
2986174-01
QO-15A-P-52A ISI Test Procedure - Component Cooling
Pump
01/06/2022
2986893-01
QO-14B-P7B, IST Service Water Pump
01/11/2022
2987814-01
QO-21C -P-8C, Auxiliary Feedwater Pump Inservice Test
01/24/2022
2989054-01
QO-21B-P-8B, IST Auxiliary Feedwater System
2/15/2022
Work Orders
2990893-01
QO-5 - Valve Test Procedure (Including Containment
Isolation Valves)
2/15/2022
NRC Performance Indicators Unplanned Scrams with
Complications (IE-04)
01/01/2021-
2/31/2021
NRC Performance Indicators Unplanned Scrams per
7,000 Critical Hours (IE-01)
01/01/2021 -
2/31/2021
71151
Miscellaneous
NRC Performance Indicators Mitigating Systems
Performance Indicator Heat Removal Systems (AFW)
(MS-08)
01/01/2021 -
2/31/2021