Georgia b Power Vce PresKient, Nuclear Vogtle Prosect the souttern electrc System December 13, 1989 ELV-01148 0161 Docket Nos. 50-424 50-425' Director, Office of Resource Management U. S. Nuclear Regulatory Commission | |||
' Washington, D. C. '20555 4 | |||
Gentlemen: | |||
.V0GTLE ELECTRIC GENERATING PLANT MONTHLY OPERATING REPORTS Enclosed are the November,1989 monthly operating reports for Vogtle Units 1 and | |||
: 2. 'These reports are submitted in accordance with Technical Specification 6.8.1.5. | |||
Sincerely, C. K. McCoy CKM/NJS/gm Enclosures xc: Georaia Power Company i Mr. C. K. McCoy 1 Mr. G. Bockhold, Jr. I | |||
-Mr. P..D. Rushton Mr. R. M. Odom NORMS' | |||
~U. S. Nuclear Reaulatory Commission ! | |||
, Mr. S. D. Ebneter, Regional Administrator ; | |||
Mr. J. B. Hopkins, Licensing Project Manager, NRR i Mr. J. F. Rogge, Senior Resident Inspector, Vogtle Document Control Desk U | |||
8912210051 891130 | |||
+PDR ADOCK 05000424 . | |||
iR PDC , | |||
) | |||
r.--. | |||
<4; : c. | |||
[ | |||
ENCLOSURE 1 V0GTLE ELECTRIC GENERATING PLANT - UNIT 1 MONTilLY OPERATING REPORT FOR NOVEMBER, 1989 TABLE OF CONTENTS NARRATIVE. REPORT Page Vl-1 OPERATING DATA REPORT Page Vl-2 AVERAGE DAILY POWER LEVEL Page VI-3 UNIT SiluTDOWNS AND POWER' REDUCTIONS Page VI-4 | |||
.l i | |||
l l | |||
l~ | |||
3 i | |||
;n.. | |||
, 8 NARRATIVE REPORT DOCKET NO. 50-424 UNIT 1 DATE: DECEMBER 5 1989 COMPLETEDBY:'J.C.WILL}AMS TELEPHONE: (404) 826-4279 NOVEMBER 1 00:00 -UNIT 1 AT 100% POWER WITH NO OPERATIONAL PROBLEMS. | |||
. NOVEMBER 10 08:20 POWER REDUCTION TO 90% DUE TO FAILED MFP "B" SPEED PICKUP # 2. | |||
. NOVEMBER 10. 19:54 POWER REDUCTION TO 72% TO REPLACE MFP "B" SPEED PICKUP # 2. | |||
' NOVEMBER 12 00:30 COMMENCE RAMP TO FULL POWER. l | |||
' NOVEMBER 12 14:00 UNIT 1 AT FULL POWER. | |||
NOVEMBER 28 12:38 POWER REDUCTION TO 70% TO REPLACE MFP "B" SPEED PICKUP # 1. | |||
NOVEMBER'29 18:04 COMMENCE RAMP TO FULL POWER. | |||
NOVEMBER 30 03:00 UNIT 1 AT 100% POWER. | |||
. NOVEMBER 30 23:59 UNIT 1 AT 100% POWER WITH NO OPERATIONAL PROBLEMS, L i l | |||
l l | |||
1 l | |||
Vl-1 | |||
T .; | |||
s'y 1', _ . l n ._ . | |||
t 1 l | |||
OPERATING DATA REPORT DOCKET NO. 50-424- 1 DATE: DECEMBER'S I | |||
- COMPLETED BY: J.d.1989WILLIAMS' l TELEPHONE: (404) 826-4279 | |||
~0PERATING STATUS . | |||
l li UNIT NAME:- . | |||
VEGP UNIT 1 | |||
-2.' REPORT-PERIOD: | |||
NOVEMBER 89 | |||
: 3. LICENSED THERMAL POWER MWt : 3411 | |||
.4. NAMEPLATE RATING-(GROSS (MWe : 1148 | |||
: 5. DESIGN ELECTRICAL RATING (N T MWe): 1101- | |||
" 6.. MAXIMUM DEPENDABLE: CAPACITY (GROSS MWe): 1137 7.-MAXIMUM DEPENDABLE CAPACITY 1083 8.-IF CHANGES OCCUR INRATINGS CAPACITY (NET MWe): | |||
,(ITEMS 3 THROUGH 7) SINCF-LAST REPORT, GIVE REASONS: N/A l | |||
9.-POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWe): NO RESTRICTIONS | |||
: 10. REASONS FOR RESTRICTION, IF ANY:- N/A . | |||
THIS MONTH YR. TO DATE CUMULATIVE | |||
: 11. HOURS IN REPORTING PERIOD: . 720 8016 21937 12~. NUMBER OF HOURS REACTOR WAS CRITICAL: 720.0 7669.0 18544.1 < | |||
f | |||
-13. REACTOR RESERVE SHUTDOWN HOURS: 0.0 0. .0 | |||
: 14. HOURS-GENERATOR ON-LINE: 720.0 7533.1 18025.9 r | |||
: 15. UNIT RESERVE SHUTDOWN HOURS: 0.0~ 0 0= | |||
: 16. GROSS: THERMAL-ENERGY GENERATED MWH 2391716- 25022147 59453303 | |||
-17.-GROSS ELEC. ENERGY GENERATED (M H):): 805480 8300570- 19690640 | |||
: 18. NET ELEC.' ENERGY GENERATED-(MWH : 768940 7886420- 18598550 L 419. REACTOR SERVICE FACTOR 100.0% 95.7% 84.5% , | |||
h 20.~~ REACTOR AVAILABILITY FACTOR 100.0%- 95.7% 84.5%' ! | |||
L 21. UNIT-SERVICE FACTOR: 100.0% 94.0% 82.2%' | |||
l- -22. UNIT AVAILABILITY FACTOR: 100.0% 94.0% 82.2% > | |||
l= 23. UNIT CAPACITY FACTOR USING MDC NET): 98.6% 90.8% 78.3% | |||
: 24. UNIT CAPACITY FACTOR USING DER NET): 97.0% 89.4% 77.0% | |||
L25. UNIT-FORCED OUTAGE RA E: - 0.0% 6.0% 11.4% | |||
: 26. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH): , | |||
REFUELING -- FEB 23 -- 45 DAYS E 27..IF' SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: N/A y | |||
L V1-2 | |||
h | |||
{ ,- ,- | |||
> O'h ' | |||
UNIT 1 AVERAGE DAILY DOCKET NO. 50-424 POWER LEVEL DATE: DECEMBER 5 1989 COMPLETED BY: J.C.WILL}AMS TELEPHONE: (404) 826-4279 DAY Net MW j 1 ......... 1090 *- 'i 2 ......... 1096 | |||
* 3 ......... 1098 | |||
* 4 ......... 1099 | |||
* 5 ....,.... 1100.* | |||
6 ......... 1090 | |||
* 7 ......... 1087 | |||
* 8 ......... 1086 * ! | |||
9 ......... 1091 | |||
* 10 ......... 978 | |||
~11 ......... 760 j, 12 ......... 1037 -l' p 13 .....-.... 1095 | |||
* 14 ......... 1098 | |||
* 15 ......... 1091 | |||
* 16 .........= 1104 | |||
* L 17 . . . . . . . . . . 1113 | |||
* q 18 ......... ~1111 *: | |||
19 ......... '1106-* l 20 ......... 1105 | |||
* i 21 ......... 1102 | |||
* l 22 ......... 1109 | |||
* 23 ......... 1110 | |||
* i 24 ......... 1113 * : | |||
l-25.......... 1105 | |||
* H 26 ......... 1101 | |||
* 27 ......... 1101 * , | |||
28 ......... 947 . | |||
29 ......... 818 l l | |||
30 ......... 1097 | |||
* j L ! | |||
L 1 | |||
E | |||
* MDC CAN BE EXCEEDED UNDER OPTIMAL CONDITIONS ! | |||
1. | |||
f | |||
'h I | |||
I VI-3 i | |||
.V UNIT SHUTDOWNS AND POWER RED'JCTIONS DOCKET NO. 50-424 DATE: DECEMBER 5 1989 UNIT NAME: VEGP UNIT 1 COMPLETED BY: J.C. WILLIAMS ) | |||
TELEPHONE: (404) 826-4279 REPORT MONTH NOVEMBER 89 i | |||
'l- R M 5 ~j E E Y T A T LICENSEE SC . | |||
Y S H EVENT T 0- COMPONENT CAUSE & CORRECTIVE ! | |||
P DURATION 0 0 REPORT ED CODE ACTION TO ! | |||
-NO. DATE E (HOURS) N D NUMBER HE (SUBCODE) PREVENT RECURRENCE ! | |||
89-11 11/10 .S 0 A 5 N\A JK SIC SEE BELOW 89-12' 11/28 -S 0 .A. 5 N\A JK SIC SEE BELOW i | |||
l F: FORCED REASON: METHOD: EVENTS REPORTED INVOLVE i S: SCHEDULED 1 - MANUAL A GREATER THAN 20% , | |||
A-EQUIPMENT FAILURE B-MAINTENANCE OR-TEST (EXPLAIN) 2 - MANUAL SCRAM REDUCTION IN AVERAGE ! | |||
C-REFUELING 3 - AUTO. SCRAM DAILY. POWER LEVEL FOR ! | |||
D-REGULATORY RESTRICTION 4 - CONTINUATIONS THE PRECEDING 24 HOURS. ! | |||
E-0PERATOR TRAINING & LICENSE 5 - LOAD REDUCTION l F-ADMINISTRATIVE 9 - OTHER (EXPLAIN) , | |||
G-0PERATIONAL ERROR (EXPLAIN) | |||
H-0THER (EXPLAIN) 89-11 CAUSE: POWER REDUCTION DUE TO FAILED SPEED PICKUP # 2 ON MAIN FEEDPUMP "B". | |||
l CORRECTIVE ACTION: REPLACED SPEED PICKUP # 2 ON MAIN FEEDPUMP "B". | |||
89-12 CAUSE: POWER REDUCTION-DUE TO FAILED SPEED PICKUP # 1 ON MAIN FEEDPUMP "B". , | |||
-CORRECTIVE ACTION: REPLACED-SPEED PICKUP # 1 ON MAIN FEEDPUMP "B". i VI-4 L | |||
t ENCLOSURE 2 V0GTLE ELECTRIC OENERATING PLANT - UNIT 2 l MONTilLY OPERATING REPORT FOR NOVEMBER,1989 TABLE OF CONTENTS l i | |||
l NARRATIVE REPORT Page V2-1 OPERATING DATA REPORT Page V2-2 AVERAGE DAILY POWER LEVEL Page V2-3 UNIT SilVIDOWNS AND POWER REDUCTIONS Page V2-4 ; | |||
I i | |||
I o | |||
k l | |||
o | |||
.~ | |||
NARRATIVE REPORT DOCKET NO.- 50-425 UNIT 2 DATE: DECEMBER 5 1989 COMPLETED BY: J.C. WILLIAMS I TELEPHONE: (404)-826-4279 1 | |||
NOVEMBER 1 00:00 UNIT 2 AT 100% POWER WITH NO OPERATIONAL PROBLEMS. '1 | |||
. NOVEMBER 5 12:23 MANUAL REACTOR TRIP DUE TO LOSS OF MFP "A". UNIT STABILIZED AT MODE 3 NOVEMBER 5 23:27 . UNIT 2 ENTERS MODE 2. + | |||
NOVEMBER 6 00:16 UNIT 2 REACTOR CRITICAL. | |||
NOVEMBER 6- 03:51 UNIT-2 ENTERS MODE 1. : | |||
NOVEMBER 6 06:22 UNIT 2 TIED TO THE GRID. | |||
NOVEMBER 7. 06:33 UNIT 2-AT 100% POWER . | |||
NOVEMBER 20 11:38 POWER REDUCTION TO 95% FOR FEEDWATER HEATER AND HDT "B" MAINTENANCE. 1 | |||
' NOVEMBER 24 04:00 COMMENCE RAMP T0 FULL POWER. | |||
' NOVEMBER 24- 07:00 UNIT 2LAT 100% POWER. | |||
NOVEMBER 28 03:01 POWER REDUCTION TO 91% DUE TO HDT "B" HIGH LEVEL INDICATION. | |||
NOVEMBER 28 05:35 COMMENCE RAMP TO FULL POWER. | |||
1 NOVEMBER 28 17:48 UNIT 2 AT 100% POWER. | |||
NOVEMBER 30 23:59 UNIT 2 AT 100% POWER WITH.N0 OPERATIONAL PROBLEMS. | |||
t V2-1 l | |||
l | |||
+ | |||
a . | |||
OPERATING DATA REPORT DOCKET NO. LO-42! | |||
DATE: DECEM0ER 5 | |||
-COMPLETED BY: J.E.1989 WILLIAMS | |||
, OPERATING STATUS r | |||
: l. UNIT NAME:1 VEGP UNIT 2 1 | |||
: 2. REPORT PERIOD:' - . | |||
NOVEMBER 1989 3.-LICENSED THERMAL POWER (MWt): 3411 | |||
-40 NAMEPLATE RATING' 1148 | |||
-5. DESIGN ELECTRICAL RATING NET (GROSS MWe : MWe): 1101 6.3 MAXIMUM DEPENDABLE CAPACI Y GROS MWe): 1137 , | |||
: 7. MAXIMUM DEPENDABLE CAPACITY NET MWe 1083- f | |||
: 8. IF CHANGES OCCUR IN CAPACITY-RATINGS): 1 | |||
'(ITEMS 3 THROUGHf7) SINCE LAST REPORT, GIVE REASONS: .; | |||
: 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWe): No restrictions ! | |||
'10. REASONS FOR RESTRICTION, IF ANY: N/A THIS MONTH YR. TO DATE CUMULATIVE ; | |||
.11. HOURS IN REPORTING PERIOD: 720 4681- 4681- ! | |||
l 112.-NUMBER OF HOURS REACTOR WAS CRITICAL: '708.1 4489.9 .4489.9- - | |||
H | |||
: 13. REACTOR RESERVE SHUTDOWN. HOURS: 0.0 0.0 . | |||
0.0 .1 | |||
:14. HOURS-GENERATOR ON-LINE: 702.0- 4417.7 4417.7 ! | |||
15.l UNIT-RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0 ! | |||
: 16. GROSS THERMAL ENERGY' GENERATED H): 2350213 14871541 14871541 -i | |||
'17. GROSS ELEC. ENERGY GENERATED : 798539 5012780~ 5012780- ' | |||
l | |||
: 18. NET ELEC. ENERGY GENERATED'(M : 762059 4783630 4783630 i 1 | |||
-19. REACTOR SERVICE-FACTOR 98.3% 95.9% 95.9%' :! ' | |||
.20.TREACTOR AVAILABILITY FACTOR 98.3%' 95.9% 95.9%- | |||
21 ' UNIT! SERVICE FAC10R:- 97.5% 94.4%~ 94.4% ! | |||
= | |||
: 22. UNIT' AVAILABILITY FACTOR: 97.5% 94.4% 94.4% l | |||
'23.:. UNIT CAPACITY- FACTOR USING MDC NET : 97.7% 94.4% 94.4% =i | |||
: 24. UNIT CAPACITY FACTOR USING DER NET : 96,1%. 92.8% 92.8% i | |||
: 25. UNIT' FORCED OUTAGE RA E:: -. - | |||
~. 2.5% 2.4% 2.4%- | |||
L 26. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE DATE, AND DURATION OF EACH): | |||
L | |||
'27.IF.SHUTDOWNAT-ENDOFREPORTPERIOD,ESTIMATEDDdTEOFSTARTUP: | |||
N/A .i | |||
: l. ! | |||
, i l | |||
l l | |||
Li V2-2 | |||
O .j.T , | |||
- c. . . | |||
l | |||
. l | |||
) | |||
i UNIT 2 AVERAGE DAILY DOCKET NO. 50-425 l l POWER LEVEL DATE: DECEMBER 5 1989 COMPLETED BY: J.C. WILLIAMS TELEPHONE: (404) 826-4279 DAY Net MW l 1 ......... 1113 * ) | |||
2 ......... 1117 | |||
* 3 ......... 1119 * ; | |||
4 ......... 1121 * ! | |||
, 5 ......... 554 . | |||
it. ' | |||
6 ......... 430 ) | |||
7 ......... 1061 , | |||
8 ......... 1074 j 1088 * | |||
~ | |||
9 ......... | |||
10 ......... 1105 | |||
* 11 ......... 1103 | |||
* 12 ......... 1101 | |||
* 13 ......... 1104 | |||
* 14 ......... 1102 | |||
* 15 ......... 1093 | |||
* 16 ......... 1101 | |||
* 17 ......... 1123 | |||
* 1 18 ......... 1121 | |||
* 19 ......... 1121 | |||
* 20 ......... 1079 21 ......... 1042 22 ......... 1057 ; | |||
23 ......... 1057 24 ......... 1108 | |||
* 25 ......... 1122 | |||
* 26 ......... 1116 | |||
* 27 ......... 1114 | |||
* 2P ......... 1057 e 29 ......... 1122 + | |||
30 ......... 1124 * | |||
* MDC CAN BE EXCEEDED UNDER OPTIMAL CONDITIONS 3-V2-3 1 | |||
l | |||
o , | |||
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-425 DATE: DECEMBER 5 1989 VNIT NAME: VEGP UNIT 2 COMPLETED BY: J.C. WILLIAMS ; | |||
TELEPHONE: (404) 826-4279 i REPORT MONTH NOVEMBER 89 R M s E E Y T A T LICENSEE SC Y S H EVENT T0 COMPONENT CAUSE & CORRECT 10 P DURATION 0 0 REPORT ED CODE ACTION TO NO. DA1E E (HOURS) N D NUMBER HE (SUBCODE) PREVENT RECURRENCE 89-12 11/05 F 17.99 A 2 2-89-29 SJ LCV SEE BELOW I F: FORCED REASON: METHOD: EVENTS REPORTED INVOLVE S: SCHEDULED 1 - MANUAL A GREATER THAN 20% | |||
A-EQUIPMENT FAILURE (EXPLAIN) 2 - MANUAL SCRAM | |||
! B-MAINTENANCE OR TEST REDUCTION IN AVERAGE I | |||
C-REFUELING 3 - AUTO. SCRAM DAILY POWER LEVEL FOR D-REGULATORY RESTRICTION 4 - CONTINVATIONS THE PRECEDING 24 HOURS. | |||
E-0PERATOR TRAINING & LICENSE 5 - LOAD REDUCTION F-ADMINISTRATIVE 9 - OTHER (EXPLAIN) | |||
L G-OPERATIONAL ERROR (EXPLAIN) l H-0THER (EXPLAIN) 89-12 CAUSE: MANUAL REACTOR TRIP DVE TO LOW MAIN FEEDWATER PUMP SUCTION CAUSING MAIN FEEDWATER PUMP "A" TO TRIP. | |||
CORRECTIVE ACTION: DEFECTIVE 0-RING IN VALVE (2LV-4333 ACTUATOR WAS REMOVED AND REPLACED TO BRING VALVE TO FULL) OPERATIONA STATUS. | |||
1 i | |||
V2-4 | |||
._ _ .=. . . . __ . | |||
l i | |||
(ATTACHMENT 1) | |||
VEGP UNITS 1 & 2 DATE: DECEMBER 5. 1989 COMPLETED BY: J. C. WILLIAMS TELEPHONE: (404) 826-4279 : | |||
CHALLENGES TO PORV OR SAFETY VALVES L | |||
VT EY NP , | |||
DATE TAG NUMBER TE DESCRIPTION , | |||
l THERE WERE NO CHALLENGES TO PORY OR SAFETY VALVES. , | |||
4 EVENT TYPE : | |||
* A-AUTOMATIC M-MANUAL 4 - -_ ___ , ___ . . , . . . _. -- - r.}} |
Latest revision as of 12:00, 18 February 2020
ML19332G316 | |
Person / Time | |
---|---|
Site: | Vogtle ![]() |
Issue date: | 11/30/1989 |
From: | Mccoy C, Williams J GEORGIA POWER CO. |
To: | NRC |
References | |
ELV-01148, ELV-1148, NUDOCS 8912210051 | |
Download: ML19332G316 (12) | |
Text
R
' '1
- Georgia Power Company
< -N 40 invemess Conter Pcrkway
- - ' Post Offee Dox 1295
.?.
- Dirminghtm, Alibama 35201-
' Tdephone 205 877 7122
- c. K. uccoy -
Georgia b Power Vce PresKient, Nuclear Vogtle Prosect the souttern electrc System December 13, 1989 ELV-01148 0161 Docket Nos. 50-424 50-425' Director, Office of Resource Management U. S. Nuclear Regulatory Commission
' Washington, D. C. '20555 4
Gentlemen:
.V0GTLE ELECTRIC GENERATING PLANT MONTHLY OPERATING REPORTS Enclosed are the November,1989 monthly operating reports for Vogtle Units 1 and
- 2. 'These reports are submitted in accordance with Technical Specification 6.8.1.5.
Sincerely, C. K. McCoy CKM/NJS/gm Enclosures xc: Georaia Power Company i Mr. C. K. McCoy 1 Mr. G. Bockhold, Jr. I
-Mr. P..D. Rushton Mr. R. M. Odom NORMS'
~U. S. Nuclear Reaulatory Commission !
, Mr. S. D. Ebneter, Regional Administrator ;
Mr. J. B. Hopkins, Licensing Project Manager, NRR i Mr. J. F. Rogge, Senior Resident Inspector, Vogtle Document Control Desk U
8912210051 891130
+PDR ADOCK 05000424 .
iR PDC ,
)
r.--.
<4; : c.
[
ENCLOSURE 1 V0GTLE ELECTRIC GENERATING PLANT - UNIT 1 MONTilLY OPERATING REPORT FOR NOVEMBER, 1989 TABLE OF CONTENTS NARRATIVE. REPORT Page Vl-1 OPERATING DATA REPORT Page Vl-2 AVERAGE DAILY POWER LEVEL Page VI-3 UNIT SiluTDOWNS AND POWER' REDUCTIONS Page VI-4
.l i
l l
l~
3 i
- n..
, 8 NARRATIVE REPORT DOCKET NO. 50-424 UNIT 1 DATE: DECEMBER 5 1989 COMPLETEDBY:'J.C.WILL}AMS TELEPHONE: (404) 826-4279 NOVEMBER 1 00:00 -UNIT 1 AT 100% POWER WITH NO OPERATIONAL PROBLEMS.
. NOVEMBER 10 08:20 POWER REDUCTION TO 90% DUE TO FAILED MFP "B" SPEED PICKUP # 2.
. NOVEMBER 10. 19:54 POWER REDUCTION TO 72% TO REPLACE MFP "B" SPEED PICKUP # 2.
' NOVEMBER 12 00:30 COMMENCE RAMP TO FULL POWER. l
' NOVEMBER 12 14:00 UNIT 1 AT FULL POWER.
NOVEMBER 28 12:38 POWER REDUCTION TO 70% TO REPLACE MFP "B" SPEED PICKUP # 1.
NOVEMBER'29 18:04 COMMENCE RAMP TO FULL POWER.
NOVEMBER 30 03:00 UNIT 1 AT 100% POWER.
. NOVEMBER 30 23:59 UNIT 1 AT 100% POWER WITH NO OPERATIONAL PROBLEMS, L i l
l l
1 l
Vl-1
T .;
s'y 1', _ . l n ._ .
t 1 l
OPERATING DATA REPORT DOCKET NO. 50-424- 1 DATE: DECEMBER'S I
- COMPLETED BY: J.d.1989WILLIAMS' l TELEPHONE: (404) 826-4279
~0PERATING STATUS .
l li UNIT NAME:- .
VEGP UNIT 1
-2.' REPORT-PERIOD:
NOVEMBER 89
- 3. LICENSED THERMAL POWER MWt : 3411
.4. NAMEPLATE RATING-(GROSS (MWe : 1148
- 5. DESIGN ELECTRICAL RATING (N T MWe): 1101-
" 6.. MAXIMUM DEPENDABLE: CAPACITY (GROSS MWe): 1137 7.-MAXIMUM DEPENDABLE CAPACITY 1083 8.-IF CHANGES OCCUR INRATINGS CAPACITY (NET MWe):
,(ITEMS 3 THROUGH 7) SINCF-LAST REPORT, GIVE REASONS: N/A l
9.-POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWe): NO RESTRICTIONS
- 10. REASONS FOR RESTRICTION, IF ANY:- N/A .
THIS MONTH YR. TO DATE CUMULATIVE
- 11. HOURS IN REPORTING PERIOD: . 720 8016 21937 12~. NUMBER OF HOURS REACTOR WAS CRITICAL: 720.0 7669.0 18544.1 <
f
-13. REACTOR RESERVE SHUTDOWN HOURS: 0.0 0. .0
- 14. HOURS-GENERATOR ON-LINE: 720.0 7533.1 18025.9 r
- 15. UNIT RESERVE SHUTDOWN HOURS: 0.0~ 0 0=
- 16. GROSS: THERMAL-ENERGY GENERATED MWH 2391716- 25022147 59453303
-17.-GROSS ELEC. ENERGY GENERATED (M H):): 805480 8300570- 19690640
- 18. NET ELEC.' ENERGY GENERATED-(MWH : 768940 7886420- 18598550 L 419. REACTOR SERVICE FACTOR 100.0% 95.7% 84.5% ,
h 20.~~ REACTOR AVAILABILITY FACTOR 100.0%- 95.7% 84.5%' !
L 21. UNIT-SERVICE FACTOR: 100.0% 94.0% 82.2%'
l- -22. UNIT AVAILABILITY FACTOR: 100.0% 94.0% 82.2% >
l= 23. UNIT CAPACITY FACTOR USING MDC NET): 98.6% 90.8% 78.3%
- 24. UNIT CAPACITY FACTOR USING DER NET): 97.0% 89.4% 77.0%
L25. UNIT-FORCED OUTAGE RA E: - 0.0% 6.0% 11.4%
- 26. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH): ,
REFUELING -- FEB 23 -- 45 DAYS E 27..IF' SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: N/A y
L V1-2
h
{ ,- ,-
> O'h '
UNIT 1 AVERAGE DAILY DOCKET NO. 50-424 POWER LEVEL DATE: DECEMBER 5 1989 COMPLETED BY: J.C.WILL}AMS TELEPHONE: (404) 826-4279 DAY Net MW j 1 ......... 1090 *- 'i 2 ......... 1096
- 3 ......... 1098
- 4 ......... 1099
- 5 ....,.... 1100.*
6 ......... 1090
- 7 ......... 1087
- 8 ......... 1086 * !
9 ......... 1091
- 10 ......... 978
~11 ......... 760 j, 12 ......... 1037 -l' p 13 .....-.... 1095
- 14 ......... 1098
- 15 ......... 1091
- 16 .........= 1104
- L 17 . . . . . . . . . . 1113
- q 18 ......... ~1111 *:
19 ......... '1106-* l 20 ......... 1105
- i 21 ......... 1102
- l 22 ......... 1109
- 23 ......... 1110
- i 24 ......... 1113 * :
l-25.......... 1105
- H 26 ......... 1101
- 27 ......... 1101 * ,
28 ......... 947 .
29 ......... 818 l l
30 ......... 1097
- j L !
L 1
E
1.
f
'h I
I VI-3 i
.V UNIT SHUTDOWNS AND POWER RED'JCTIONS DOCKET NO. 50-424 DATE: DECEMBER 5 1989 UNIT NAME: VEGP UNIT 1 COMPLETED BY: J.C. WILLIAMS )
TELEPHONE: (404) 826-4279 REPORT MONTH NOVEMBER 89 i
'l- R M 5 ~j E E Y T A T LICENSEE SC .
Y S H EVENT T 0- COMPONENT CAUSE & CORRECTIVE !
P DURATION 0 0 REPORT ED CODE ACTION TO !
-NO. DATE E (HOURS) N D NUMBER HE (SUBCODE) PREVENT RECURRENCE !
89-11 11/10 .S 0 A 5 N\A JK SIC SEE BELOW 89-12' 11/28 -S 0 .A. 5 N\A JK SIC SEE BELOW i
l F: FORCED REASON: METHOD: EVENTS REPORTED INVOLVE i S: SCHEDULED 1 - MANUAL A GREATER THAN 20% ,
A-EQUIPMENT FAILURE B-MAINTENANCE OR-TEST (EXPLAIN) 2 - MANUAL SCRAM REDUCTION IN AVERAGE !
C-REFUELING 3 - AUTO. SCRAM DAILY. POWER LEVEL FOR !
D-REGULATORY RESTRICTION 4 - CONTINUATIONS THE PRECEDING 24 HOURS. !
E-0PERATOR TRAINING & LICENSE 5 - LOAD REDUCTION l F-ADMINISTRATIVE 9 - OTHER (EXPLAIN) ,
G-0PERATIONAL ERROR (EXPLAIN)
H-0THER (EXPLAIN) 89-11 CAUSE: POWER REDUCTION DUE TO FAILED SPEED PICKUP # 2 ON MAIN FEEDPUMP "B".
l CORRECTIVE ACTION: REPLACED SPEED PICKUP # 2 ON MAIN FEEDPUMP "B".
89-12 CAUSE: POWER REDUCTION-DUE TO FAILED SPEED PICKUP # 1 ON MAIN FEEDPUMP "B". ,
-CORRECTIVE ACTION: REPLACED-SPEED PICKUP # 1 ON MAIN FEEDPUMP "B". i VI-4 L
t ENCLOSURE 2 V0GTLE ELECTRIC OENERATING PLANT - UNIT 2 l MONTilLY OPERATING REPORT FOR NOVEMBER,1989 TABLE OF CONTENTS l i
l NARRATIVE REPORT Page V2-1 OPERATING DATA REPORT Page V2-2 AVERAGE DAILY POWER LEVEL Page V2-3 UNIT SilVIDOWNS AND POWER REDUCTIONS Page V2-4 ;
I i
I o
k l
o
.~
NARRATIVE REPORT DOCKET NO.- 50-425 UNIT 2 DATE: DECEMBER 5 1989 COMPLETED BY: J.C. WILLIAMS I TELEPHONE: (404)-826-4279 1
NOVEMBER 1 00:00 UNIT 2 AT 100% POWER WITH NO OPERATIONAL PROBLEMS. '1
. NOVEMBER 5 12:23 MANUAL REACTOR TRIP DUE TO LOSS OF MFP "A". UNIT STABILIZED AT MODE 3 NOVEMBER 5 23:27 . UNIT 2 ENTERS MODE 2. +
NOVEMBER 6 00:16 UNIT 2 REACTOR CRITICAL.
NOVEMBER 6- 03:51 UNIT-2 ENTERS MODE 1. :
NOVEMBER 6 06:22 UNIT 2 TIED TO THE GRID.
NOVEMBER 7. 06:33 UNIT 2-AT 100% POWER .
NOVEMBER 20 11:38 POWER REDUCTION TO 95% FOR FEEDWATER HEATER AND HDT "B" MAINTENANCE. 1
' NOVEMBER 24 04:00 COMMENCE RAMP T0 FULL POWER.
' NOVEMBER 24- 07:00 UNIT 2LAT 100% POWER.
NOVEMBER 28 03:01 POWER REDUCTION TO 91% DUE TO HDT "B" HIGH LEVEL INDICATION.
NOVEMBER 28 05:35 COMMENCE RAMP TO FULL POWER.
1 NOVEMBER 28 17:48 UNIT 2 AT 100% POWER.
NOVEMBER 30 23:59 UNIT 2 AT 100% POWER WITH.N0 OPERATIONAL PROBLEMS.
t V2-1 l
l
+
a .
OPERATING DATA REPORT DOCKET NO. LO-42!
DATE: DECEM0ER 5
-COMPLETED BY: J.E.1989 WILLIAMS
, OPERATING STATUS r
- l. UNIT NAME:1 VEGP UNIT 2 1
- 2. REPORT PERIOD:' - .
NOVEMBER 1989 3.-LICENSED THERMAL POWER (MWt): 3411
-40 NAMEPLATE RATING' 1148
-5. DESIGN ELECTRICAL RATING NET (GROSS MWe : MWe): 1101 6.3 MAXIMUM DEPENDABLE CAPACI Y GROS MWe): 1137 ,
- 7. MAXIMUM DEPENDABLE CAPACITY NET MWe 1083- f
- 8. IF CHANGES OCCUR IN CAPACITY-RATINGS): 1
'(ITEMS 3 THROUGHf7) SINCE LAST REPORT, GIVE REASONS: .;
- 9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWe): No restrictions !
'10. REASONS FOR RESTRICTION, IF ANY: N/A THIS MONTH YR. TO DATE CUMULATIVE ;
.11. HOURS IN REPORTING PERIOD: 720 4681- 4681- !
l 112.-NUMBER OF HOURS REACTOR WAS CRITICAL: '708.1 4489.9 .4489.9- -
H
- 13. REACTOR RESERVE SHUTDOWN. HOURS: 0.0 0.0 .
0.0 .1
- 14. HOURS-GENERATOR ON-LINE: 702.0- 4417.7 4417.7 !
15.l UNIT-RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0 !
- 16. GROSS THERMAL ENERGY' GENERATED H): 2350213 14871541 14871541 -i
'17. GROSS ELEC. ENERGY GENERATED : 798539 5012780~ 5012780- '
l
- 18. NET ELEC. ENERGY GENERATED'(M : 762059 4783630 4783630 i 1
-19. REACTOR SERVICE-FACTOR 98.3% 95.9% 95.9%' :! '
.20.TREACTOR AVAILABILITY FACTOR 98.3%' 95.9% 95.9%-
21 ' UNIT! SERVICE FAC10R:- 97.5% 94.4%~ 94.4% !
=
- 22. UNIT' AVAILABILITY FACTOR: 97.5% 94.4% 94.4% l
'23.:. UNIT CAPACITY- FACTOR USING MDC NET : 97.7% 94.4% 94.4% =i
- 24. UNIT CAPACITY FACTOR USING DER NET : 96,1%. 92.8% 92.8% i
- 25. UNIT' FORCED OUTAGE RA E:: -. -
~. 2.5% 2.4% 2.4%-
L 26. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE DATE, AND DURATION OF EACH):
L
'27.IF.SHUTDOWNAT-ENDOFREPORTPERIOD,ESTIMATEDDdTEOFSTARTUP:
N/A .i
- l. !
, i l
l l
Li V2-2
O .j.T ,
- c. . .
l
. l
)
i UNIT 2 AVERAGE DAILY DOCKET NO. 50-425 l l POWER LEVEL DATE: DECEMBER 5 1989 COMPLETED BY: J.C. WILLIAMS TELEPHONE: (404) 826-4279 DAY Net MW l 1 ......... 1113 * )
2 ......... 1117
- 3 ......... 1119 * ;
4 ......... 1121 * !
, 5 ......... 554 .
it. '
6 ......... 430 )
7 ......... 1061 ,
8 ......... 1074 j 1088 *
~
9 .........
10 ......... 1105
- 11 ......... 1103
- 12 ......... 1101
- 13 ......... 1104
- 14 ......... 1102
- 15 ......... 1093
- 16 ......... 1101
- 17 ......... 1123
- 1 18 ......... 1121
- 19 ......... 1121
- 20 ......... 1079 21 ......... 1042 22 ......... 1057 ;
23 ......... 1057 24 ......... 1108
- 25 ......... 1122
- 26 ......... 1116
- 27 ......... 1114
- 2P ......... 1057 e 29 ......... 1122 +
30 ......... 1124 *
l
o ,
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-425 DATE: DECEMBER 5 1989 VNIT NAME: VEGP UNIT 2 COMPLETED BY: J.C. WILLIAMS ;
TELEPHONE: (404) 826-4279 i REPORT MONTH NOVEMBER 89 R M s E E Y T A T LICENSEE SC Y S H EVENT T0 COMPONENT CAUSE & CORRECT 10 P DURATION 0 0 REPORT ED CODE ACTION TO NO. DA1E E (HOURS) N D NUMBER HE (SUBCODE) PREVENT RECURRENCE 89-12 11/05 F 17.99 A 2 2-89-29 SJ LCV SEE BELOW I F: FORCED REASON: METHOD: EVENTS REPORTED INVOLVE S: SCHEDULED 1 - MANUAL A GREATER THAN 20%
A-EQUIPMENT FAILURE (EXPLAIN) 2 - MANUAL SCRAM
! B-MAINTENANCE OR TEST REDUCTION IN AVERAGE I
C-REFUELING 3 - AUTO. SCRAM DAILY POWER LEVEL FOR D-REGULATORY RESTRICTION 4 - CONTINVATIONS THE PRECEDING 24 HOURS.
E-0PERATOR TRAINING & LICENSE 5 - LOAD REDUCTION F-ADMINISTRATIVE 9 - OTHER (EXPLAIN)
L G-OPERATIONAL ERROR (EXPLAIN) l H-0THER (EXPLAIN) 89-12 CAUSE: MANUAL REACTOR TRIP DVE TO LOW MAIN FEEDWATER PUMP SUCTION CAUSING MAIN FEEDWATER PUMP "A" TO TRIP.
CORRECTIVE ACTION: DEFECTIVE 0-RING IN VALVE (2LV-4333 ACTUATOR WAS REMOVED AND REPLACED TO BRING VALVE TO FULL) OPERATIONA STATUS.
1 i
V2-4
._ _ .=. . . . __ .
l i
(ATTACHMENT 1)
VEGP UNITS 1 & 2 DATE: DECEMBER 5. 1989 COMPLETED BY: J. C. WILLIAMS TELEPHONE: (404) 826-4279 :
CHALLENGES TO PORV OR SAFETY VALVES L
VT EY NP ,
DATE TAG NUMBER TE DESCRIPTION ,
l THERE WERE NO CHALLENGES TO PORY OR SAFETY VALVES. ,
4 EVENT TYPE :
- A-AUTOMATIC M-MANUAL 4 - -_ ___ , ___ . . , . . . _. -- - r.