ML20100R270

From kanterella
Jump to navigation Jump to search
Monthly Operating Repts for Feb 1995 for Vogtle Electric Generating Plant
ML20100R270
Person / Time
Site: Vogtle  
Issue date: 02/29/1996
From: Hooper G, Mccoy C
GEORGIA POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LCV-0757-B, LCV-757-B, NUDOCS 9603120336
Download: ML20100R270 (11)


Text

..y Georgia Power Company I

40 inverness Center Parkway

+

Post Omca Box 1295 Birmongham, Alabama 35201 Telephone 205 877 7122 C.K.M Coy Georgia Power Vce Pre dent. Nuclear Vogtfe Vs nect the southem eiectnc system March 8, 1996 LCV-0757-B Docket Nos. 50-424 50-425 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555 Gentlemen:

VOGTLE ELECTRIC GENERATING PLANT

- MONTHLY OPERATING REPORT Enclosed are the February 1996, monthly operating reports for Vogtle Electric Generating Plant (VEGP) Units 1 and 2. These reports are submitted in accordance with Technical Specification 6.8.1.5.

Sincerely, j

l C. K. McCoy i

CKM/JLL Enclosures cc:

Georgia Power Company Mr. J. B. Beasley, Jr.

Mr. M. Sheibani NORMS U. S. Nuclear Regula.tgry Commission Mr. S. D. Ebneter, Regional Administrator Mr. L. L. Wheeler, Licensing Project Manager, NRR Mr. C. R. Ogle, Senior Resident inspector, Vogtle 1

[I 9603120336 960229 l

PDR ADOCK O$000424 L

i g

PDR

)

O o

ENCLOSURE 1 e

VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 MONTHLY OPERATING REPORT FOR FEBRUARY 1996 TABLE OF CONTENTS NARRATIVE REPORT Page Vl-1 OPERATING DATA REPORT Page Vl-2 AVERAGE DAILY POWER LEVEL Page Vl-3 UNIT SHUTDOWNS AND POWER REDUCTIONS Page VI-4 j

a M

E

r NARRA flVE REPORT DOCKET NO. 50-424 UNIT 1 DATE:

MARCH 1,1996 COMPLETED BY: G. L. HOOPER TELEPHONE:

(706) 826-4104 FEBRUARY 01 00:00 UNIT 1 AT 100% POWER WITH NO OPERATIONAL PROBLEMS.

FEBRUARY 06 12:00 UNIT 1 BEGAN DERATE TO 43% POWER TO REPAIR MAIN GENERATOR RECTIFIER COOLING LEAK.

FEBRUARY 09 22:00 UNIT 1 RETURNED TO 100% POWER.

FEBRUARY 14 08:38 UNIT 1 BEGAN COASTDOWN FOR REFUELING OUTAGE.

FEBRUARY 29 23:59 UNIT 1 AT 81% POWER COASTDOWN IN PROGRESS.

I i

V1-1

~

l

\\

l OPERATING DATA REPORT DOCKET NO. 50-424 DATE:

MARCH 1,1996 COMPLETED BY: G. L. HOOPER TELEPHONE:

(706) 826-4104 OPERATING STATUS

1. UNIT NAME:

VEGP UNIT 1

2. REPORT PERIOD:

FEBRUARY 1996

3. LICENSED THERMAL POWER (MWt):

3565

4. NAMEPLATE RATING (GROSS MWe):

1215

5. DESIGN ELECTRICAL RATING (NET MWe):

1169

6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWe):

1216

7. MAXIMUM DEPENDABLE CAPACITY (NET MWe):

1162

8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS:

NA

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWe):

NO RESTRICTIONS

10. REASONS FOR RESTRICTION, IF ANY:

NA 4

THIS MONTH YR. TO DATE CUMULATIVE

11. HOURS IN REPORTING PERIOD:

696 1440 76705

12. NUMBER OF HOURS REACTOR WAS CRITICAL:

696.0 1440.0 67906.2

13. REACTOR RESERVE SHUTDOWN HOURS:

0.0 0.0 0.0 l

14. HOURS GENERATOR ON-LINE:

696.0-1440.0 66782.4

15. UNIT RESERVE SHUTDOWN HOURS:

0.0 0.0 0.0

16. GROSS THERMAL ENERGY GENERATED (MWH):

2255312 4905920 226307654

17. GROSS ELEC. ENERGY GENERATED (MWH):

773677 1690725 76363252

18. NET ELEC. ENERGY GENERATED (MWH):

738117 1616035 72658442

19. REACTOR SERVICE FACTOR 100.0 %

100.0 %

88.5 %

20. REACTOR AVAILABILITY FACTOR 100.0 %

100.0%

88.5 %

21. UNIT SERVICE FACTOR:

100.0 %

100.0 %

87.1 %

22. UNIT AVAILABILITY FACTOR:

100.0 %

100.0 %

87.1 %

23. UNIT CAPACITY FACTOR (USING MDC NET):

91.3 %

96.6 %

85.1 %

24. UNIT CAPACITY FACTOR (USING DER NET):

90.7 %

96.0 %

84.4 %

25. UNIT FORCED OUTAGE RATE:

0.0%

0.0%

4.3%

26. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):

REFUELING,03/03/96,31 DAYS

27. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:

NA V1-2

UNIT 1 - AVERAGE DAILY DOCKET NO. 50-424 POWER LEVEL DATE:

MARCH 1,1996 COMPLETED BY: G. L. HOOPER TELEPHONE:

(706) 826-4104 DAY Net MW 1...........

1181

  • 2.

1181

  • l 3.................

1185

  • 4....................

1184

  • l 5......

1184

  • l l

6.................

1049 1

i 7.....................

484 i

8................

729 I

9.................

1131 10................

1176

  • 11.....................

1172

  • 12...

1182

  • 13..................

1182

  • 14...................

1163

  • 15................

1138 16...

1132 17...................

1115 18..............

1100 l

i l

19...............

1082 20..................

1071 21.................

1053 22...

1042 23...............

1021 24.......

1012 25...................

995 26......

976 l

27................

958 28.....................

936 29.

943 t

l r

l l

l

[

f

  • MDC CAN BE EXCEEDED UNDER OPTIMAL CONDITIONS

[

J i

o l

j V1-3 1

i

~

n s.

o

~

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-424 DATE:

MARCH 1,1996 UNIT NAME:

VEGP UNIT 1 COMPLETED BY: G. L. HOOPER TELEPHONE:

(706) 826-4104 REPORT MONTH FEBRUARY 1996 R

M S

E E

Y T

A T

LICENSEE SC Y

S H

EVENT TO COMPONENT CAUSE & CORRECTIVE P

DURATION O

O REPORT ED CODE ACTION TO NO.

DATE E

(HOURS)

N D

NUMBER ME (SUBCODE)

PREVENT RECURRENCE 96-1 2/6 S

0.0 B

5 NA TJ PSF SEE BELOW F: FORCED REASON:

METHOD:

EVENTS REPORTED INVOLVE S: SCHEDULED A-EQUIPMENT FAILURE (EXPLAIN) 1 - MANUAL A GREATER THAN 20%

B-MAINTENANCE OR TEST 2 - MANUAL SCRAM REDUCTION IN AVERAGE C-REFUELING 3 - AUTO. SCRAM DAILY POWER LEVEL FOR D-REGULATORY RESTRICTION 4 - CONTINUATIONS THE PRECEDING 24 HOURS.

E-OPERATOR TRAINING & LICENSE 5 - LOAD REDUCTION F-ADMINISTRATIVE 9 - OTHER (EXPLAIN)

G-OPERATIONAL ERROR (EXPLAIN)

H-OTHER (EXPLAIN)

EVENT 96-1 CAUSE: UNIT DERATED TO REPAIR LEAK IN GENERATOR RECTIFIER COOLING SYSTEM.

COBRECTIVE ACTION: LEAK WAS REPAIRED AND UNIT WAS RETURNED TO 100% POWER.

V1-4

ENCLOSURE 2 VOGTLE ELECTRIC GENERATING PLANT - UNIT 2 MONTHLY OPERATING REPORT FOR FEBRUARY 1996 TABLE OF CONTENTS NARRATIVE REPORT Page V2-1 OPERATING DATA REPORT Page V2-2 AVERAGE DAILY POWER LEVEL Page V2-3 UNIT SHUTDOWNS AND POWER REDUCTIONS Page V2-4

a NARRATIVE REPORT DOCKET NO. 50-425 UNIT 2 DATE:

MARCH 1,1996 COMPLETED BY: G. L. HOOPER TELEPHONE:

(706)826-4104 FEBRUARY 01 00:00 UNIT 2 AT 100% POWER WITH NO OPERATIONAL PROBLEMS.

FEBRUARY 29 23:59 UNIT 2 AT 100% POWER WITH NO OPERATIONAL PROBLEMS, i

i V21

r OPERATING DATA REPORT DOCKET NO. 50-425 DATE:

MARCH 1,1996 COMPLETED BY: G. L. HOOPER TELEPHONE:

(706) 826-4104 OPERATING STATUS

1. UNIT NAME:

VEGP UNIT 2

2. REPORT PERIOD:

FEBRUARY 1996

3. LICENSED THERMAL POWER (MWt):

3565 j

4. NAMEPLATE RATING (GROSS MWe):

1215

5. DESIGN ELECTRICAL RATING (NET MWe):

1169

6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWe):

1216

7. MAXIMUM DEPENDABLE CAPACITY (NET MWe):

1162

8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS:

NA

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWe):

NO RESTRICTIONS

10. REASONS FOR RESTRICTION,IF ANY:

NA THIS MONTH YR. TO DATE CUMULATIVE

11. HOURS IN REPORTING PERIOD:

696 1440 59449

12. NUMBER OF HOURS REACTOR WAS CRITICAL:

696.0 1440.0 53556.5

13. REACTOR RESERVE SHUTDOWN HOURS:

0.0 0.0 0.0

14. HOURS GENERATOR ON-LINE:

696.0 1440.0 52939.5

15. UNIT RESERVE SHUTDOWN HOURS:

0.0 0.0 0.0

16. GROSS THERMAL ENERGY GENERATED (MWH):

2479725 5130559 178584674

17. GROSS ELEC. ENERGY GENERATED (MWH):

861955 1785289 60808591

18. NET ELEC. ENERGY GENERATED (MWH):

825565 1711049 57949311

19. REACTOR SERVICE FACTOR 100.0 %

100.0 %

90.1 %

20. REACTOR AVAILABILITY FACTOR 100.0 %

100.0 %

90.1 %

21. UNIT SERVICE FACTOR:

100.0 %

100.0 %

89.1 %

22. UNIT AVAILABILITY FACTOR:

100.0 %

100.0 %

89.1 %

23. UNIT CAPACITY FACTOR (USING MDC NET):

102.1 %

102.3 %

86.5 %

24. UNIT CAPACITY FACTOR (USING DER NET):

101.5 %

101.6 %

86.4 %

25. UNIT FORCED OUTAGE RATE:

0.0%

0.0%

1.9%

26. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):

NONE

27. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP :

NA V2-2 i

-... ~.

c UNIT 2 AVERAGE DAILY DOCKET NO. 50-425 POWER LEVEL DATE:

MARCH 1,1996 COMPLETED BY: G. L. HOOPER TELEPHONE:

(706) 826-4104 DAY Net MW 1..................

1193

  • 2..

1194

  • 3................

1196

  • 4..................

1195

  • 5...............

1196

  • 6..................

1195

  • 7...................

1196

  • 8..

1189

  • 9......................

1184

  • 10.................

1187

  • 11...........

1183

  • 12.................

1192

  • 1 13...............

1193

  • 14.................

1188

  • i 15................

1184

  • 16..................

1193

  • 17..

1193

  • 18....................

1191

  • 19..............

1188

  • 20...................

1183

  • 21......................

1183

  • 22......................

1180

  • 23.................

1176

  • 24..................

1167

  • j 25.............

1184 *

26...

1174

  • i 27................

1173

  • 28...............

1169

  • 2 9..............

1183 *

  • MDC CAN BE EXCEEDED UNDER OPTIMAL CONDITIONS V2-3

l 3

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-425 DATE:

MARCH 1,1996 UNIT NAME:

VEGP UNIT 2 COMPLETED BY: G. L. HOOPER TELEPHONE:

(706) 826-4104 REPORT MONTH FEBRUARY 1996 R

M S

I E

E Y

T A

T LICENSEE SC l

Y S

H EVENT TO COMPONENT CAUSE & CORRECTIVE P

DURATION O

O REPORT ED CODE ACTION TO NO.

DATE E

(HOURS)

N D

NUMBER ME (SUBCODE)

PREVENT RECURRENCE 1

l NA NA NA NA NA NA NA NA NA NA l

F: FORCED REASON:

METHOD:

EVENTS REPORTED INVOLVE l

S: SCHEDULED A-EQUIPMENT FAILURE (EXPLAIN) 1 - MANUAL A GREATER THAN 20%

l B-MAINTENANCE OR TEST 2 - MANUAL SCRAM REDUCTION IN AVERAGE C-REFUELING 3 - AUTO. SCRAM DAILY POWER LEVEL FOR D-REGULATORY RESTRICTION 4 - CONTINUATIONS THE PRECEDING 24 HOURS.

E-OPERATOR TRAINING & LICENSE 5 - LOAD REDUCTION i

F-ADMINISTRATIVE 9 - OTHER (EXPLAIN) l G-OPERATIONAL ERROR (EXPLAIN)

H-OTHER (EXPLAIN) l i

I 1

4 3

i V2-4 I

, '., t, ENCLOSURE 3 VOGTLE ELECTRIC GENERATING PLANT-UNITS 1 AND 2 CIIALLENGES TO PORY OR SAFETY VALVES l

DOCKET NOS. 50-424,50-425 DATE:

MARCH 1,1996 COMPLETED BY: G. L. HOOPER TELEPHONE:

(706) 826-4104 EVENT DATE TAG NO.

TYPE DESCRIPTION NA NA NA NA w

-.