| title = Forwards Response to IE Bulletin 80-17,Suppl 3, Failure of 76 of 185 Control Rods to Fully Insert During Scram at Bwr. Procedure at Dresden 2 & 3 Changed to Require Immediate Manual Scram When Air Pressure Reaches 60 Psi
| title = Forwards Response to IE Bulletin 80-17,Suppl 3, Failure of 76 of 185 Control Rods to Fully Insert During Scram at Bwr. Procedure at Dresden 2 & 3 Changed to Require Immediate Manual Scram When Air Pressure Reaches 60 Psi
| author name = RAUSCH T J
| author name = Rausch T
| author affiliation = COMMONWEALTH EDISON CO.
| author affiliation = COMMONWEALTH EDISON CO.
| addressee name = KEPPLER J G
| addressee name = Keppler J
| addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
| addressee affiliation = NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
| docket = 05000010, 05000237, 05000249, 05000254, 05000265
| docket = 05000010, 05000237, 05000249, 05000254, 05000265
Line 16: Line 16:


=Text=
=Text=
{{#Wiki_filter:Commonwealth Edison One First'onal Plaza, Chicago, illinois Address fy to: Post Office Box 767 Chicago, fotnois 60690 7/w September 2, 1980 Mr.Dames G.Keppler, Director''Di.rectorate of Inspection and Enforcement
{{#Wiki_filter:Commonwealth Edison One First   'onal Plaza, Chicago, illinois 7/w Address       fy to: Post Office Box 767 Chicago, fotnois 60690 September 2, 1980
-Region III U.S.Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137  
'' Mr. Dames G.         Keppler, Director Di.rectorate         of Inspection and Enforcement Region U.S. Nuclear Regulatory Commission III 799 Roosevelt Road Glen Ellyn, IL             60137


==Subject:==
==Subject:==
Dresden Station Units 2 and 2 Quad Cities Station Units 1 and 2 Response t o I E Bulletin 80-17 Supplement 3"Failure of Control Rods to Insert During a Scram at a BWRn NRC Docket Nos.50-10/237/249 and 50-254/265 Reference (a): 3.G.Keppler letter to C.Reed dated August 22, 1980  
Dresden       Station Units 2 and 2 Quad     Cities Station Units 1 and 2 Response t o I E Bulletin 80-17 Supplement 3 "Failure of Control Rods to Insert During       a   Scram       at a BWRn NRC     Docket Nos. 50-10/237/249 and 50-254/265 Reference           (a):       3. G. Keppler letter to C. Reed dated August 22, 1980


==Dear Mr.Keppler:==
==Dear Mr. Keppler:==
Reference (a)transmitted IE Bulletin 80-17 Supplement 3 requesting a response to concerns identified with a postulated loss of the control rod drive'control air systems.The Commonwealth Edison Company responses for Dresden Units 2 and 3 and Quad Cities Units 1 and 2 are provided in the enclosure to this letter.~r 1 I 8009sao/0P 0~" V Commonwealth Edison Mr.Dames G.Keppler, Director September 2, 1980 Page 2 Please address any questions you may have in this regard to this office.Approximately 80 man-hours were expended in the review and preparation of this report, 24 of which were for corrective actions.Very truly yours, Attachment Thomas 3.Rausch Nuclear Licensing Administrator Special Projects cc: Director, Division of Reactor Operations Inspection NRC Office of Inspection and Enforcement Washington, DC 20555 SUBCRIBED and SWOR to befor.me this day of 1980 Nota ub lie Enclosure Commonwealth Edison Com an Res onse to IE Bulletin 80-17 Su lement 3 The subject bulletin has been reviewed at the stations, and the following responses are provided: Dresden Units 2 and 3 Item l.a.The appropriate procedure has been changed to require an immediate manual scram when air pressue reaches 60 psi.The pressure required to open the scram outlet valves is 50 psi.Item l.b.(1)The appropriate procedure has been changed to require an immediate manual scram when three rods have drifted.Item l.b.(2)The temperature recorder used for the CRD high temperature alarm is located on the back panel in the control room.The recorder is a combination electrical-mechanical type that takes approximately 13 minutes to scan all the drives.The recorder and front panel alarms must be reset after each high temperature condition is detected on every scram.The recorder was installed for long-term monitoring of the CRD's, which is used for planning maintenance on the drives at the end of each cycle.It was not designed with the intent to provide rapid indication of multiple CRD high temperatures which may suddenly appear.Based on the above reasons, Dresden is not implementing an immediate manual scram, based solely on a marked change in CRD's with high temperature alarms.Adequate assurance of all rod insertion for the bulletin scenario is provided by the manual scram measures taken in items l.a and l.b.(1).Item 2 An operating order has been issued to include testing the scram instrument volume level switches after each scram event.Quad Cities Units 1 and 2 l.a.Per telephone conversations and letter from GE and CECo., the opening air pressure for the scram outlet valves is 50 psig decreasing pressue.Pressure switch PS-l(2)-302-81 senses instrument air pressure to the scram outlet valves and is annunciated in the Control room.Instrument Setpoint Change 224 was written to have the alarm setpoint on.PS-l(2)-302-81 changed to 60 psig decreasing pressure.This setpoint provides a 10 psi margin requested in the Bulletin.In addition, a procedure change to QOA-900-5-A I~
 
was written requiring an immediate manual reactor scram if this alarm setpoint is reached.l.b.(1)A procedure change to QOA 900-5-A was written requiring an immediate manual reactor scram if three or more control rods are drifting in at the same time.l.b.(2)Control rod drive temperature is monitored and recorded on TRS-l(2)-340-16.
Reference (a) transmitted IE Bulletin 80-17 Supplement 3 requesting       a response to concerns identified with a postulated loss of the control rod drive 'control air systems.
This recorder is located behind the main control boards and takes approximately 13 minutes to sequence through all the control rods.The purpose of this instrument is to establish long term trends on the condition of the drive units such that preventative maintenance can be planned.It was not designed with the intent to provide rapid indication of multiple CRD high temperatures which may suddenly appear.Therefore, we will not initiate a manual reactor scram solely on"a marked change in the number of control rods with high temperature alarms".Requiring a reactor scram on the low air pressure alarm, or when three or more rods are drifting in, provide adequate assurance of full rod insertion in the scenario described'in the Bulletin.2.Procedure changes to QGP l-l, 1-2, 2-3.and QIP-Sl have been written to functionally test the level alarm, rod block and scram switches on the instrument volume following each scram event, prior to going to reactor power operation.
The Commonwealth Edison Company responses                             for Dresden Units 2 and 3 and Quad Cities Units 1 and 2 are provided                               in the enclosure to this letter.
These procedures will remain in effect until modifications have been made to increase the reliability of the water level indication in the scram discharge volume.6390A 1 r}}
                ~ r 1 I
8009sao               /0P
 
0   ~"
V
 
Commonwealth Edison Mr. Dames G. Keppler,       Director September 2, 1980 Page 2 Please   address   any questions   you may have in this regard to this office. Approximately 80         man-hours were expended in the review and preparation of this report,         24 of which were for corrective actions.
Very   truly yours, Thomas 3. Rausch Nuclear Licensing Administrator Special Projects Attachment cc:   Director, Division of Reactor Operations Inspection NRC Office of Inspection and Enforcement Washington,     DC   20555 SUBCRIBED and SWOR       to befor   .me this                 day of                           1980 Nota       ub lie
 
Enclosure Commonwealth Edison   Com   an Res onse   to IE Bulletin 80-17   Su   lement   3 The subject bulletin has been reviewed at the stations,             and the following responses     are provided:
Dresden Units   2 and 3 Item l.a.
The appropriate procedure has been changed to require           an immediate manual scram when air pressue reaches 60 psi. The pressure required to open the scram outlet valves is 50 psi.
Item l.b. (1)
The appropriate procedure has been changed to require an immediate manual scram when three rods have drifted.
Item l.b.(2)
The temperature recorder used for the CRD high temperature alarm   is located on the back panel in the control room. The recorder is a combination electrical-mechanical type that takes approximately 13 minutes to scan all the drives. The recorder and front panel alarms must be reset after each high temperature condition is detected on every scram. The recorder was installed for long-term monitoring of the CRD's, which is used for planning maintenance on the drives at the end of each cycle. It was not designed with the intent to provide rapid indication of multiple CRD high temperatures     which may suddenly appear.
Based on the above reasons, Dresden is not implementing an immediate manual scram, based solely on a marked change in CRD's with high temperature alarms. Adequate assurance of all rod insertion for the bulletin scenario is provided by the manual scram measures taken in items l.a and l.b. (1).
Item 2 An operating order has been issued to include testing the scram instrument volume level switches after each scram event.
Quad Cities Units 1 and 2 l.a. Per telephone conversations and letter from GE valves      and CECo.,
is 50 the opening air pressure     for the   scram   outlet psig decreasing pressue.     Pressure   switch   PS-l(2) -302-81 senses instrument air pressure to the scram outlet valves and is annunciated in the Control room.           Instrument Setpoint Change 224 was written     to   have   the alarm setpoint on.PS-l(2)-302-81 changed to 60 psig       decreasing     pressure.
This setpoint provides a 10 psi margin         requested   in the Bulletin. In addition, a procedure change to             QOA-900-5-A
 
I~
was this written requiring an immediate alarm setpoint is reached.
manual reactor  scram if l.b. (1)   procedure change to QOA 900-5-A was written requiring an A
immediate manual reactor scram   if three or more control rods are drifting in at the same time.
l.b.(2) Control   rod drive temperature is monitored and recorded on TRS-l(2)-340-16. This recorder is located behind the main control boards and takes approximately 13 minutes to sequence through all the control rods. The purpose of this instrument is to establish long term trends on the condition of the drive units such that preventative maintenance can be planned. It was not designed with the intent to provide rapid indication of multiple CRD high temperatures which may suddenly appear.
Therefore, we will not initiate a manual reactor scram solely on "a marked change in the number of control rods with high temperature alarms". Requiring a reactor scram on the low air pressure alarm, or when three or more rods are drifting in, provide adequate assurance of full rod insertion in the scenario described'in the Bulletin.
: 2. Procedure changes to QGP l-l, 1-2, 2-3. and QIP-Sl have been written to functionally test the level alarm, rod block and scram switches on the instrument volume following each scram event, prior to going to reactor power operation. These procedures will remain in effect until modifications have been made to increase the reliability of the water level indication in the scram discharge volume.
6390A
 
r 1}}

Latest revision as of 10:49, 22 October 2019

Forwards Response to IE Bulletin 80-17,Suppl 3, Failure of 76 of 185 Control Rods to Fully Insert During Scram at Bwr. Procedure at Dresden 2 & 3 Changed to Require Immediate Manual Scram When Air Pressure Reaches 60 Psi
ML17341A013
Person / Time
Site: Dresden, Quad Cities  Constellation icon.png
Issue date: 09/02/1980
From: Rausch T
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
IEB-80-17, NUDOCS 8009260109
Download: ML17341A013 (7)


Text

Commonwealth Edison One First 'onal Plaza, Chicago, illinois 7/w Address fy to: Post Office Box 767 Chicago, fotnois 60690 September 2, 1980

Mr. Dames G. Keppler, Director Di.rectorate of Inspection and Enforcement Region U.S. Nuclear Regulatory Commission III 799 Roosevelt Road Glen Ellyn, IL 60137

Subject:

Dresden Station Units 2 and 2 Quad Cities Station Units 1 and 2 Response t o I E Bulletin 80-17 Supplement 3 "Failure of Control Rods to Insert During a Scram at a BWRn NRC Docket Nos. 50-10/237/249 and 50-254/265 Reference (a): 3. G. Keppler letter to C. Reed dated August 22, 1980

Dear Mr. Keppler:

Reference (a) transmitted IE Bulletin 80-17 Supplement 3 requesting a response to concerns identified with a postulated loss of the control rod drive 'control air systems.

The Commonwealth Edison Company responses for Dresden Units 2 and 3 and Quad Cities Units 1 and 2 are provided in the enclosure to this letter.

~ r 1 I

8009sao /0P

0 ~"

V

Commonwealth Edison Mr. Dames G. Keppler, Director September 2, 1980 Page 2 Please address any questions you may have in this regard to this office. Approximately 80 man-hours were expended in the review and preparation of this report, 24 of which were for corrective actions.

Very truly yours, Thomas 3. Rausch Nuclear Licensing Administrator Special Projects Attachment cc: Director, Division of Reactor Operations Inspection NRC Office of Inspection and Enforcement Washington, DC 20555 SUBCRIBED and SWOR to befor .me this day of 1980 Nota ub lie

Enclosure Commonwealth Edison Com an Res onse to IE Bulletin 80-17 Su lement 3 The subject bulletin has been reviewed at the stations, and the following responses are provided:

Dresden Units 2 and 3 Item l.a.

The appropriate procedure has been changed to require an immediate manual scram when air pressue reaches 60 psi. The pressure required to open the scram outlet valves is 50 psi.

Item l.b. (1)

The appropriate procedure has been changed to require an immediate manual scram when three rods have drifted.

Item l.b.(2)

The temperature recorder used for the CRD high temperature alarm is located on the back panel in the control room. The recorder is a combination electrical-mechanical type that takes approximately 13 minutes to scan all the drives. The recorder and front panel alarms must be reset after each high temperature condition is detected on every scram. The recorder was installed for long-term monitoring of the CRD's, which is used for planning maintenance on the drives at the end of each cycle. It was not designed with the intent to provide rapid indication of multiple CRD high temperatures which may suddenly appear.

Based on the above reasons, Dresden is not implementing an immediate manual scram, based solely on a marked change in CRD's with high temperature alarms. Adequate assurance of all rod insertion for the bulletin scenario is provided by the manual scram measures taken in items l.a and l.b. (1).

Item 2 An operating order has been issued to include testing the scram instrument volume level switches after each scram event.

Quad Cities Units 1 and 2 l.a. Per telephone conversations and letter from GE valves and CECo.,

is 50 the opening air pressure for the scram outlet psig decreasing pressue. Pressure switch PS-l(2) -302-81 senses instrument air pressure to the scram outlet valves and is annunciated in the Control room. Instrument Setpoint Change 224 was written to have the alarm setpoint on.PS-l(2)-302-81 changed to 60 psig decreasing pressure.

This setpoint provides a 10 psi margin requested in the Bulletin. In addition, a procedure change to QOA-900-5-A

I~

was this written requiring an immediate alarm setpoint is reached.

manual reactor scram if l.b. (1) procedure change to QOA 900-5-A was written requiring an A

immediate manual reactor scram if three or more control rods are drifting in at the same time.

l.b.(2) Control rod drive temperature is monitored and recorded on TRS-l(2)-340-16. This recorder is located behind the main control boards and takes approximately 13 minutes to sequence through all the control rods. The purpose of this instrument is to establish long term trends on the condition of the drive units such that preventative maintenance can be planned. It was not designed with the intent to provide rapid indication of multiple CRD high temperatures which may suddenly appear.

Therefore, we will not initiate a manual reactor scram solely on "a marked change in the number of control rods with high temperature alarms". Requiring a reactor scram on the low air pressure alarm, or when three or more rods are drifting in, provide adequate assurance of full rod insertion in the scenario described'in the Bulletin.

2. Procedure changes to QGP l-l, 1-2, 2-3. and QIP-Sl have been written to functionally test the level alarm, rod block and scram switches on the instrument volume following each scram event, prior to going to reactor power operation. These procedures will remain in effect until modifications have been made to increase the reliability of the water level indication in the scram discharge volume.