DCS No: 50311871024 Date: October 26, 1987-PRELIMINARY NOTIFICATION OF. EVENT'OR UNUSUAL OCCURRENCE--PNO-I-87-99 This preliminary notification' constitutes EARLY notice of events of POSSIBLE safety;or-public: interest signif_icance. The information is as initially received without .verifi-reation'or evaluation', and is basically all that is known by the Region'I staff on this date.

' Facility: . Licensee Emergency Classification:

-Public Service Electric & Gas.Co. Notification of. Unusual Event Salem Unit 2: Alert

'DN 50-311 Site Area Emergency General-Emergency

-X Not Applicable

Subject:

SHUTDOWN.IN EXCESS OF 48' HOURS

-Breaker coordination concerns were previously ' identified during an NRC Appen' dix R inspection in September 1987. Specific problems on the Unit.2 emergency diesel generator 4 Kv switchgear were identified and corrected on October 22 (see 10/23 morning report). At approximately 4:00 p.m. on October 23,.1987, the licensee identified to NRC Region I

' management that additional uncertainties existed in the onsite electrical distribution

system design,. such that a: potential for breaker coordination problems existed.

The licensee was unable.to document a comprehensive justification for continued operation-I and commenced a' shutdown-of Unit 2 at 4:00 p.m. on October 23. The unit was removed from service at 4:41 a.m. on October 24, 1987, and is currently in cold shutdown. 'The licensee has committed to provide to NRC-an analysis of the onsite electrical distribution system >

including proper electrical breaker coordination prior to restart of the unit.

~ 0uring' the shutdown the licensee plans to also make repairs to the No. 24 steam generator, which had a 50Lgallon/ day primary to secondary leak prior to the_ plant shutdown.

The resident inspector is onsite monitoring the licensee's actions. g The States of New Jersey and Delaware have been notified. '$ g

Contact:

P. Swetland - (488-1114) R. Summers - (488-1115) $

DISTRIBUTION:

H. St. MNBB Phillips E/W Willste Mail: ADM:DMB @

> @t Chairman Zech E00 NRR NMSS DOT:Trans esly Comm. Roberts PA OIA RES h3 'l Comm. Bernthal 0GC AE00 NRC Ops Crt Comm. Carr.

Comm. Rogers ACRS- Air Rights INP0----

SECY SP NSAC----

_CA POR Regional Offices TMI Resident Section RI Resident Office Licensee: l (Reactor Licensees) i Region I Form 83 i

. (Rev.. August 1987) 1 i jo 3 gO2 04 871026 l l PNO-I-87-o99 O PDR

~

/ I r

a