Category:PRELIMINARY NOTIFICATION OF EVENT OR OCCURRENCE (PNO
MONTHYEARPNO-I-99-043, on 990916,Hurricane Floyd Was Approaching Ccnpp,Sgs,Hcgs & Ocnpp.Hurricane Was Centered at Latitude 36.0 North & Longitude 76.6 West & Moving north-northeast at Approx 25 Mph.Plants Remain at Power1999-09-16016 September 1999
[Table view]PNO-I-99-043:on 990916,Hurricane Floyd Was Approaching Ccnpp,Sgs,Hcgs & Ocnpp.Hurricane Was Centered at Latitude 36.0 North & Longitude 76.6 West & Moving north-northeast at Approx 25 Mph.Plants Remain at Power PNO-I-99-010, on 990228,Unit 1 Reactor Automatically Tripped, Due to Main Turbine Trip That Resulted from Rapid Loss of Lube Oil Pressure.Plant Equipment Operators Adjusting Isolation Valve of Main Turbine Lube Oil Cooler1999-03-0101 March 1999 PNO-I-99-010:on 990228,Unit 1 Reactor Automatically Tripped, Due to Main Turbine Trip That Resulted from Rapid Loss of Lube Oil Pressure.Plant Equipment Operators Adjusting Isolation Valve of Main Turbine Lube Oil Cooler PNO-I-99-008, on 990203,determined That Computer Sys Supporting Overhead Annunciators in CR Had Malfunctioned. Mishap Occurred During Preventive Maint on Annunciator Computer Sys,Which Involves Two Computer Processors1999-02-0303 February 1999 PNO-I-99-008:on 990203,determined That Computer Sys Supporting Overhead Annunciators in CR Had Malfunctioned. Mishap Occurred During Preventive Maint on Annunciator Computer Sys,Which Involves Two Computer Processors PNO-I-98-060, on 981208,CR Operators Declared Unusual Event at Salem Unit 2,due to Indications of Substantial RCS Leak. Unit 1 Was Operating at Full Power.Resident Inspectors Responded to Event & Observed CR Activities1998-12-0909 December 1998 PNO-I-98-060:on 981208,CR Operators Declared Unusual Event at Salem Unit 2,due to Indications of Substantial RCS Leak. Unit 1 Was Operating at Full Power.Resident Inspectors Responded to Event & Observed CR Activities PNO-I-98-057, on 981130,util Commenced Shutdown of Salem Unit 2 to Repair 21 RCP Seal.Resident Inspectors Observed Portions of Plant Shutdown & Plan to Observe Continuing Maint Activities on RCP Seal1998-12-0101 December 1998 PNO-I-98-057:on 981130,util Commenced Shutdown of Salem Unit 2 to Repair 21 RCP Seal.Resident Inspectors Observed Portions of Plant Shutdown & Plan to Observe Continuing Maint Activities on RCP Seal PNO-I-98-012, on 980407,reactor Went Critical.Nrc Inspectors Observed Approach to Criticality.Util Issued Press Release1998-04-0808 April 1998 PNO-I-98-012:on 980407,reactor Went Critical.Nrc Inspectors Observed Approach to Criticality.Util Issued Press Release PNO-I-98-009, on June 1995 CAL Which Modified to Allow Salem Unit 2 Restart on 970806 Has Now Been Modified to Permit Unit 1 Restart.Approach to Criticality Expected to Begin on 980405.Addl Insp Planned to Monitor Power Ascension Program1998-04-0101 April 1998 PNO-I-98-009:on June 1995 CAL Which Modified to Allow Salem Unit 2 Restart on 970806 Has Now Been Modified to Permit Unit 1 Restart.Approach to Criticality Expected to Begin on 980405.Addl Insp Planned to Monitor Power Ascension Program PNO-I-98-006, on 980218,util Commenced Heat Up & Mode 4 Entered.Nrc Inspectors Onsight for Readiness Assessment Team Insp Observed Heat Up Activities1998-02-18018 February 1998 PNO-I-98-006:on 980218,util Commenced Heat Up & Mode 4 Entered.Nrc Inspectors Onsight for Readiness Assessment Team Insp Observed Heat Up Activities PNO-I-98-004, on 980211,PSE&G Commenced Shut Down of Unit 2 in Order to Make Repairs to 2A EDG & Other Plant Equipment. Operators Noted Abnormal Noise While Securing 2A EDG During Post Maint Surveillance Test1998-02-12012 February 1998 PNO-I-98-004:on 980211,PSE&G Commenced Shut Down of Unit 2 in Order to Make Repairs to 2A EDG & Other Plant Equipment. Operators Noted Abnormal Noise While Securing 2A EDG During Post Maint Surveillance Test PNO-I-97-052, on 970817,NRC inspectors,on-shift at Time, Observed Approach to Criticality.Backshift Insp Coverage in Progress to Monitor Reactor Startup & Power Ascension Program.States of Nj & DE Notified1997-08-18018 August 1997 PNO-I-97-052:on 970817,NRC inspectors,on-shift at Time, Observed Approach to Criticality.Backshift Insp Coverage in Progress to Monitor Reactor Startup & Power Ascension Program.States of Nj & DE Notified PNO-I-97-048, on 970807,approach to Criticality Expected to Begin,Based on June 1995 CAL Modified to Allow Restart of Salem Unit 2.Addl Insps Planned to Monitor Power Ascension Program.States of Nj & DE Notified1997-08-0707 August 1997 PNO-I-97-048:on 970807,approach to Criticality Expected to Begin,Based on June 1995 CAL Modified to Allow Restart of Salem Unit 2.Addl Insps Planned to Monitor Power Ascension Program.States of Nj & DE Notified PNO-I-96-072, on 961009,screws Had Been Removed from Plant, Unit 2 Radiation Monitor Control Cabinet Due to Possible Tampering or Prank Activities.Investigation Is in Progress & Area Has Been Quarantined.State of Nj Has Been Notified1996-10-10010 October 1996 PNO-I-96-072:on 961009,screws Had Been Removed from Plant, Unit 2 Radiation Monitor Control Cabinet Due to Possible Tampering or Prank Activities.Investigation Is in Progress & Area Has Been Quarantined.State of Nj Has Been Notified PNO-I-96-010, on 960223,util Announced Restart of Unit 1 Will Be Delayed for Indefinite Period to Assess Condition of Four Sgs.Restart of Unit 2 Remains Scheduled for Third Quarter of 19961996-02-23023 February 1996 PNO-I-96-010:on 960223,util Announced Restart of Unit 1 Will Be Delayed for Indefinite Period to Assess Condition of Four Sgs.Restart of Unit 2 Remains Scheduled for Third Quarter of 1996 PNO-I-95-043, on 951004,temporary Loss of CR Annunciators Occurred.Licensee Continuing to Troubleshoot Sys1995-10-0505 October 1995 PNO-I-95-043:on 951004,temporary Loss of CR Annunciators Occurred.Licensee Continuing to Troubleshoot Sys ML18101A7791995-06-0909 June 1995 PNO-1-95-018:on 950607,unit 2 Operators Commenced TS 3.0.3 Required Shutdown from 100% Power Due to Declaration of Two Inoperable RHR Trains.Protective Relay Actuation Caused Loss of One Source of Power to Vital 4KV Buses PNO-I-94-051, on 940919,plant Operators Took High Head Safety Injection Pump Out of Svc for Scheduled Maint & Proceeded to Shutdown Plant Due to Abnormal Vibration of Gear Drive.State of Nj Notified1994-09-23023 September 1994 PNO-I-94-051:on 940919,plant Operators Took High Head Safety Injection Pump Out of Svc for Scheduled Maint & Proceeded to Shutdown Plant Due to Abnormal Vibration of Gear Drive.State of Nj Notified PNO-I-93-068, on 931203,ALCO Emergency Diesel Generator Cylinder Cracking Discovered.Health Physics Technician Noticed Coolant Leaking from Number 3 Cylinder Sleeve on Right Bank of Cylinders (3R)1993-12-0707 December 1993 PNO-I-93-068:on 931203,ALCO Emergency Diesel Generator Cylinder Cracking Discovered.Health Physics Technician Noticed Coolant Leaking from Number 3 Cylinder Sleeve on Right Bank of Cylinders (3R) PNO-I-93-062, on 931112,informed That Current 30-day Contract Extension W/United Govt Security Officers of America Will Expire on 931115.Licensee Indicated That They Have Adequate Personnel Trained & Available to Satisfy Security Plan1993-11-12012 November 1993 PNO-I-93-062:on 931112,informed That Current 30-day Contract Extension W/United Govt Security Officers of America Will Expire on 931115.Licensee Indicated That They Have Adequate Personnel Trained & Available to Satisfy Security Plan PNO-I-93-060, on 931102,fire Reported in 230 Volt Lighting Transformer in Turbine Bldg.Caused by Loose Electrical Connection.State of Nj Has Been Notified1993-11-0303 November 1993 PNO-I-93-060:on 931102,fire Reported in 230 Volt Lighting Transformer in Turbine Bldg.Caused by Loose Electrical Connection.State of Nj Has Been Notified PNO-I-93-032, on 930627, Licensee Resolved Latest Issue Re Card Failures in Rod Control Power Cabinet.Licensee Completed Root Cause Evaluation & Briefed AIT on Site.Press Release Planned within 2 Wks1993-06-28028 June 1993 PNO-I-93-032:on 930627, Licensee Resolved Latest Issue Re Card Failures in Rod Control Power Cabinet.Licensee Completed Root Cause Evaluation & Briefed AIT on Site.Press Release Planned within 2 Wks PNO-I-93-030, during Startup of Plant from Recent Refueling Outage Multiple Failures Experienced in Sys. Augmented Insp Team Dispatched to Investigate Failures.Team Expects to Complete Work in 1 Wk1993-06-0707 June 1993 PNO-I-93-030:during Startup of Plant from Recent Refueling Outage Multiple Failures Experienced in Sys. Augmented Insp Team Dispatched to Investigate Failures.Team Expects to Complete Work in 1 Wk PNO-I-92-075, upon Investigation of Alarm Printed Out on Auxiliary Typewriter on 921213,operators Determined That Cpu for Overhead Annunciator (Oha) Had Failed to Perform, Resulting in Loss of Oha Sys for 1 H & 41 Minutes1992-12-15015 December 1992 PNO-I-92-075:upon Investigation of Alarm Printed Out on Auxiliary Typewriter on 921213,operators Determined That Cpu for Overhead Annunciator (Oha) Had Failed to Perform, Resulting in Loss of Oha Sys for 1 H & 41 Minutes PNO-I-90-056, on 900722,potential Design Deficiency in Main Steam Isolation Sys Noted.Units Shut Down Until Final Analysis & Appropriate Corrective Actions Completed1990-07-23023 July 1990 PNO-I-90-056:on 900722,potential Design Deficiency in Main Steam Isolation Sys Noted.Units Shut Down Until Final Analysis & Appropriate Corrective Actions Completed PNO-I-90-043, on 900523,supervisor W/No Operations Responsibilities Failed Random Alcohol Test W/Presence of Alcohol Above Program Limits (.04).Site Access Suspended & Individual Entered Licensee Rehabilitation Program1990-05-25025 May 1990 PNO-I-90-043:on 900523,supervisor W/No Operations Responsibilities Failed Random Alcohol Test W/Presence of Alcohol Above Program Limits (.04).Site Access Suspended & Individual Entered Licensee Rehabilitation Program PNO-I-90-024, on 900319,power Outage on Salem Deans Line Resulted in Hope Creek Reactor Scram.Caused by Low Reactor Vessel Water Level Resulting from Loss of All Feedwater & Condensate Pumps.States of Nj & DE Have Been Notified1990-03-20020 March 1990 PNO-I-90-024:on 900319,power Outage on Salem Deans Line Resulted in Hope Creek Reactor Scram.Caused by Low Reactor Vessel Water Level Resulting from Loss of All Feedwater & Condensate Pumps.States of Nj & DE Have Been Notified PNO-I-89-095, on 891201,unit Initiated Cold Shutdown to Mode 4 Due to Nearing Expiration of Tech Spec Action Statement. Containment Insp Revealed Body to Bonnet Leak on Safety Injection Check Valve.Repairs Completed1989-12-0404 December 1989 PNO-I-89-095:on 891201,unit Initiated Cold Shutdown to Mode 4 Due to Nearing Expiration of Tech Spec Action Statement. Containment Insp Revealed Body to Bonnet Leak on Safety Injection Check Valve.Repairs Completed ML18094A4151989-05-0404 May 1989 PNS-I-89-005:on 890503,unusual Event Declared When Helicopter Hovered Over Protected Area of Plants.Attempts to Land Helicopter for Identification Ignored.Helicopter Chartered by Util for Public Info Film PNO-I-89-029, on 890411,unit Tripped from lo-lo Level in Steam Generator as Result of Closure of Msiv.Caused by Faulty Relay in Test Circuitry During Main Steam Valve Cycling Surveillance & Severe Seat Damage.Valves Replaced1989-04-13013 April 1989 PNO-I-89-029:on 890411,unit Tripped from lo-lo Level in Steam Generator as Result of Closure of Msiv.Caused by Faulty Relay in Test Circuitry During Main Steam Valve Cycling Surveillance & Severe Seat Damage.Valves Replaced PNO-I-89-024, on 890323,unit Removed from Svc Due to High Combustible Gas Concentrations on Phase a Main Power Transformer.Licensee Plans to Maintain Unit in Mode 3 for Estimated 6-day Outage1989-03-24024 March 1989 PNO-I-89-024:on 890323,unit Removed from Svc Due to High Combustible Gas Concentrations on Phase a Main Power Transformer.Licensee Plans to Maintain Unit in Mode 3 for Estimated 6-day Outage PNO-I-88-125, on 881209,unit Removed from Svc Due to High Combustible Gas Concentrations on Phase C of Main Power Transformer.Shutdown Expected to Exceed 2 Days.Licensee Plans to Replace Transformer W/Spare1988-12-12012 December 1988 PNO-I-88-125:on 881209,unit Removed from Svc Due to High Combustible Gas Concentrations on Phase C of Main Power Transformer.Shutdown Expected to Exceed 2 Days.Licensee Plans to Replace Transformer W/Spare PNO-I-88-108, on 881018,hot Particle Identified on Worker Leg Above Ankle.Working Wearing Bubble Suit.Particle Was Fuel Fragment W/Total Activity Between 10 & 80 Rems to Skin. Steam Generator Tube Plugging Work Completed1988-10-20020 October 1988 PNO-I-88-108:on 881018,hot Particle Identified on Worker Leg Above Ankle.Working Wearing Bubble Suit.Particle Was Fuel Fragment W/Total Activity Between 10 & 80 Rems to Skin. Steam Generator Tube Plugging Work Completed PNO-I-88-105, on 881011,contractor Employee Fell from Refueling Floor of Reactor Containment Into Partially Drained Reactor Cavity.Contamination Found on Employee. Individual Sent to Hosp & Decontaminated1988-10-11011 October 1988 PNO-I-88-105:on 881011,contractor Employee Fell from Refueling Floor of Reactor Containment Into Partially Drained Reactor Cavity.Contamination Found on Employee. Individual Sent to Hosp & Decontaminated PNO-I-88-091, on 880831,Unit 1 Tripped from Full Power as Result of Main Turbine Trip.Cause Unknown.Unit 2 Tripped from Full Power Due to High Steam Generator (SG) Level Resulting from SG Feed Regulating Valve Failing Open1988-09-0101 September 1988 PNO-I-88-091:on 880831,Unit 1 Tripped from Full Power as Result of Main Turbine Trip.Cause Unknown.Unit 2 Tripped from Full Power Due to High Steam Generator (SG) Level Resulting from SG Feed Regulating Valve Failing Open PNO-I-88-066, on 880622,unit Tripped Following Loss of Vital Instrument Bus Inverter C.Loss Caused Low Reactor Loop Flow Trip.Caused by Loss of Reactor Coolant Pump Breaker Open Indication & Loss of Power.Licensee Initiated Investigation1988-06-22022 June 1988 PNO-I-88-066:on 880622,unit Tripped Following Loss of Vital Instrument Bus Inverter C.Loss Caused Low Reactor Loop Flow Trip.Caused by Loss of Reactor Coolant Pump Breaker Open Indication & Loss of Power.Licensee Initiated Investigation PNO-I-88-038, on 880330,reactor Manually Tripped Following Loss of Turbine Generator Hydraulic Control Oil Pumps.Util Will Remain Shutdown for 2 Wks to Repair Steam Generator Tube Leakage.State of Nj Notified1988-03-31031 March 1988 PNO-I-88-038:on 880330,reactor Manually Tripped Following Loss of Turbine Generator Hydraulic Control Oil Pumps.Util Will Remain Shutdown for 2 Wks to Repair Steam Generator Tube Leakage.State of Nj Notified PNO-I-88-027, on 880307,util Announced Election of Jf Paquette as President & Chief Operating Officer & Director of Company & CA Mcneill as Executive Vice President Effective on 8803141988-03-0707 March 1988 PNO-I-88-027:on 880307,util Announced Election of Jf Paquette as President & Chief Operating Officer & Director of Company & CA Mcneill as Executive Vice President Effective on 880314 PNO-I-88-020, on 880216,CA Mcneill Named Executive Director - Nuclear W/Responsibility of Directing Nuclear Operations, Including Nuclear Dept Reorganization & Restart Efforts of Peach Bottom1988-02-16016 February 1988 PNO-I-88-020:on 880216,CA Mcneill Named Executive Director - Nuclear W/Responsibility of Directing Nuclear Operations, Including Nuclear Dept Reorganization & Restart Efforts of Peach Bottom ML20217F8541987-10-27027 October 1987 PNS-I-87-017:on 871026,fireman Received Call of Bomb Threat at Plant.Search of Facility Proved Negative PNO-I-87-099, on 871023,licensee Notified Region I of Addl Uncertainties in Onsite Electrical Distribution Sys Design W/Potential for Breaker Coordination Problems.Unit Shutdown Commenced on 871023.Analysis Underway1987-10-26026 October 1987 PNO-I-87-099:on 871023,licensee Notified Region I of Addl Uncertainties in Onsite Electrical Distribution Sys Design W/Potential for Breaker Coordination Problems.Unit Shutdown Commenced on 871023.Analysis Underway PNO-I-87-075, on 870807,licensee Removed Facility from Svc to Replace Phase a Main Power Transformer.Caused by Breakdown in Insulation of Main Power Transformers.Facility in Mode 5 (Cold Shutdown)1987-08-10010 August 1987 PNO-I-87-075:on 870807,licensee Removed Facility from Svc to Replace Phase a Main Power Transformer.Caused by Breakdown in Insulation of Main Power Transformers.Facility in Mode 5 (Cold Shutdown) PNO-I-87-060, on 870703,unit Removed from Svc to Make Repairs to Low Pressure Turbines 21 & 22.Unit Being Maintained in Hot Shutdown.Licensee Expects to Complete Turbine Gasket Repairs within 14 Days1987-07-0606 July 1987 PNO-I-87-060:on 870703,unit Removed from Svc to Make Repairs to Low Pressure Turbines 21 & 22.Unit Being Maintained in Hot Shutdown.Licensee Expects to Complete Turbine Gasket Repairs within 14 Days PNO-I-87-059, on 870626,operators Received High Vibration Alarm on Bearing 6 of Low Pressure Turbine 22.Bearing Vibration Increased & High Pitched Noise Discovered.Licensee Elected to Remove Unit from Svc1987-06-26026 June 1987 PNO-I-87-059:on 870626,operators Received High Vibration Alarm on Bearing 6 of Low Pressure Turbine 22.Bearing Vibration Increased & High Pitched Noise Discovered.Licensee Elected to Remove Unit from Svc PNO-I-87-038, on 870429,licensee Learned That Control Room Operator Tested Positive for Use of Controlled Substance. Employee Will Be Terminated.Individual Acceptance Into Rehabilitation Program Under Consideration1987-04-29029 April 1987 PNO-I-87-038:on 870429,licensee Learned That Control Room Operator Tested Positive for Use of Controlled Substance. Employee Will Be Terminated.Individual Acceptance Into Rehabilitation Program Under Consideration PNO-I-86-075, on 860916,operators Removed Unit 1 from Svc to Repair Steam Leak on High Pressure Turbine Steam Return Line.Leak Caused by Steam Erosion on Section of 20-inch Pipe.Affected Section of Pipe Replaced1986-09-18018 September 1986 PNO-I-86-075:on 860916,operators Removed Unit 1 from Svc to Repair Steam Leak on High Pressure Turbine Steam Return Line.Leak Caused by Steam Erosion on Section of 20-inch Pipe.Affected Section of Pipe Replaced PNO-I-86-073, on 860911,Unit 2 Tripped from 75% Power.Caused by Loss of Reactor Coolant Pumps 22 & 23 Due to Deenergization of Two Nonvital Buses.Unit Entered Cold Shutdown on 860913.Repair Completion Expected by 8609201986-09-15015 September 1986 PNO-I-86-073:on 860911,Unit 2 Tripped from 75% Power.Caused by Loss of Reactor Coolant Pumps 22 & 23 Due to Deenergization of Two Nonvital Buses.Unit Entered Cold Shutdown on 860913.Repair Completion Expected by 860920 PNO-I-86-066, on 860826,turbine Trip/Reactor Trip & Safety Injection Occurred During Troubleshooting on Steam Generator Level Indicator 22.Natural Circulation Established & Third Vital Bus & Nonvital Loads Reenergized1986-08-26026 August 1986 PNO-I-86-066:on 860826,turbine Trip/Reactor Trip & Safety Injection Occurred During Troubleshooting on Steam Generator Level Indicator 22.Natural Circulation Established & Third Vital Bus & Nonvital Loads Reenergized PNO-I-86-061, on 860806,equipment Qualification Discrepancy Identified W/Field Wiring within Limitorque Valve Operators in Containments.Both Units Shut Down to Replace Questionable Wires W/Qualified Wires1986-08-0707 August 1986 PNO-I-86-061:on 860806,equipment Qualification Discrepancy Identified W/Field Wiring within Limitorque Valve Operators in Containments.Both Units Shut Down to Replace Questionable Wires W/Qualified Wires PNO-I-86-054, on 860721,licensee Initiated Normal Shutdown from 100% Power to Inspect & Correct Main Generator Hydrogen Leak Into Stator Cooling Water Sys.Completion of Insp & Repairs Expected in Approx 7 Days1986-07-21021 July 1986 PNO-I-86-054:on 860721,licensee Initiated Normal Shutdown from 100% Power to Inspect & Correct Main Generator Hydrogen Leak Into Stator Cooling Water Sys.Completion of Insp & Repairs Expected in Approx 7 Days PNO-I-85-075, on 851006,plant Tripped.Caused by Condensation in Condenser Vacuum Sensing Line Reaching Sensor Causing Turbine Trip W/Automatic Reactor Trip.Plant in Cold Shutdown for Maint & Mod to Condenser1985-10-0707 October 1985 PNO-I-85-075:on 851006,plant Tripped.Caused by Condensation in Condenser Vacuum Sensing Line Reaching Sensor Causing Turbine Trip W/Automatic Reactor Trip.Plant in Cold Shutdown for Maint & Mod to Condenser PNO-I-85-071A, on 850927,Hurricane Gloria Located at Northampton,Ma Moving in Northeasterly Direction.Status Downgrade to Tropical Storm Expected Early Evening on 850927.Salem Unit 1 & Millstone Complex Suffered Damage1985-09-27027 September 1985 PNO-I-85-071A:on 850927,Hurricane Gloria Located at Northampton,Ma Moving in Northeasterly Direction.Status Downgrade to Tropical Storm Expected Early Evening on 850927.Salem Unit 1 & Millstone Complex Suffered Damage 1999-09-16 Category:TEXT-INSPECTION & AUDIT & I&E CIRCULARS MONTHYEARIR 05000272/19990071999-09-28028 September 1999
[Table view]Insp Repts 50-272/99-07 & 50-311/99-07 on 990712-0829. Non-cited Violations Noted.Major Areas Inspected:Selected Exam of Procedures & Representative Records,Observed Work Activities & Interviews with Various Personnel IR 05000272/19990061999-09-20020 September 1999 Insp Repts 50-272/99-06 & 50-311/99-06 on 990716-0806 & (Region I-Inoffice) 990809-19 & 0901.No Violations Noted. Major Areas Inspected:Results of Team Insp of Auxiliary Feedwater Sys by Region Based Inspectors PNO-I-99-043, on 990916,Hurricane Floyd Was Approaching Ccnpp,Sgs,Hcgs & Ocnpp.Hurricane Was Centered at Latitude 36.0 North & Longitude 76.6 West & Moving north-northeast at Approx 25 Mph.Plants Remain at Power1999-09-16016 September 1999 PNO-I-99-043:on 990916,Hurricane Floyd Was Approaching Ccnpp,Sgs,Hcgs & Ocnpp.Hurricane Was Centered at Latitude 36.0 North & Longitude 76.6 West & Moving north-northeast at Approx 25 Mph.Plants Remain at Power IR 05000272/19990051999-08-10010 August 1999 Insp Repts 50-272/99-05 & 50-311/99-05 on 990530-0711.No Violations Noted.Major Areas Inspected:Licensee Performance Indicators ML18107A4741999-07-28028 July 1999 Notice of Violation from DOL Case 98-ERA-39,dtd 990314. Violation Noted:Licensee Discriminated Against Employee for Engaging in Protected Activities IR 05000272/19990041999-07-0606 July 1999 Insp Repts 50-272/99-04 & 50-311/99-04 on 990419-0529.Two Violations of NRC Requirements Occurred & Being Treated as non-cited Violations.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 05000272/19990021999-05-21021 May 1999 Insp Repts 50-272/99-02 & 50-311/99-02 on 990308-0418. Noncited Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support.Also Inspected Status of Util Ongoing Cable Raceway Fire Barrier Project IR 05000272/19990031999-05-0303 May 1999 Insp Repts 50-272/99-03 & 50-311/99-03 on 990315-19.No Violations Identified.Major Areas Inspected:Operations,Maint & Corrective Actions ML18107A2721999-04-30030 April 1999 Notice of Violation from Investigation Between 980303- 990119.Violation Noted:On 980103 & 980223,release Rate Calculations to Support Release of Liquid Waste Changed by Chemistry Supervisor ML18107A2691999-04-30030 April 1999 Notice of Violation from Investigation Conducted by NRC OI at Salem Nuclear Generating Station.Violation Noted:On 980223,D Branham Completed Record for Liquid Waste Intended to Be Released from CVCS Monitor Tank.Record Inaccurate IR 05000272/19993011999-04-0909 April 1999 NRC Operator Licensing Exam Repts 50-272/99-301 & 50-311/99-301 (Including Completed & Graded Tests) for Tests Administered on 990222-0305 & Grading on 990308-12.Seven of Eight ROs & All Eight SRO Applicants Passed Exam PNO-I-99-010, on 990228,Unit 1 Reactor Automatically Tripped, Due to Main Turbine Trip That Resulted from Rapid Loss of Lube Oil Pressure.Plant Equipment Operators Adjusting Isolation Valve of Main Turbine Lube Oil Cooler1999-03-0101 March 1999 PNO-I-99-010:on 990228,Unit 1 Reactor Automatically Tripped, Due to Main Turbine Trip That Resulted from Rapid Loss of Lube Oil Pressure.Plant Equipment Operators Adjusting Isolation Valve of Main Turbine Lube Oil Cooler IR 05000272/19980121999-02-12012 February 1999 Insp Repts 50-272/98-12 & 50-311/98-12 on 981206-990116. Violations Noted.Major Areas Inspected:Operations, Engineering,Maint & Plant Support ML18106B0671999-02-12012 February 1999 Notice of Violation from Insp on 981206-990116.Violation Noted:On 981208,identified That Procedure S2.OP-IO-ZZ-0002(Q), Cold Shutdown to Hot Standby, Permitted Increase in RCS Pressure to 375 Psig PNO-I-99-008, on 990203,determined That Computer Sys Supporting Overhead Annunciators in CR Had Malfunctioned. Mishap Occurred During Preventive Maint on Annunciator Computer Sys,Which Involves Two Computer Processors1999-02-0303 February 1999 PNO-I-99-008:on 990203,determined That Computer Sys Supporting Overhead Annunciators in CR Had Malfunctioned. Mishap Occurred During Preventive Maint on Annunciator Computer Sys,Which Involves Two Computer Processors IR 05000272/19980111998-12-21021 December 1998 Insp Repts 50-272/98-11 & 50-311/98-11 on 981025-1205. Violations Noted.Major Areas Inspected:Operations, Engineering,Maintenance & Plant Support & Insp on Radiation Protection Program ML18106B0061998-12-21021 December 1998 Notice of Violation from Insp on 981025-1205.Violation Noted:On 980916,NRC Identified Measuring & Test Equipment Connected to All Four Operable Channels of RPS Without Appropriate Channel Separation & Electrical Isolation PNO-I-98-060, on 981208,CR Operators Declared Unusual Event at Salem Unit 2,due to Indications of Substantial RCS Leak. Unit 1 Was Operating at Full Power.Resident Inspectors Responded to Event & Observed CR Activities1998-12-0909 December 1998 PNO-I-98-060:on 981208,CR Operators Declared Unusual Event at Salem Unit 2,due to Indications of Substantial RCS Leak. Unit 1 Was Operating at Full Power.Resident Inspectors Responded to Event & Observed CR Activities PNO-I-98-057, on 981130,util Commenced Shutdown of Salem Unit 2 to Repair 21 RCP Seal.Resident Inspectors Observed Portions of Plant Shutdown & Plan to Observe Continuing Maint Activities on RCP Seal1998-12-0101 December 1998 PNO-I-98-057:on 981130,util Commenced Shutdown of Salem Unit 2 to Repair 21 RCP Seal.Resident Inspectors Observed Portions of Plant Shutdown & Plan to Observe Continuing Maint Activities on RCP Seal IR 05000272/19980091998-11-19019 November 1998 Insp Repts 50-272/98-09 & 50-311/98-09 on 980913-1024. Violations Noted.Major Areas Inspected:Aspects of Licensee Operations,Engineering,Maint & Plant Support ML18106A9671998-11-19019 November 1998 Notice of Violation from Insp on 980913-1024.Violation Noted:On 980725,maint Technicians Failed to Properly Restore & Independently Verify That 22 AFW Pump Discharge Pressure Instrument Isolation Valve Was in Open Position IR 05000272/19983021998-10-0505 October 1998 NRC Operator Licensing Exam Repts 50-272/98-302 & 50-311/98-302 (Including Completed & Graded Tests) for Exams Administered on 980914-24.All Candidates Demonstrated Good Control of Plant Operations When in SRO Position ML18106A9061998-10-0505 October 1998 Insp Repts 50-272/98-08 & 50-311/98-08 on 980802-0912. Violations Noted.Major Areas Inspected:Aspects of Licensee Operation,Engineering,Maint & Plant Support ML18106A9041998-10-0505 October 1998 Notice of Violation from Insp on 980802-0912.Violation Noted:On 980820 Licensee Failed to Complete Required Containment Penetration Breaker Functional Testing within Time Period Mandated by Unit 2 TS 4.8.3.1.a.2 IR 05000272/19980991998-09-15015 September 1998 SALP Repts 50-272/98-99 & 50-311/98-99 for Salem Nuclear Generation Station,Units 1 & 2 for Period of 970301-980801 IR 05000272/19980061998-08-21021 August 1998 Insp Repts 50-272/98-06 & 50-311/98-06 on 980622-0801. Violations Noted.Major Areas Inspected:Licensee Operations, Maint,Engineering & Plant Support IR 05000272/19980071998-08-0404 August 1998 Insp Repts 50-272/98-07 & 50-311/98-07 on 980629-0716.No Violations Noted.Major Areas Inspected:Review Engineering Activities Re Previously Identified Issues ML18106A7061998-07-10010 July 1998 Notice of Violation from Insp on 980524-0621.Violations Noted:On 980504,NRC Inspectors Noted That Procedure Writers Failed to Perform 10CFR50.59 Applicability Review & SE for Rev to Procedure SC.MD-CM.ZZ-0024 as Required by NAP-59 ML18106A7011998-07-0808 July 1998 NRC Operator Licensing Exam Repts 50-272/98-301(OL) & 50-311/98-301(OL) (Including Completed & Graded Tests) for Tests Administered on 980626.Individual Passed Retake Exam & Issued License ML18106A6331998-05-22022 May 1998 Notice of Violation from Insp on 980316-0503.Violation Noted:Personnel Did Not Perform Condition Resolution to Evaluate Impact of Unsatisfactory Results for Emergency Control Air Compressor Test ML18106A6361998-05-22022 May 1998 Insp Repts 50-272/98-03 & 50-311/98-03 on 980316-0503. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support ML18106A7081998-05-0404 May 1998 Insp Repts 50-272/98-05 & 50-311/98-05 on 980504-0621. Violations Noted.Major Areas Inspected:Licensee Operations, Engineering,Maint & Plant Support ML20217N6221998-04-24024 April 1998 Notice of Violation from Investigation Conducted by Oi. Violation Noted:Safeguard Event Log,Required to Be Maintained by Licensee,Was Not Complete & Accurate in All Matl Aspects PNO-I-98-012, on 980407,reactor Went Critical.Nrc Inspectors Observed Approach to Criticality.Util Issued Press Release1998-04-0808 April 1998 PNO-I-98-012:on 980407,reactor Went Critical.Nrc Inspectors Observed Approach to Criticality.Util Issued Press Release ML18106A4321998-04-0202 April 1998 Insp Repts 50-272/98-01 & 50-311/98-01 on 980202-0315.No Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support ML18106A4311998-04-0202 April 1998 Notice of Violation from Insp on 980202-0315.Violation Noted:From 980125-0225,several Instances of Biofouling in SW Cooled Heat Exchangers Were Observed & Missing Strainer Filter Media Identified W/O Initiating Action Request PNO-I-98-009, on June 1995 CAL Which Modified to Allow Salem Unit 2 Restart on 970806 Has Now Been Modified to Permit Unit 1 Restart.Approach to Criticality Expected to Begin on 980405.Addl Insp Planned to Monitor Power Ascension Program1998-04-0101 April 1998 PNO-I-98-009:on June 1995 CAL Which Modified to Allow Salem Unit 2 Restart on 970806 Has Now Been Modified to Permit Unit 1 Restart.Approach to Criticality Expected to Begin on 980405.Addl Insp Planned to Monitor Power Ascension Program IR 05000272/19980041998-04-0101 April 1998 Insp Repts 50-272/98-04 & 50-311/98-04 on 980316-31.No Violations Noted.Major Areas Inspected:Engineering & Plant Support IR 05000272/19980801998-03-20020 March 1998 Insp Repts 50-272/98-80,50-311/98-80 & 50-354/98-04 on 980302-04.No Violations Noted.Major Areas inspected:full- Participation Emergency Preparedness Exercise Evaluation IR 05000272/19980811998-03-17017 March 1998 Insp Repts 50-272/98-81 & 50-311/98-81 on 980210-20.No Violations Noted.Major Areas Inspected:Mgt Programs & Independent Oversight,Operations,Maint & Surveillance & Engineering ML18106A3691998-03-0505 March 1998 Insp Repts 50-272/97-21 & 50-311/97-21 on 971201-980201. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support PNO-I-98-006, on 980218,util Commenced Heat Up & Mode 4 Entered.Nrc Inspectors Onsight for Readiness Assessment Team Insp Observed Heat Up Activities1998-02-18018 February 1998 PNO-I-98-006:on 980218,util Commenced Heat Up & Mode 4 Entered.Nrc Inspectors Onsight for Readiness Assessment Team Insp Observed Heat Up Activities IR 05000272/19980021998-02-17017 February 1998 NRC Operator Licensing Exam Repts 50-272/98-02OL & 50-311/98-02OL Administered on 980112-30.Seven SRO Candidates Administered Initial Exams.One Candidate Did Not Pass Written Portion,All Other Candidates Passed All Exams PNO-I-98-004, on 980211,PSE&G Commenced Shut Down of Unit 2 in Order to Make Repairs to 2A EDG & Other Plant Equipment. Operators Noted Abnormal Noise While Securing 2A EDG During Post Maint Surveillance Test1998-02-12012 February 1998 PNO-I-98-004:on 980211,PSE&G Commenced Shut Down of Unit 2 in Order to Make Repairs to 2A EDG & Other Plant Equipment. Operators Noted Abnormal Noise While Securing 2A EDG During Post Maint Surveillance Test IR 05000272/19970191997-12-24024 December 1997 Insp Repts 50-272/97-19 & 50-311/97-19 on 971020-1130.No Violations Noted.Major Areas Inspected:Operations, Engineering,Maintenance,Plant Support & Security Program IR 05000272/19970811997-12-0303 December 1997 Corrected Pages for Insp Repts 50-272/97-81,50-311/97-81 & 50-354/97-81.Rev to More Clearly Show Status of Two Issues Discussed in Rept ML18106A1661997-11-18018 November 1997 Notice of Violation from Insp on 970908-1019.Violation Noted:From 970909-16,valves 1FP186 & 1FP187 Were Closed, Isolating All Fire Protection Water to Units 1 & 2 Auxiliary & Containments ML18106A1671997-11-18018 November 1997 Insp Repts 50-272/97-18 & 50-311/97-18 on 970908-1019. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support Re Inadvertent Isolation of Fire Protection Water to Units 1 & 2 Auxiliary Bldgs IR 05000272/19970201997-11-14014 November 1997 Insp Repts 50-272/97-20 & 50-311/97-20 on 971020-1113.No Violations Noted.Major Areas Inspected:Engineering & Plant Support ML18102B6141997-10-0808 October 1997 NOV from Insp on 930517-970418.Violation Noted:Fire Watch Patrols Were Not Properly Implemented or Maintained for Inoperable Fire Barriers During Such Time as Capability of Three Types of 1 H ERFBSs Was in Question as Listed 1999-09-28 |
Text
'7 W (2c W k W) Cy [Oh,641Q PRELIMINARY NOTIFICATION m:-
(7 q,.
January 12, 1978 V
PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-78-05 This preliminary notification constitutes EARLY notice of an event of POSSI3LE safety or public interest significance.
The information nresented is as initially received without verification or evaluation
'and is basically all that is known by IE staff on this date.
Facility:
Public Service Electric and Gas Company Salem Nuclear Generating Station, Unit 1 Salem, New Jersey (DN50-272)
Subject:
UNPLANNED FACILITY SHUTDOWN At 1:46 a.m., January ll,1978, an orderly unit shutdown was made because of debris accumulation and icing of the circulating water intake screens.
The inability to maintain condenser vacuum because of icing necessitated the shutdown.
Early in the afternoon of January ll, 1978, the screens had been cleaned and de-iced and preparations were being made for startup. At this time a leak was found in the bonnet gasket of a check valve in the line from a safety injection FW accumulator tank.
..T.7::.
{"~
The unit is being maintained in the cold shutdown condition while the gasket is being replaced.
It is expected that the unit will be back at power on Sunday, January 15, 1978.
C:
The State of New Jersey has been informed. A press release is planned by the licensee. Media interest is expected.
.d -
NRC, Region I. (Philadelphia) received notification of this occurrence by c
telephone from the Station Manager at 8:20 a.m., on January 12, 1978.
O
Contact:
EBBlackwood, IE x28019 JHSniezek, IE x28019 N
i Distribution:
TransmittedHSt/((b Chairman Hendrie Commissioner Bradford
{
Commissioner Kennedy S. J. Chilk, SECY C. C. Kammerer, CA
)
Commi'ssioner Gilinsky (ForDistribution)
Transmitted:
MNBB /[/[b PBldg//)/[
E. Volgenag, IE L. V. Gossick, EDO E. G. Case, NRR Region L ff _1/
S. H. Hanauer, EDO J. J. Fouchard, PA SS Bldg //l 2. D (MAIL)
R. Hartfield, MIPC C. V. Sniith, NMSS R. J. McTiernan, 01A R. G. Ryan, OSP R. Minogue, SD I
H. K. Shapar, ELD j
]
=e. _
PRELIMINARY NOTIFICATION 1
Y~
tN 9806160001 780110 i
!