Special Rept 88-005:on 880923,high Lube Oil Temp Trip Occurred When Start 1-88-0076,diesel Generator Train B Being Run to Prove Operability Following Routine Maint.Diesel Restarted to Verify High Lube Oil Temp
ML20205G672
Person / Time
Site: Vogtle Southern Nuclear icon.png
Issue date: 10/24/1988
From: Hairston W
GEORGIA POWER CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
88-005, 88-5, NON-00369, NON-369, NUDOCS 8810280312
Download: ML20205G672 (2)


Text

, _ _ _ _ _ _ _ _ _ _ _ __-_ ._ _ . _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ . _ _ _ _ _ _ _ - _ _

'et Georg a Fweet Ccmcany 333 Pie,1mori Avenye AUar14. Georg;a 30308 l Tetephone 404 5264526 Mitng AMress Fbst Othce Bom 4545 Ararta.Ceg a 30302 ,

t?e Sotswn estric splan ,

  • 'f(**l NON-00369 j naciear cw.i,ons i

October 24, 1988  !

I

+

U. S. Nuclear Regulatory Comission [

ATTN: Document Control Desk 1 Washington, D. C. 20555 PLANT V0 GILE - UNIT 1 i NRC DOCKET 50-424  !

OPERATING LICENSE NPF-68 SPECIAL REPORT INVALID DIESEL GENERATOR FAILURE

.l Gentlemen: }

In accordance with the requirements of the Plant Yogtle - Unit 1  !

Technical Specification section 4.8.1.1.3 and 6.8.2, Georgia Power Company  !

is submitting the enclosed Special Report concerning an invalid diesel  !

generator failure.  !

I Sincerel . .

f64.

W. G. Hairsto , III  ;

l TEW:dmh t i

2 j

Enclosure:

Special Report 88-005 c: Georgia Power Company l

! Mr. P. D. Rice  !

Mr. G. Bockhold. Jr.  !

Mr. M. Sheibani j Mr. J. P. Kane l GO-NORMS  !

Vogtle-NORMS

?

U. S. Nuclear Regulatory Comission }

Dr. J. N. Grace Regional Administrator  !

Mr. J. B. Hopkins Licensing Project Manager NRR(2 copies) i

, Mr. J. F. Rogge Senior Resident Inspector Operations. Vogtle ,

' I f

lZ i

\

8G10280312 891024 l

, PDR ADOCK 05000424 $ ;

S PDC i  !

r n

a'

  • e, e s ENCLOSURE PLANT YOGTLE - UNIT 1 NRC DOCKET 50-424 OPERATING LICENSE NPF-68 TECHNICAL SPECIFICATION SPECIAL REPORT 88-005 A. Requirement for Report This report is required in accordance with the Plant Vogtle - Unit 1 Technical Specifications Section 4.8.1.1.3. This section of the Technical Specificctions requires that all diesel generator failures, valid or non-valid, shall be reported to the Comission in a Special Report pursuant to Technical Specification 6.8.2.

B. Description of Invalid Failure for Train B Diesel Generator On September 23, 1988, Start Number 1-88-0076, Diesel Generator Train B, was being run to prove operability following routine maintenance. A High Lube Oil Temperature Trip occurred; although lube oil temperature was normal at the time. A review determined that the lube oil and lube oil cooling subsystems should not have been affected by the recently completed maintenance nor could any other reason for the trip be found. The diesel was started again in an attempt to verify the high lube oil temperature. l However, no high lube oil temperature was experienced. A successful test  !

was completed and the diesel was returred to service. Further l investigation is in progress.

l C. Sumary This non-valid failure per Reg. Guide 1.108, Section C.2.E.2. did not affect the diesel's energency response capability.

Since there are no valid failures in the past 20 valid tests, the Train B f Diesel Generator is still on a once per 31 day test frequency as defined by Technical Specification Table 4.8-1, 0095e