ELV-00909, Revised Special Rept Re Valid Diesel Generator Failure on 890719.Caused by Remote Gate Firing Module on Bridge Circuit 1.Rework on Module Completed & Circuit Returned to Svc

From kanterella
Jump to navigation Jump to search
Revised Special Rept Re Valid Diesel Generator Failure on 890719.Caused by Remote Gate Firing Module on Bridge Circuit 1.Rework on Module Completed & Circuit Returned to Svc
ML20248C156
Person / Time
Site: Vogtle Southern Nuclear icon.png
Issue date: 09/25/1989
From: Hairston W
GEORGIA POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
ELV-00909, ELV-909, NUDOCS 8910030380
Download: ML20248C156 (2)


Text

4 L' (JPOrgia power COmDYG

  • , . ", '333 Picamont Avernue Atlanta Georgra 30308 leiephone 404 526 3195 Ma.kno Address 40 invemess Center Par & way Post Ofhce Box 1295 Birmingham. Alabama 35201 Telephone 205 668 5561 e.v wuna.m vanc syntem
w. o. Hairston, n' September 25, 1989 Senior Wce President ELV-00909 Nuclear Operations 0023 i

Docket No. 50-424 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555 Gentlemen:

V0GTLE ELECTRIC GENERATING PLANT SPECIAL REPORT VALID DIESEL GENERATOR FAILURE In accordance with the requirements of the Vogtle Electric Generating Plant Technical Specifications 4.8.1.1.3 and 6.8.2, Georgia Power Company submitted -

a Special Report concerning a valid diesel generator failure by letter dated August 14, 1989 (ELV-00790). Enclosed is a revision to.this Special Report which corrects two typographical errors and updates the status of the repair work to correct the cause of the failure.

Sincerely, ,

,,.c W./. ICLf W. G. Hairston, III WGH,III/NJS/gm i

c(w): Georaia Power Company 1 Mr. C. K. McCoy  !

Mr. G. Bockhold, Jr. {

Mr. R. M. Odom '

Mr. P. D. Rushton NORMS ,

U. S. Nuclear Reaulatory Commission ,

l Mr. S. D. Ebneter, Regional Administrator Mr. J. B. Hopkins, Licensing Project Manager, NRR Mr. J. F. Rogge, Senior Resident Inspector, Vogtle

, I: .;

I

$R20030380 s9o925 S .ADocM 0500o424 -

PNU  !

  1. '. , ,.4 ENCLOSURE V0GTLE ELECTRIC GENERATING PLANT TECHNICAL SPECIFICATION SPECIAL REPORT 1-89-02 A. Requirement for Report This report is required in accordance with the Vogtle Electric Generating Plant's Technical Specifications, Section 4.8.1.1.3. This section of the Technical Specifications requires that all diesel-generator failures, valid or non-valid,. shall be reported to the Commission in a Special Report pursuant to Technical Specification -6.8.2.

B. Description of Valid Failure for Train B Diesel Generator On July 19, 1989, Diesel Generator IB was started for the monthly I surveillance testing and loaded to approximately 5000 KW when the operator noticed spikes in the current and KVAR meter readings. The l generator was taken off-line and the field voltage remained unstable.

~

The diesel was stopped for further investigation by the system engineer.

The cause of the problem was believed to be in.the exciter bridge or-voltage regulator, so the bridge circuit was switched from bridge No. .I.

to bridge No. 2 and the diesel started. The surveillance was- completed ,

with no further problems. The cause has been determined to be the Remote Gate Firing Module on bridge circuit No. 1. Rework on the module {

was completed and bridge circuit No. I was returned to service.

C. Summary This failure, per Regulatory Guide 1.108, Section C.2.e.7, was the first-valid failure in the last 20 valid tests and the fourth.in the last' 52  !

valid tests, which is the total number of valid tests to date on Diesel J Generator IB.

Test frequency remains at 31 days in compliance with Table 4.8-l' of the i Technical Specifications.  ;

)