ML20137Q316
| ML20137Q316 | |
| Person / Time | |
|---|---|
| Site: | Fermi |
| Issue date: | 11/23/1985 |
| From: | Hobbs M DETROIT EDISON CO. |
| To: | |
| Shared Package | |
| ML20137Q310 | List: |
| References | |
| 111585, 24.324.01, NUDOCS 8512050234 | |
| Download: ML20137Q316 (14) | |
Text
r Ij' o
.6,-
SR
_ Safety Classification y FERMI 2 PROCEDURE - OPERATIONS PROCEDURE - SURVEILLANCE TITLE:
CTG-11-1 MONTHLY OPERABILITY CHECK PROCEDURE NUMBER:
24.324.01 REVISION:
0 Name of preparer:
M. Hobbs Technically
[
Date: //-23-I (
reviewed by:
u-uf Reviewed / concurred by:
Date:
Supv - Operational Assurance Approved by:
Date:
Responsible Section Head or OSRO Member / Alt Further Approval Required for Safety-Related or Superintendent-Designated Procedures:
Recommended by:
Date:
OSRO Chairman / Alternate Date:
Approved by:
Superintendent - Nuclear Production The following approved Procedure Change Requests are incorporated in this revision:
i This revision l [ does l l does not constitute periodic review.
bh e
By M W Ik l
8512050234 85 4i l
F
24.324.01 C
R2v. 0 TABLE OF CONTENTS Page 1.0 Purpose......................................
1 F
2.0 References...................................
1 3.0 Precautions and Limitations..................
2 4.0 Frerequisites................................
2 5.0 Procedure....................................
3 6.0 Acceptance criteria..........................
3 Enclosures CTG-Il Selector Switches (111585)............
Estimated Reactive Capability Curve for Turbine-Generator Unit (111585)..............
Attachments CTG-ll-1 Generator Operability Verification Test (111585)................................
CTG-ll-1 Generator Operational Data (111585).....................................
Test Personnel ( 111585)......................
LBP/100/R495/1.0 111585
s-24.324.01 R;v. 0 Page 1 1.0 Purpose 1.1 To provide the detailed steps necessary to perform the required surveillance testing of.the CTG-ll-1 generator in accorda1ce with Technical Specifications, Section 4.7.9.2.
F 1.2 _To provide the detailed steps necessary to perform the Alternate Shutdown Monitoring CTG-il-1 Monthly Channel Checks in accordance with Technical Specifications, Section 4.3.10.1 and Table 4.3.10.
1.3 Required frequency is at least once every 31 days when in Condition 1, POWER OPERATION, Condition 2, STARTUP.
2.0 References 2.1 Source References 2.1.1 Fermi 2 Technical Specifications, 3/4.7.9 Appendix R Alternative Shutdown Auxiliary Systems, Section 4.3.10.1 and Table 4.3.10.
2.1.2 Plant Operations Manual (POM) 12.000.07, Plant Operations Manual Procedures 2.1.3 POM Procedure 12.000.13, Radiation Work Permit 2.1.4 POM Procedure 12.000.18, Survelliance Program 2.1.5 POM Procedure 12.000.43, verification of Correct Performance of Operating Activities 2.1.6 Drawings 4SD721F-61 Ratcheting and Starting Means - Unit 1 only CTG #11.
4SD721F-62 Starting means CKT CTG #11.
4SD721F-64 Purge, Firing and Fuel Supply CTG #11.
4SD721F-65 Flame Detector CTG #11.
4SD721F-95 Governor control CTG fil.
4SD721F-68 Exhaust Temp. Control CTG fil.
4SD721F-70 Temp. Indicator and Heaters CTG #11.
2.1.7 Functional System Description, Supervisory Control of the 120KV Switchyard and CTG-ll Generators at Fermi 1, 0721-2-E14 DRAF1
>v
-r, 24.324.01 Rev. 0 P 33 2
,f 3.0 Precautions and Limitations 3.1 When operating the LOWER / RAISE Control Switch for the CTC-11 Generators voltage and governor load control, the control command
_ ill be executed as long as the control switch is held in the w
LOWER or RAISE position. Operator has to anticipate time lag of y
the controlled value after release of the control switch.
3.2 Following the power block start-up or the use of manual load controls (GOVERNOR CONTROL switch), the automatic load controls are blocked. Automatic load controls (MIN, BASE and PEAK push-buttons) are restored by giving the Power Block a second ALL START signal.
3.3 If the Power Block Master Control switch is taken to STOP a second time the units will go off ratchet sear. If the units so off the ratchet gear, it will have to be reset at the CTG-11 Control Center. When reset, the unit will go back on ratchet gear.
3.4 When a unit (s) is loaded without any warm-up period, Attachment 2 must be completed every 15 minutes for the associated unit (s).
4.0 Prerequisites 4.1 43S Keylock Switch located on CTC-11 Control subpanel in the Fermi ! Control Room is in Fermi 2 position.
4.2 120kV circuit breaker control switch handles are removed from the Feral 1 Control Room Panel #2.
4.3 43P Selector Switch in the CTC-11 Control Center is in the REMOTE position.
4.4 43 Selector Switch on Individual unit control panel in the CTG-11 Control Center is in the REMOTE position.
4.5 Synchronizing Mode Selector Switch is in the OFF/ REMOTE position on CTG-11 Control Center Power Block Panel.
4. 6. Unit is ready to start as indicated by the green backlighted READY TO START indication on Panel H11-P811.
4 7 The NSS has given permission to perform this test on the Surveillance Performance Form.
4.( Verify all radiation protection requirements are met, as listed on the Radiation Work Fermit, if required.
DRAfl
24.324.01 key. 0 Page 3 5.0 Procedure 5.1 General Instructions F
5.1.1 All controls and indications for this test are located on C0P Hl1-P811 and Remote Shutdown Panel H21-P623, unless otherwise noted.
5.1.2 The names of all test personnel are to be listed on.
5.1.3 Compare all test results with the given acceptance criteria at all times throughout the test period.
5.2 Perform the CTG-11-1 Generator Operability Verification Test in accordance with Attachment 1.
6.0 Acceptance criteria 6.1 The Tech Spec requirements of this test are satisfied when the CTG-11-1 generator is shown to be operable in accordance with.
If not, refer to Tech Spec 3.7.9.
BRAF1
24.324.01 Page 1 of 1 ESTIMATED REACTIVE CAPABILITY CURVE FOR TURBINE-GENERATOR UNIT ATB-2-POLE - 18824 KVA - 3600 RPM - 13800 VOLTS - 0.85 PF 788 ARMATURE AMPS - 250 VOLTS EXCITATION IDENTIFICATION CTG 1 y
a 25
.4.
1 20
. ~...
--0. 4..Pr. a
...0. 6.pg.
A_50,F IfEET.
IR.TE!!P.. -
y 15..
q..
'A 80 F IIEET AIR TEri.
a #
. \\.
- 0. 8 3. P. T..,( R. A..T.ED.)... -
. w
'Ad 00,F ItEET Al.
'l '!!..
~ B""'
^B 10 M...
g j g
. 0. 9 5..P.F.-.....
.5 l
4: e
.,~1. 0 PF.
O
~*.
~s.
~.. -
c..
4
-10...
15-H,+0
-20..
.. 2 5...
.. 30 g
2 000 I;ILot1A.T.TS
...~
C3 o
O
,.4
.a.
5
- m; i PF
- 0 9.
1 r p.
_.4
.i.
D
.e..
.1 10
- 1..
4
... 0,8. P F. 4."..s... "...".. *..
.~.
w g.
3 e.
O,$ )
.A..... ~..
..q.
0b P. T.. '. '
.s<.
w.
15
.~.
4.
.1.
1..
.4 4.
.t i
..i
.22.
i
.aa.
.s.
4...
)
.2e
..a...
a..
20 l
l Curve AB Limited By Field Heating i
Curve BC Limited By Armature Heating I
Curve CD Limited By Armature Core End Meeting 111585 I
]
l l
l
,__.._.._,..__.-,...,__,._,_,,.____m
24.324.01 Page 1 of I CTC-Il SELECTOR SWITCHES P
UNIT 1 UNIT 2 UNIT 3 UNIT 4 43 43 43 43 I
I AUTO REPOTE AUTO REMOTE AUTO REMOTE AUTO REMOTE (UNIT (UNIT (UNIT (UNIT CONTROL)
CONTROL)
CONTROL)
CONTROL) e POWER BLOCK CONT. PNL.
43P (CTG-11CONTROLCTR.)
LOCAL REMOTE (POWERBLOCK CONTROL) 6 CTG-11 PASTER CONT. PNL.
435 (EF1 CONTROL ROOM)
EQU1PPED WITH KEY-LOCK EF1 EF2 (POWERBLOCK CONTROL 9 EF1 CONT. ROOM)
(POWERBLOCK, UNIT AND BLACKSTART CONTROL 9EF2 CONT. ROOM) 6 111585 n
24.324.01 Page 1 of 5 CTG-ll-1 GENERATOR OPERABILITY VERIFICATION TEST Step No.
Initiale/ Data Note:
See Enclosure 1 for CTG-ll Selector p
Switch diagram.
-1.0 -Starting:
NOTE:
When a unit is loaded without any warm-up period, Attachment 2 must be completed every 15 minutes.
1.1 Depress the red backlighted START pushbutton and verify the following:
/
1.1.1 The red backlighted START pushbutton is on.
/
1.1.2 The green backlighted READY TO START indication goes off.
/
1.1.3 The red backlighted SEQUENCE IN PROGRESS indication is on.
/
NOTE:
The unit will require 8-10 minutes to reach synchronous speed and to automatically synchronize.
1.2 When the unit breaker closes as indicated by a red CLOSED light verify the following 1.2.1 The red backlighted SEQUENCE IN PROGRESS indication goes off.
/
1.2.2 The red backlighted SEQUENCE COMPLETE indication is on.
/
s
\\m-
.s'.
m a
a BRAF1
!!!585
L*.
24.324.01 Page 2 of 5 CTC-11-1 GENERATOR OPERABILITY VERIFICATION TEST Step No.
Initials /Date 1.2.3 Unit MW output increases to 3-5 MW (Minimum).
/
NOTE:
The automatic synchronizing will adjust voltage to 107-124V and the frequency to SI -6f 45, as noted on Panel Hil-P811.
2.0 Loading
NOTE (1): There are two sets of controls available to adjust the MW output of the CTG-ll Generators ( Abu s Aus Aewanc.).
NOTE (2):
Following the power block start-up or the use of manual load controls (GOVERNOR CONTROL switch), the automatic load controls are blocked. Automatic load controls (MIN, BASE and PEAK push-buttons) are restored by giving the power block a second ALL START signal.
Manual - Governor Control Switches on the unit control subpanel.
Automatic - Load Selection - Minimum, Base or Peak on the Power Block Control subpanel.
NOTE (3): At this point the operator must decide to operate the unit load in Manual or Automatic.
2.1 Manual Load Control NOTE:
When operating the Lower / Raise control switches for the unit voltage and Governor Load controls, the operator should be aware that the command signal is present as long as the switch is held in the LOWER or RAISE position. The operator has to anticipate time lag of the controlled value after release of the control switch.
2.1.1 Turn the Governor Control Switch to RAISE and increase load to Base load (13-15 MW).
/
DRAF1
a 24.324.01 J i -.
Attechunt 1 Page 3 of 5 CTG-ll-1 GENERATOR OPERABILITY VERIFICATION TEST Step No.
Initials /Date 2.1.2 Adjust VARS as indicated on the individual Megavar (MVAR) indicator using the Voltage Control switch.
Maintain voltage and VARS within the capability curve (see Enclosure 2).
/
4 2.2 Automatic Load Control:
NOTE:
After the unit breaker closes the unit wilt load to Minimum load (3-5 MW).,
2.2.1 Depress the red backlighted START pushbutt5n and release.
/
NOTE:
The previous step allows the automatic load control to be used.
2.2.2 Verify the unit load increased to Base load (13-15 MW).
/
2.3 CTG-11-1 Channel Checks (To be performed while unit is running.)
2.3.1 CTG-11-1 Volts Record CTG-ll-1 volts from a.
H21-P623 V
/
b.
Record CTG-ll-1 volts from Hil,P811 V
/
c.
Verify Channel Check acceptable if readings taken above are within 10% of THE M rcov C.u r^ sa u t4tet..
% Difference
/
2.3.2 CTG-ll-l Fiequency a.
Recorf CTG-ll-1 frequency from H21-P623 Hz
/
b.
Record CTG-11-1 frequency from H11-P811 Hz
/
24.324.01 Attachm2nt 1 Page 4 of 5 CTG-11-1 GENERATOR OPERABILITY VERIFICATION TEST Step No.
Initials /Date c.
Verify Channel Check acceptable if readings taken above are y
within 10% of nc Courecu % # m u tt_.
% Difference
/
2.3.3 CTG-ll-1 Watts a.
Record CTG-ll-1 watts from H21-P623 W
/
b.
Record CTG-ll-1 watts from Hil-P811 W
/
c.
Verify Channel Check acceptable if readings taken above are within 10% of Tac Cearctc h,4 zgutArcE.
% Difference
/
2.3.4 CTG-ll-1 VARS a.
Record CTG-ll-1 VARS from H21-P623 VARS
/
b.
Record CTG-ll-1 VARS from Hil-P811 VARS
/
c.
Verify Channel Check acceptable if readings taken above are within 10% of we.0.c e u N <.A ratacAtet.
%' Difference
/
3.0 Shutdown NOTE:
If the unit is at a load other than Peak l
load, only step 3.2 and 3.3 will be performed.
If unit is at Minimum load, perform only step 3.3.
If the unit is in Manual perform step 3.3 only.
3.1-Depress and release the green backlighted STOP pushbutton and verify the following:
/
3.1.1 The green backlighted STOP pushbutton comes on and then goes off.
/
111585
24.324.01 Attechm2nt 1 Page 5 of.5 CTG-ll-1 GENERATOR OPERABILITY VERIFICATION TEST Step No.
Initials /Date 3.1.2 The unit load decreases to Base load y
(13-15 MW).
/
3.2 Depress and release the green backlighted STOP pushbutton and verify the following:
/
3.2.1 The green backlighted STOP pushbutton comes on and then goes off.
/
3.2.2 The unit load decreases to Minimum load (3-5 MW).
/
3.3 Depress and release the green backlighted STOP pushbutton and verify the following:
/
3.3.1 The unit load decreases load to O MW.
/
3.3.2 The unit breaker opens as indicated by the unit breaker green OPEN light on.
/
3.3.3
- When the unit decreases to O RPM, the Ratcheting System will begin to rotate the shaft.
/
NOTE:
If the unit green backlighted pushbutton is depressed again, the unit will go off ratchet gear. If the unit goes off the ratchet gear, it will have to be resetuat the CTG-ll Control Center. When reset, the unit will go back on gear.
1 111585 n
24.324.01 Attschmant 2
>:~
Page 1 of I CTG-ll-1 GENERATOR OPERATIONAL DATA DATE:
Acceptable Unit Component Range / Status 1
I Unit Start Time N/A NOTE:
Megawatts 5
.5 MW All CTG Megavars
<5 MVAR Readings.
Exciter D.C. Volts 80 - 160 Volt Should Be Exhaust Thermocouple Temp.
1
< 750' F Taken After Exhaust Thermocouple Temp.
2
< 750' F Approx.
Exhaust Thermocouple Temp. 3
< 750' F 10 minutes Exhaust Thermocouple Temp. 4
< 750' F Run Time Exhaust Thermocouple Temp.
5
< 750' F On the Exhaust Thermocouple Temp.
6
< 750* F Respective Exhaust Thermocouple Temp.
7
< 750' F CTG.
Exhaust Thermocouple Temp.
8
< 750' F Exhaust Thermocouple Temp.
9
< 750' F Exhaust Thermocouple Temp. 10
< 750' F Exhaust Thermocouple Temp. 11
< 750' F Exhaust Thermocouple Temp. 12
< 750' F MNX. Temp.
T (1-12 above)
< 50' F Fuel Oil Press. Before Main Filter I 100 psi Fuel Oil Press. After Main Filter I 85 psi Fuel Oil Press. d/p f 15 psi Lube' Oil Press. Before Main Filter I 40 psi Lube Oil Press. After Main Filter f 35 psi Lube Oil Press, d/p I
5 psi Vibration Detectors 1 f 1 in/sec
~ Vibration Detectors 2 f 1 in/sec Vibration Detectors 3 f 1 in/see Time for Unit to sync.
< 11 min.
Unit Sel. SW. in remote at end of test SAT OPERATOR:
NSO:
111585
v
+-
24.324.01 Page 1 of 1 TEST PERSONNEL Time Completed Date Completed F
- Printed names'of test personnel Initials Signatures e
N 0RAF1
>>1 -
4
%__