LIC-90-0876, Special Rept:On 901009,fire Door 1011-1 Declared Inoperable as Fire Barrier.Caused by Damage to Skin of Door During Corrective Maint on Lockset.Door Expected to Be Replaced by 901231

From kanterella
Jump to navigation Jump to search
Special Rept:On 901009,fire Door 1011-1 Declared Inoperable as Fire Barrier.Caused by Damage to Skin of Door During Corrective Maint on Lockset.Door Expected to Be Replaced by 901231
ML20062E963
Person / Time
Site: Fort Calhoun Omaha Public Power District icon.png
Issue date: 11/15/1990
From: Gates W
OMAHA PUBLIC POWER DISTRICT
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LIC-90-0876, LIC-90-876, NUDOCS 9011260230
Download: ML20062E963 (2)


Text

, _ _ _ _ _ _ _ _ _ . . _ - . _ _ _ _ _ _ . _ _ . - _ _ . _ _ _ _ _ _ _ _ . _ . _ .

4 Omaha Public Power District 444 South 16th Street Mall Omaha, Nebraska 68102-2247 402/636 2000 l

l November 15, 1990 LIC-90-0876 l

U.S. Nuclear Regulatory Commission i Attn Document Control Desk l Mail Station P1-137 i Washington, D.C. 20555 l

Reference:

Docket No. 50-285 l

Gentlement

SUBJECT:

Special Report on Inoperability of Fire Protection Equipment l

l. The Omaha Public Power District, holder of Operating License DPR-40, submits this special report pursuant to the requirements of Fort Calhoun Station Unit No 1 Technical Specification 2.19, " Fire Protection Systems".

FortCalhounStationUnitNo.1TechnicalSpecificationSection2.19(7) states

All penetration fire barriers protecting safety-related areas shall be functional intact). With a penetration fire barrier non functional, within l

r onehour,e(therestablishacontinuousfirewatchonatleastonesideofthe i

l affected penetration, or verify the~ operability of fire detectors on at least one side of the penetration and establish an hourly fire watch patrol. Restore the nonfunctional penetration to functional status within 7 days, or prepare and submit a report to the Nuclear Regulatory Commission, pursuant to Section ,

5.9.3 of the Technical Specifications, within an additional 30 days outlining the action taken, the cause, and the plans and schedule for restoring the penetration to functional status."

Fire Door 1011-1 was declared inoperable as a fire barrier on October 9, 1990 due to damage to the skin of the door during corrective maintenance on the door's lockset. The door has remained inoperable as a fire barrier for greater than 7 days due to the time required to procure the replacement fire door. As required by Technical Specifications the necessary compensatory measures were established within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and will remain in place until the door is replaced and returned to an operable status. Replacement of the fire door is expected l to be complete by December 31, 1990.

l l

)

i 9011260230 901115 fDR ADOCK 0500 5 assua tmunegn,tygmno k

& 1

i 1

e

  • U. S. Nuclear Regulatory Commission  !

LIC-90-0876  !

' .1 Page 2  ;

i If you have any questions, please contact me.

Sincerely, hf LAY W. G. Gates Division Manager h I s Nuclear Operations WGG/jb c: LeBoeuf, Lamb, Leiby & MacRae ,

N A.Bournia}n,RCProjectManager R. D. Mart NRC Regional Administrator, Region IV R. P. Mullikin,-NRC Senior Resident Inspector i t

i 7

9 6