LER 79-014/03L-0 on 790319:during Refueling Outage,Core Spray Sys Snubber 40-HS-10 Found Inoperable.Caused by Worn Piston Seals on Core Spray Snubber Resulting in Loss of Fluid from Snubber.Seals Replaced & Snubber Reinstalled
ML18037A176
Person / Time
Site: Nine Mile Point Constellation icon.png
Issue date: 06/14/1979
From: DUDA E
NIAGARA MOHAWK POWER CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML17053A731 List:
References
LER-79-014-03L, LER-79-14-3L, NUDOCS 7906220408