ML20209D946

From kanterella
Jump to navigation Jump to search
Forwards marked-up Tech Spec Section 3/4.8 Re Electrical Power Sys Identifying Differences Between FSAR Analysis & Rev 4 to NUREG-0452,in Response to 841217 Request for Review
ML20209D946
Person / Time
Site: 05000000, Diablo Canyon
Issue date: 01/14/1985
From: Rubenstein L
Office of Nuclear Reactor Regulation
To: Crutchfield D
Office of Nuclear Reactor Regulation
Shared Package
ML082410749 List: ... further results
References
FOIA-86-197, RTR-NUREG-0452, RTR-NUREG-452 NUDOCS 8502220358
Download: ML20209D946 (25)


Text

'

u iG 1

d4

%*t, f

UNITED STATES NUCLEAR REGULATORY COMMISSION j

18 y WASHINGTON, D. C. 20555

\\ +!CM $

p jgg 141985 MEMORANDUM FOR: Dennis M. Crutchfield, Assistant Director for Safety Assessment, DL

'FROM:

L. Rubenstein, Assistant Director for Core and Plant Systems, DSI

SUBJECT:

DIABLO CANYON UNIT 2 - COMPLETION OF REVIEW OF TECHNICAL SPECIFICATIONS

REFERENCE:

(

Memorandum for L. Rubenstein (and others) from D. Crutchfield dated December 17, 1984

\\

As requested in the above referenced memorandum, the Power Systems Branch has reviewed Section 3/4 8 of the Diablo Canyon Unit 1 and 2 combined technical specification which pertain to our area of responsibility.

In accordance with the guidelines provided by E. Butcher (DL) on December 26, 1984, Power Systems Branch limited its review of the subject technical specification -for Diablo Canyon to the following:

(a) Differences between Unit 1 and 2 listed in Enclosure 2 of the referenced memorandum and (b) Shared systems between Unit I and 2.

With respect to differences between Unit 1 and 2 listed in Enclosure 2 of the referenced memorandum, PSB concludes the following:

1.

A minimum volume of 52,046 gallons of fuel for five diesel generators (two unit operation) is consistent with the volume of fuel required for three diesel generators (one unit operation) and is, therefore, acceptable.

2.

On page 3/4 8-3 of the specification, the applicant implies incorrectly by a footnote statement that surveillance requirement 4.8.1.1.2 need not be s,

,I

?s performed more frequently than required to satisfy the operability 4

requirement for the most limiting unit. Surveillance requirement 4.8.1.1.2.b.5 for example is related to a unitized system that is not

Contact:

J. Knox, x24568 R. Giardina, x24953 mumd

/

9

.:.;. =.-

=

=

- g.

=

4 1

5

. 1,

,y

?

'!~

Dennis !i. Crutchfield D common to both units and, therefore, must be tested at the specified frequency of 18 months. The proposed specification should be clarified.to specifically address only those systems common to both units.

I

3. > 'On page 3/4 8-3 of the specification, the applicant rtates that testing of Diesel Generator 3 on one unit does~not place the other unit in an action

>i

. statement. PSB does not see the rationality /for thissstatement.

Additional.instification is required to assess,its acceptability.

e l

,o

. 7 4

1 Generator 3 and the fdel;ctl transfe'r4 system as systems beintshared between j ${]

With ' respect to shared, systems betes Unit 1 and 2, PSB has identified Diesel Unit 1 and 2.

Technical specifications systems shared between units /have not been adequately Mdressed'in theccombined Unit 1 and 2 tech:rxal specifications.

i It is-recommended theit all shared / systems be identified witt/their appropriate technicalspecificatiensforstaff'syeviewandconcurrence.

ro m

We have also compared the Unit 1 and 2 'c'ombined techutal specification with the FSAR analysis and Revision 4 of NUREG-0452, STS from W PWR's. The enclosed marked up pages of the Diablo Canyon Unit I and 2 technical specificaticos identify the differences between these two documents.

i <J d

~

t gl Ofthedifferencesfromthestandardte~hnicalspecificationsidentified[hnical c

two:

items are considered necessary and should be included in the enshineditec f

specificatipns for unit 1 and 2.

These items are:

(-

z 1.

Compliance with the requirements of GDC 50 for/ containment electrical I

penetrations is addresseOin supplemental safety evaluation reports number.

t 8 and 9 for the Diablo Canyon plants.

Primary / circuit protective devicesi have been provided in accordince with the 'rmirements of. GDC 50.

f Technical Specifications for these devicephave not been included in the-Diablo Canyon specification. In order'to meet. testing requirements of GDC 18 and 50, it is recommended th:2.STS s With 6 sped.pecification'3.8.4.1 be includei in the Diablo specification.

to backup-protection,'SSCR number 8 indicates that their installat h e.'not required until after first i

M

? 1 refueling. Surveillance requirementilfor betyprimary and backup TA

.,y protection should be included in the fgecificaion for Diablo Canyon after the fi st refueling.

as part of pr(opera %Because primary l protection, should have been verified nal' testing, it,may be appropriate to defer implemeccation of surveillance requf rements" for primary protectica -ui:til 3

after,first refueling.

/

'9

/

b/

2.

The Diablo Canyon plants combined 0 nit I and E technical specifications N

4.8.1.1.3.b, c, d, e, and 6,on fuel oil quality was compared to the'.4 i/

Standard Technical Specification (STS), and it does not conform to the STSi

$y nor to that approyed for' Unit 1.

The applicant has selectively applied portions of a phnt specific technical specification approved for McGuire, i

! //

portions of the STS, and a modification of theirtown. The resultant' technical specification for Unit 1 and 2 is deficient in that it doeFnot 1

M A>

[.

-?

t

> +

f

?n a.

  • . g

' ;?"

>/

l.

J.

4

a

- JAN 141985 Dennis

. Crutchfield address removal of accumulated water from the fuel oil storage tank at the recommended periodicity of every 31 days. The applicant must also u

demonstrate that the water can be completely removed from the storage tank (s).

In addition, once every 10 years, a pressure leak test shall be performed for those portions of the diesel fuel oil system designed to Section III (or equivalent), subsection ND of the ASME Code in accordance with ASME Code Section II Article 1WD-500. The technical specification should be modified to acconnodate these concerns or PGE should provide justification for the proposed combined technical specification change for i

Units 1 and 2.

A

'Two.otheritemsidentified,i.e.,surveillancerequirement4.8.3.1.g.2and 4.8.3.1.c 3 which change battery. terminal resistance from 150 x 10' to 250 x 10-6, and surveillance requirement 4.8.3.1.a.1 and 4.8.3.1.b.1 which changes the battery charging current from 2 amps to 5 amps, are not sufficiently significant to require changing to the Standard Technical Specification values.

However, the applicant may want to consider their adoption as an improvement in practice. The remaining differences identified are clarifications and administrative wording presently in the STS and not in the Diablo Canyon specification.

With the incorporation of the above recommended changes to the combined Diablo Canyon Units 1 and 2 technical specifications, the staff believes the plant technical specification will be complete.

p-~~~._

w.

L. S.

nstein, Assistant Director for Core and Plant Systems Division of Systems Integration

Enclosure:

As stated I

cc:

D. Eisenhut' M. Srinivasan R. Bernero H. Schierling T. Novak A. Ungaro i

G. Knighton J. Knight C. Thomas R.'Giardina E. Butcher J. Knox-C. Moon

.M.

w.,

-w e

p q

g.-

,--m w.-

d y y

,,ev..-9 y


9

-... ~...

%Irth k hk &_

s L,

cr f

J+.p.

w A

3/4.8 ELECTRICAL POWER SYSTEMS f

3/4.8.1 A.C. SOURCES j

A g,s( 7 R OPERATING

[

gg 7

LIMITING CONDITION FOR OPERATION

(

N Tf8mIdf ffr**y4 3.8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

a.

Two independent circuits (one with delayed access) between the offsite transmission network and the Onsite Class 1E Distribution System, and b.

Three separate and independent diesel generators, each with:

)

gr.

1.

A separate engine-mounted fuel tank containing a minimum volume of 200 gallons of fuel, and S' i, 2.

A common' fuel storage system containing a minimum volume of CN 31,023 gallons of fuel for one unit operation and 52,046 gallons of fuel for two unit opera ion, and two diesel fuel transfer pumps *

~

3

~

1,2,3,and4.gh\\a.1*DblMMMf^r APPLICABILITY: MODES w,h b7N ACTION:

n r-a.

With either an offsite circuit or diesel generator of the above required A.C. electrical power sources inoperable, demonstr. ate the OPER6ELITY of the remaining A.C. sources by performing grequirej

/

tments oTsSpecifications 4.8.1.1.la. and 4.8.1.1.2a.2) within 1 nour

/

and at 7 east once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least two offsite circuits and three diesel generators to OPERA 8LE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With one offsite circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing the u

@menf Specifications 4.8.1.1.la. and 4.8.1.'1.24.2) within 1 our 1

and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least j HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Restore at least two offsite circuits and three fb diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of

[

h#

initial loss or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and

'/

in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

{

~ ~ ~ - -

,- ~ # ',n-:

(

N Q iesel generator.

ff 4lp,.

g3 DIABLO CANYON - UNITS 1 AND 2 3/4 8-1 f;

.(

.. _ _.-. ~_.. _ _

ELECTRICAL POWER SYSTEMS j

LIMITING CONDITION FOR OPERATION s

l ACTION (Continued)

^

c.

With one diesel generator inoperable in addition to ACTION a. or b.

V

' above verify that:

1.

All required systems, subsystems, trains, components and devices /

that depend on the remaining OPERABLE dlesel generators as a source of emergency power are also OPERA 8LE, and

/

2.

When in MODE 1, 2, or 3 that at'least two auxiliary feed pumps are OPERABLE.

If the a conditions are not satisfied within*2 hours be in at leas

/-

4 HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the fol.lowina 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

d.

With two of the above required offsite A.C. circuits inoperable,.

demonstrate the opFRABILITY of three diesel generators by performing g'~ requirements oD$pecification 4.8.1.1.2a.2) within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at

+ ance per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, unless the diesel generators are f

already operating; restore at least one of the inoperable offsite

/

sources to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. With only one offsite source restored, restore at least two offsite circuits to OPERABLE ste.tus within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initiallloss or be in at least HOT STANDBY within the-next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the i

following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

i With two or more of the above required diesel generators inoperable, e.

demonstrate

@ e'TeW N,m,JhtLOPERABILITY of two offsite A.C. circuits by performing ant 7epecification 4.8.1.1.la. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at o

least once.per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least two of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANOBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Restore at least three diesel genera-

)

tors to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in least HOT STANDBY within th'e next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

e 4

4e te W

DIABLO CANYON - UNITS 1 AND 2 3/4 8-2 I

(

.c_.-.

,5 ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS 4.8.1.1.1 Each of the above required independent circuits between the offsite

/

transmission network and the Onsite Class IE Distribution System shall be:

Determined OPERABLE at least once per 7 days by verifying correct h /'

a.

breaker alignments, indicated power availability, and b.

Demonstrated OPERABLE at least once per l8 month's tiuring shutdown by:

/

1)

Transferring 4 kV vital bus power supply from the normal circuit h j to the alternate circuit (manually and automatically) and to F

V, the delayed access circuit (manually), and 2)

Verifying that on a Safety Injection test signal, without loss of o'ffsite power, the preferred, immediate access offsite power

_j source energizes the emergency busses with permanently connecte V

loads and energizes the auto-connected emergency (accident) loads through sequenci,ng timers.

4.8.1.1.2 Each diesel generator

  • shall be demonstrated OPERABLE:

a.

In accordance with the frequency specified in Table 4.8-1 on a STAGGERED TEST BASIS by:

1)! Verifying the fuel level in the engine-mounted fuel tank, Verifying the diesel starts from ambient condition 'and accelerates to at least 900 rpm in less than or equal to 10 seconds.

The generator voltage and frequency shall be 4160 1 420 volts and 60 1 1.2 Hz within 13 seconds after the start signal.

The y

diesel generator shall be started for this test by using one of V the following signals with startup on each signal verified at b

least once per 92 days:

[

a)

Manual, or b)

Simulated loss of offsite power by itself (Startup busr

.y under voltage), or c)

A Safety Injection actuation test signal by itself.

y 3)

Verifying the generator is synchronized, loaded to greater than

_f or equal to 2484 kW in less than or equal to 60 seconds, and V

operates for greater than or equal to 60 minutes, V

l

  • Diesel Generator 3 is common to both units and need not be testad more frequently than required to satisfy the OPERABILITY requirement for the most limiting unit.

Unit specific portions of this Surveillance Requirement shall be performed on an alternating schedule-from Units 1 and 2.

Testing

)

of Diesel. Generator 3 on one unit does not place the other unit'in an ACTION Statement.

DIABLO CANYON - UNITS 1 AND 2 3/4 8-3

-~

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 4)

Verifying the diesel generator is aligned to provide standby power to the associated emergency busses, and 5)

Verifying the diesel engine protective relay trip cutout switch

')

y is returned to the cutout position following each diesel generator

(

b. <

At least once per 18 months, during shutdown, by:

b h' 1)

Subjecting the diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's y

recommendations for this class of standby service; 2)

Verifying that the load sequence timers are OPERABLE with each load sequence timer within the limits specified in Table 4.8-2; 3)/Verifyingthe.generatorcapabilitytore'jectaloadofgreater than or equal to 508 kW while maintaining voltage at 4160 + 420 V

volts and frequency at 60 + 3 H2;

4) IVerifying the generator capability to reject a load of greater than or equal to 2484 kW without tripping.

The generator L/

voltage shall not exceed 4580 volts during and following the load rejection; 5)

Simulating a loss of offsite power by itself, and:

f a)

Verifying de-energization of.the emergency busses and load shedding from the emergency busses, and b)

Verifying the diesel starts ~on the auto-start signal, energizes the emergency busses with permanently connected 1

ioaos withi %n seconds, energizes the required auto-connected loaTs through sequencing timers and operates for greater than or equal to 5 minutes while its generator i's loaded with the permanent and auto-connected loads.

After 1 energization of these loads, the steady state voltage and l

frequency of the emergency busses shall be maintained at 4160 2 420 volts and 60 i 1.2 Hz during this test.

6)

Verifying that on a Safety Injection test signal without loss of offsite power, the diesel generator starts on the auto-star.t signal and operates on standby for greater than or equal to 5 minutes.

The. generator voltage and frequency shall be

[

4160 t 420 volts and 60 1 1.2 Hz within 13 seconds after the

  • auto-start signal; the steady state generator voltage and frequency shall be maintained within these limits during this test; DIABLO CANYON - UNITS 1 AND 2 3/4 8-4 l

,... - _ _ ~ _ _

l' ELECTRICAL POWER SYSTEMS l2 SURVEILLANCE RE,')UIREMENTS (Continued) 7)

Simulating a loss of offsite power in conjunction with a Safety /

Injection test signal, and:

a)

V'erifying de-energization of the emergency busses and load shedding from the emergency busses; b)

Verifying the diesel starts on the auto-start signal, energizes the emergency busses with permanently connected l

. loads within 10 seconds, energizes the auto-connected emergency (accident) loads through sequencing timers and

/

operates for greater than or equal to 5 minutes while its

\\/

p generator is loaded with the emergency loads. After 5

energization oft these loads, the steady state voltage and j

y t frequency of the emergency busses shall be maintained at

,4160 1 420 volts and 60 2 1.2 Hz during this. test; and l

b c)

Verifying that all automatic diesel generator trips,-except D g

engine overspeed, low lube oil pressure and generator.

f 6

differential, are bypassed when the diesel engine trip cutout

/M g

switchisinthecutoutpositionandthedieselisalignedfor) automatic operation.

8)[ Verifying the diesel generator operates for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

During the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this test, the diesel generator

{.

shall be loaded to greater than 'or equal to 2750 kW and during the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this test, the diesel generator shall be loaded to greater than or equal to 2484 kW.

The generator

[

voltage and frequency shall be 4160 2 420 volts and 60 1 1.2 Hz within 13 seconds after the start signal; the steady state gener-ator voltage and frequency shall be maintained within these limits during this test. Within 5 minutes after completing this 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> test, perform Specification 4.8.1.1._2b.5_)b);"

i 9)

Verifying that the auto-connected loads tg, each diesel generator ing {z QWk

(

do not exceed t enerator's capability-k g

10) Verifying the diese.

I a)

Synchronize its isolated bus with the offsite power source while the generator is. loaded with its emergency loads

_/

upon a simulated restoration of offsite powe'r, V

b)

Transfer its loads to the offsite power source, and c)

Be restored to its standby status.

"If Specification 4.8.1.1.2b.5)b) is not satisfactorily completed, it is not necessary to repeat the preceding 24-hour test.

Instead the diesel generator i

may be operated at 2484 kW for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or until operating temperature has stabilized.

~

DIABLO CANYON - UNITS 1 AND 2 3/4 8-5

3

.i l

ELECTRICAL POWER SYSTEMS SURVEILLANCE' REQUIREMENTS (Continued)

11) Verifying that with the diesel generator operating in a test mode, connected to its bus, a simulated Safety Injection signal opens the auxiliary transformer breaker and automatically sequences the emergency loads onto the diesel generator; and
12) Verifying that the shutdown relay lockout feature prevents g; -

diesel generator starting only when required:

5 a)

Generator differential current-high, or g

t b)

Engine lube oil pressure-low, or

\\*

4 L

c) I Emergency stop button actuated, or d)

Overspeed trip actuated.

[

c.

At least once per 10 years or after any modifications which could affect diesel generator interdependence by starting all diesel generators simultaneously, during shutdown, and verifying that all 1 diesel generators accelerate to at least 900 rps in less than or h

equal to 10 seconds.

4.'8.1.1.3lThe Diesel Fuel Oil Storage and Transfer System shall be demonstrated OPERABLE:

At least once per 31 days by:

1)

Verifyingthefuellevel] nth uegoa tgngpn gg

~

2)

Verifying that each fuel transfer pumpptarts and transfers fuel from the storage system to each engine-mounted tank via installed lines.

b.

At least once per 31 days and after each operation of the diesel where the period of operation was greater than or equal.to I hour by checking for and removing accumulated water from the day tanks; c.

At least once per days by checking for and removing sccumulated water from the fuel oil storage tanks; d.

By sampling new fuel oil in accordance with ASTM-D4057 prior to f

a addition to storage tanks and:

~

1)

By verifying in. accordance with the tests specified in j

j/k ASTM-0975-81 prior to addition to the storage tanks that the

{.< [

sample has:

t g /* f,DIABLO CANYON - UNITS 1 AND 200/p 5

u u. sw.

y4 3/4 8-6

---,-w


a v-w, e,-vwr-1

,,re-e-

,,-em e,r-en--,-,-w--


m e----ww,r---a, m e--,, -, -

- =

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)

}

a)

An API Gravity of within 0.3 degrees at 60*F, or a specific gravity of within 0.0016 at 60/60*F, when compared to the supplier's certificate, or an absolute specific gravity at 60/60*F of greater than or equal to 0.83 but 4

,i less than or equal to 0.89, or'an API gravity of greater j

than or equal to 27 degrees but less than or equal to

.I 39 degrees-I l

f b)

A kinematic viscosity at 40'C of grener than or equal to 1.9 centi. stokes, but less than or equal to 4.1 centistokes, j

I c

if gravity was not determined by comparison with the dA supplier's certification; c)

A flash point equal to or greater than 125'F; and d)

A clear and bright appearance with proper: color when tested in accordance with ASTM-D4176-82.

2)

By verifying within 30 days of obtaining the sample that the other properties specified in Table 1 of ASTM-0975-81 are met i

when tested in accordance with ASTM-D975-81 except that the analysis for sulfur may be performed in accordance with

~

ASTM-D1552-79 or ASTM-02622-82.

e.

At least once every 31 days by obtaining a sample of fuel oil in accordance with ASTM-D2276-78, and verifying that tctal particulate contamination is less than 10 mg/ liter when checked in accordance with ASTM-D2276-78, Method A; f.

At least once per 10 years by:

1)

Draining each fuel oil storage tank, removing the accumulated

[j!

sediment an4 s: leaning the tank using a sodium hypochlorite l

kr q

or equivalent solution, and J'

Performing a visual examination of accessable piping

[ j

(, j

[

operating pressure leak test.

' y 4.8.1.1.4 seports - All diesel generator failures, valid or non-valid, shall be reported as a Special Report within 30 days to the Commission pursuant to Specification 6.9.2.

Reports of diesel generator failures shall include the i

information recommended in Regulatory Position C.3.b of Regulatory Guide 1.108, Revision 1, August 1977.

If the number of-failures (en a per nuclear unit basis) in the last 100 valid tests is greater than or equal to 7, the report shall be supplemented to include the additional information recommended in Reg'ulatory Position C.3.b of Regulatory Guide 1.108, Revision 1, August 1977.

i DIABLO CANYON - UNITS 1 AND 2 3/4 8-7

,-g w

w

--t*--F Mw

-^mg-a-w---

--i,m*v-et-r-n--

w ---

m-

  • --m e-d-e

=*---t-

,W e

TABLE 4.8-1 DIESEL GENERATOR TEST SCHEDULE l

i Number of Failures in Last 100 Valid Tests

  • Test Frequency 51 At least once per 31 days 2

At least once per 14 days 3

At least once per 7 days

>4 At least once per 3 days t

s ACriteria for determining number of failures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide 1.1,08, Revision 1, August 1977, where the last 100 tests are determined on a per nuclear unit basis.

For the purpose of this schedule, only valid tests con-ducted.after the completion of the preoperational test requirements of Rer,'ta-tory Guide 1.108, Revision 1, August 1977, shall be included in the computation of the "Last 100 Valid Tests."

DIABLO CANYON - UNITS 1 AND 2 3/4 8d8

,----y w-m g-.,,-

,,-,m, y

--9

-i ----

-~ -

TABLE 4.8-2a.

LOAD SEQUENCING TIMERS ESF TIMERS

~

TIMER SETTINGS (s)

COMPONENT MINIMUM NOMINAL MAXIMUM 1.

Bus F Centrifugal Charging Pump No. 1 1.5 2

3 Safety Injection Pump No. 1 5

6 7

Containment Fan Cooler Unit No. 2 9

10 11

~

Containment Fan Coo 1er Unit No. 1 13

~ 14 15 Component Cooling Water Pump No. 1 17 18 19.5 j

Auxilia'ry Saltwater Pump No. 1 20.8 22 23.2 Auxiliary Feedwater Pump No. 3 24.5 26 28 2.

Bus G Centrifugal Charging Pump No. 2

1. 5.

2 3

Residual Heat Removal Pump No. 1 5

6 7.5 Containment Fan Cooler Unit No. 3 9

10 11.5 Containment Fan Cooler Unit No. 5 13 14 15 Component Cooling Water Pump No. 2 17 18 19 Auxiliary Saltwater Pump No. 2 20.8 22 23.2 Containment Spray Pump No. 1 24.5 26 28 I

3.

Bus H Safety Injection Pump No. 2 1

2 3

Residual Heat Removal Pump No. 2 5

6 7

Containment Fan Cooler Unit No. 4 9

10 11 Component Cooling Water Pump No. 3 12.5 14

,15 Auxiliary Feedwater Pump No. 2 17 18 19.5 Containment Spray Pump No. 2 20.8 22 23.2 W

9 DIABLO C'ANYON - UNITS 1 AND 2 3/4 8-9 y-+

7

-.p-

p. -.,. >

we p.-m,-.--3+

m

,---y y

n-

-e, - - - - -

-g

.a

.-wy


.,----one-e-----aw,-m--c.wg+--

TABLE 4.8-2b.

LOAD SEOUENCING TIMERS AUTO TRANSFER TIMERS TIMER SETTINGS (s)

COMPONENT-MINIMUM NOMINAL MAXIMUM 1.

Bus F Component Cooling Water Pump No. 1 4

5 6

Auxiliary Saltwater Pump No. 1 9

10 11 Auxiliary Feedwater Pump No. 3 13 14 15 Centrifugal Charging Pump No. I 18.5 20 21.5 v/

Containment Fan Cooler Unit No. 1 23.5 25 27 Containment Fan Cooler Unit No. 2 23.5 25 27 2.

Bus G Component Cooling Water Pump No. 2 4

5 6

7 Auxiliary Saltwater Pump No. 2 9

10 11 Centrifugal Charging Pump No. 2 18.5 20 21.5 Containment Fan Cooler Unit No. 3 23.5 25 27 Containment Fan Cooler Unit No. 5 23.5 25 27 3.

Bus H Component Cooling Water Pump No. 3 4

5 6

Auxiliary Feedwater Pump No. 2 13 14 15 Containment Fan Cooler Unit No. 4 22 25 27 e

e

.e e

DIABLO CANYON - UNITS 1 AND 2 3/4 8-10 4

ELECTRICAL POWER SYSTEMS A.C. SOURCES i

SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.1.2 As a minimum, the following A.C. electrical power sources shall be OPERA 8LE:

a.

One circuit between the offsite transmission network and the Onsite Class 1E Distribution System, and b.

One diesel generator with:

l 1.

An engine-mounted fuel tank containing a minimum volume of 200 gallons of fuel, 2.

A fuel storage system containing a minimum volume of 8000 gallons of fuel, and 3.

A fuel transfer pump.

hr gg4 Tk gMS i

}

APPLICABILITY:

MODES 5 and 6.

ACTION:

i With less than the above minimum required A.C. electrical power sources OPERABLE, immediately suspend all operations hvolving CORE ALTERATIONS, positive reactivity changes, movement of irradiated fuel or crane operations with loads over the fuel storage pool.

In addition, when in MODE 5 with the reactor coolant loops [>

not filled, or in MODE 6 with the water level less than 23 feet above the l

reactor vessel flange, immediately initiate corrective action to restore the required sources to OPERABLE status as soon as possible.

t SURVEILLANCE REQUIREMENTS 4.8.1.2 The above required A.C. electrical power sources shall be demonstrated OPERABLE by the performance of each of the reouirements of Specifications 4.8.1.1.1, 4.8.1 1 S aA1 1 1' and 4 a 1.1.4./Fxcept for Sp cations 4.8.1.1.10.z; ana 8.1.1.2a.2)q), b 2) for ESF timers, b.6), b.7) b.10) and b.11). * ' ~

g ch It" $N ny h.

i e

rnNN \\u spsuS:ss l

S n

l

% % I. \\. 2L,3 DIABLO CANYON - UNITS 1 AND 2 3/4 8-11 8

v.-.ee-

....new.e-,---

  1. m.--

.....,,_..e_.

--twww-g-

-,w.y-m-wr-----m*,ei&e-w deNM-+-en--mwrver-r--em

---w

-vi-t--w'SN-N'=r-Tr~*w+=sm=wwww-ww w w

--*eNm-twwe7 wwWFv--.

,.4"5M'*"JW'*'T

I' h

ELECTRICAL POWER SYSTEMS 3/4.8.2 ONSITE POWER DISTRIBUTION d'

/

\\

OPERATING LIMITING CONDITION FOR OPERATION 3.8.2.1 The following electrical busses shall be energized in the specified manner:

a.

'4160 volt Vital Bus F, b.

480 volt Vital Bus F, c.

4160 volt Vital Bus G, d.

480 volt Vital Bus G, e.

4160 volt Vital Bus H, f.

480 volt Vital Bus H, g.

120 volt Vital Instrument A.C. Bus 1 energized from its associated inverter connected to D.C. Bus 18, h.

120 volt Supplemental Vital Instrument A.C. Bus 1A energized from its associated inverter connected to D.C. Bus 1*,

i.

120 volt Vital Instrument A.C. Bus 2 energized from its associated inverter connecteo to D.C. Bus 28, j.

120 volt Vital Instrument A.C. Bus 3 energized from its associated inverter connected to D.C. Bus 3*,

k.

120 volt Supplemental Vital Instrument A.C. Bus 3A energized from its associated inverter connected to D.C. Bus 3",

1.

120 volt Vital Instrument A.C. Bus 4 energized from its associated inverter connected to D.C. Bus 2*,

M m.

125 volt D.C. E.us 1 energized from Battery Bank 1,

    • 9 125 volt D.C. Bus 2 energized from Ba'tery Bank 2, an t

n.

125voltD.C. Bus *!energizedfromBatteryBank3h o.

APPLICABILITY: MODES 1, 2, 3, and 4.

I ACTION:

a.

With one of the required 4160 volt and/or associated 480 volt vital /

busses not energized, 'e-energize tnem within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at r

least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within i

the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, b.

With one vital instrument A.C. bus not energized from its associated inverter, or with one inverter not connected to its associated 0.C.

bus,re-energizethevitalinstrumentA.C.busfromanalternatesource/

within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be ir, at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />

^Two vital instrument A.C. inverters or one vital and one supplemental vital instrument A.C. inverter may be disconnected from their D.C. busses for up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> for the purpose of performing an equalizing charge on their associated y battery bank provided:

(1) their vital busses are energized, and (2) the vital busses associated with the other battery banks are energized from their associated inverters and connected to their associated D.C. busses.

DIABLO CANYON - UNITS 1 AND 2 3/4 8-12

= - - -

9,,---.-,---,w~y,,--,,y-2-.m-- - - i.,-,,-~--,,. -,

-.----------,._9p,---


e-m------e e -

ge-T-y

Jes e qf ELECTRICAL POWER S STEMS

/

L LIMITING CONDITION FOR OPERATION t

s ACTION (Continued) and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; re en rgize the vital instrument A.C. bus from its associated inverter co lected to

/

its associated D.C. bus within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the fo wing

)

30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

i c.

With one O.C. bus not energized fros its ass y1. Aattery bank)be re-energize it from its associated battery b T. int 2' hours of in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> nd in COLD SHUTDOWN

/

within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

'd With one supplemental vital instrument A.C. bus not energized from sf.

its associated inverter or with its inverter not connected to its b{g f

associated D.C. bus, re-energize the supplemental vital instrument A.C. bus from an alternate source within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY with n the ' ext 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD' SHUTDOWN within the

/

n S

following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; re-energize the supplemental vital instrument M

A.C. bus from its associated inverter connected to its associated 0.C. bus within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the

(

next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.8.2.1 The specified busses shall be determined energized in the required manner at least once per 7 days by verifying correct breaker alignment.and indicated voltage on the busses.

' h,Y l

6Y 1

e me DIABLO CANYON - UNITS 1 AND 2 3/4 8-13 4

- - -. - -. - + -

ELECTRICAL POWER SYSTEMS ONSITE POWER DISTRIBUTION SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.2.2 As a minimum, the following electrical busses shall be energized in the specified manner:

a.

One 4160-volt and its associated 480-volt A.C. vital bus, Two 120-volt vital instrument A.C. busses and one 120-volt supplemental [

b.

vital instrument A.C. bus energized from their associated inverters connected, to their respective D.C. busses, and c.

One 125-volt D.C. bus energited from its associated battery bank. Q [4l{.c Qr Q

$ 4gh APPLICABILITY: MODES 5 and 6.

ACTION:

With any of the above required electrical busses not energized in the required y

manner, immediately suspend all operations involving CORE ALTERATIONS, positive j

reactivity changes, or movement of irradiated fuel, initiate corrective action f

to energize the required electrical busses in the specified manner as soon as j

possible. Q g ;g g Kppy g g,4 n?h Q Q Q kL$ hr9h 41 Sg&+ IN V p

i SURVEILLANCE REQUIREMENTS i

4.8.2.2 The specified busses shall be determined energized in the required

,/

manner at least once per 7 days by verifying correct breaker alignment and v

indicated voltage on the busses.

e e

se p

DIABLO CANYON - UNITS 1 AND 2 3/4 8-14 T -

illi. TIli -.i~.

l

t L

i ELECTRICAL POWER SYSTEMS.

~

3/4.8.3 D.C. SOURCES OPERATING l

LIMITING CONDITION FOR OPERATION 3.8.3.1 The fnllowing D.C. electrical sources shall be OPERABLE:

a.

125-volt D.C. Battery No.1 and an associated full-capacity charger, r'

j b.

125-volt D.C. Battery No. 2 and an associated full-capacity charger, and c.

125-volt D.C. Battery No. 3 and an associated full-capacity charger.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTION:

With one of the required battery banks and/or full-capacity chargers inoperable, f

restore the inoperable battery bank and/or full-capacity charger to OPERA 8LE

/

status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STAND 8Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.8.3.1 Each 125-volt battery bank and charger shall be demonstrated ' OPERABLE:

a.

At least once per 7 days by verifying that:

I 1)

The parameters in Table 4.8-3 meet the Category A limits, and 2)

The total battery terminal voltage is greater than or equal to 130-volts on float charge.

e e

O 4

e 9

t O

DIABLO CANYON - UNITS 1 AND 2 3/4 8-15

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) b.

At least once per 92 days and within 7 days after a battery discharge y

- with D.C. bus voltage below 118 volts, or battery overcharge with

,V D.C. bus voltage above 145 volts, by:

1)

Verifying that the parameters in Table 4.8-3 meet the Category B

limits, 2)

Verifying there is no visible corrosion at either terminals or 1

con s, or the connection resistance of these items is less tha 10 8 ohn,.and 19 q ' 3)

Verifying t' hat the average electrolyte temperature of 10 of the y#-

connected cells is above 60*F.

0 $

c.

At least once per 18 months by verifying that:

1)

The cells, cell plates and battery racks.show no yisual indication of physical damage or abnormal deterioration, 2)

The cell-to-cell and terminal connections are clean, tight,.and I

coated with anticorrosion material,

~

3)

The resistance of each c 11-to-cell and teminal connection is less than or equal t x 10 8 ohns, and 4)

The battery charger will suppl t least 400 amperes at 130 volts for at least 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

d.

At least once per 18 months, during s utdown, by verifying that the battery capacity is adequate to supply and maintain in OPERABLE status all of the actual and/or simulated emergency loads for the design duty cycle when the battery is subjected to a battery service test; e.

At least once per 60 months, during shutdown, by verifying that the battery capacity is at least 80% of the manufacturer's rating whenTh subjected to a performance discharge test.

test may be performed in lieu of the battery service test required by Specification 4.8.3.1d.; and f.

At least once per 18 months during shutdown, by giving performance discharge tests of battery capacity to any battery that shows signs

/

of degradation or has reached 85% of the service life expected for the application.

Degradation is indicated when the battery capacity drops more than 10% of rated capacity from its average on previous performance tests, or is below 90% of the manufacturer's rating.

1 i

DIABLO CANYON - UNITS 1 AND 2 3/4 8-16

-- =

--q-,---

r--

yw r-T-e t-**%W--y-wt+--+ ppa-++

  • Py--

q--ge---y n-ggwa s p---p r+y--t-=w-v-

- - - - -wgwyd.m y r e wwynee. c v mmg & w w o w,-wcy*

y-p+

en--'wg--,-e---pe.r=*

t TABLE 4.8-3

-l l

BATTERY SURVEILLANCE REQUIREMENTS CATEGORY A(1)

CATEGORY B(2) i PARAMETER LIMITS FOR EACH LIMITS FOR EACH ALLOWABLE (3) i DESIGNATED PILOT CONNECTED CELL VALUE FOR EACH CELL CONNECTED CELL I

Electrolyte

> Minimum level

> Minimum level Above top of 4

i Level indication mark, indication mark,

plates, j!

and < %" above and < %" above.

and not maxiium level maximum level overflowing

{

indication mark indication mark Float Voltage

> 2.13 volts

> 2.13 volts (6) 3 2.07 volts Not more than 0.020 below the average of all 1

~

j-Specific

> 1.195(5)

Gravity (4)

Average of all Average of all connected cells connected cells

> 1.200

> 1.19,0(5) i I

(1) For any Category A parameter (s) outside the limit (s) shown, the battery may be considered OPERABLE provided that within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> all the Category B J

measurements are taken and found to be within their allowable values, and provided all Category A and B parameter (s) are restored to within limits within the next 6 days.

(2) For any Category B parameter (s) outside the limit (s) shown, the batte"ry may be considered OPERABLE provided that the Category B parameters are within their allowable values and provided the Category B parameter (s) are l

restored to within limits within 7 days.

1 (3) Any Category B parameter not within its allowable value indicates an inoperable battery.

(4) Corrected for electrolyte temperature and level.

(53Orbatterychargingcurre.ntislesst'ha[ amps)henoncharge.

T6) Corrected for average electrolyte temperature.

J

@#.,3 DIABLO CANYON - UNITS 1 AND 2 3/4 8-17 4

l

l..---

ELECTRICAL POWER SYSTEMS D.C. SOURCES SHUTDOWN LIMITING CONDITION FOR OPERATION l

3.8.3.2 As a minimum, one 125-volt battery bank and an associated full-capacity charger shall be OPERABLE.

g fj APPLICABILITY:

MODES 5 and 6.

W ACTION:

With the required battery bank and/or full-capacity charger inoperable, immedi-ately suspend all operations involving CORE ALTERATIONS, positive reactivity

_/

changes or movement'of irradiated fuel; initiate corrective action to restore V

3'g the required battery bank and/or full-capacity charger to OPERABLE status as

, soon as possible. M g

I A

h Mres 4 ss L Span M nJ,

i SURVEILLANCE REQUIREMENTS 4.8.3.2 The above required 125-volt battery bank and charger shall be demonstrated OPERABLE in accordance with Specification 4.8.3.1.

i

)

O DIABLO CANYON - UNITS 1 AND 2 3/4 8-18 i

.g

11. } gs g#

^

ELECTRICAL POWER SYSTEMS 3/4.8.4 ELECTRICAL EQUIPMENT PROTECTIVE DEVICES MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION AND BYPASS DEVICES LIMITING CONDITION FOR OPERATION 3.8.4.1 The thermal overload protection and bypass devices, integral with the motor starter, of each valve listed in Table 3.8-1 shall be OPERABLE.

W APPLICABILITY: Whenaver the motor-operated valve is required to be OPERABLE.

ACTION:

With one or more of the thermal overload protection and/or bypass devices inoperable, declare;the affected valve (s) inoperable and apply the appropriate

/

ACTION Statement (s) for the affected valves.

SURVEILLANCE REQUIREMENTS 4.8.4.1 The above required thermal overload protection and bypas.s devices shall be demonstrated OPERABLE:

@ p / s. N M fj I

At least once per 18 months, by the performance of aff"""^L 7"

a.

-F#NCTTURAt. TEST of the bypass circuitry for those thermal overload g

L devices which are either:

- 1)

Continuously bypassed and temporarily.placed in force only when y

the valve motors are undergoing periodic or maintenance ~ testing, or

/

2)

Normally in force during plant operation and bypassed under accident conditions.

b.

At least once per 18 months by the performance of a CilANNEL CALIBRATION 7

of a representative sample of at least 25% of:

1)

All thermal overload devices which are not bypassed, such that each non-bypassed device is calibrated at least once per 6 years, and g

2)

All thermal overload devices which are continuously bypassed, M

o such that each continuously bypassed device is calibrated and s.

A each valve is cycled through at least one complete cycle of C

g,

. full travel w.ith the motor-operator when the thermal overload device is OPERABLE and not bypass,ed at least once per 6 years.

DIABLO CANYON - UNITS 1 AND 2 3/4 8-19

TABLE 3.8-1 MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION AND BYPASS DEVICES BYPASS DEVICE VALVE NUMBER FUNCTION (YES/NO) 8107 Charging Isolation Yes 8105 Charging Pumps' Recirculation Yes FCV-430 Component Cooling Heat Exch. Outlet No LCV-1128 Volume Control Tank Outlet Yes 8801A Baron Injection Tank Outlet Yes 8803A Boron Injection Tank Inlet Yes 8807A Safety Injection / Charging Suction Crosstie No 8805A

' RWST to Charging Pumps Yes FCV-437 Raw Water Supply to Auxiliary Feedpumps No FCV-441 SG 4 Feedwater Isolation Yes FCV-750 RCP Thermal Barrier CCW Return Yes FCV-438 SG 1 Feedwater Isolation Yes 8923A SI Pump 1 Suction No FCV-38 Aux. FWP Turb. Steam Supply No 8980 RWST to RHR No 8974A SI Pumps' Recirculation No 8992 Spray Additive Tank Outlet '

Yes 8000A Pressurizer RV isolation No FCV-601 Auxiliary Saltwater Pumps Crosstie No 8808A Accumulator No. 1 Isolation No 8802A SI Pump 1 to Hot Leg No 8821A SI Pump 1 to Cold Legs No 88080 Accumulator 4 Isolation No 8808B Accumulator 2 Isolation No 8106 Charging Pumps' Recirculation Yes 8108 Charging Isolation Yes LCV-112C Volume control Tank Isolation Yes 9

4

~

DIABLO CANYON - UNITS 1 AND 2 3/4 8-20

,m.

m,--.

.--,_w

%g.-

y..

,.9

_.m c-9 3

..-,9,y-,,-,,.y

.,,,y,9 mp9..

g9-9-

p._,_

TABLE 3.8-1 (Continued)

MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION AND BYPASS DEVICES BYPASS DEVICE VALVE NUMBER FUNCTION (YES/NO) 8809A RHR to Cold Legs No 88018 Boron Injection Tank Outlet Yes 8805B RWST to Charging Pumps Yes 8700A RHR Pump 1 Suction No 8804A RHR to Charging Pumps No FCV-436 RWSR to Auxiliary Feedpump No i

9001A

, Spray Isolation Yes l

FCV-363

'RCP CCW Return Isolation Yes 8835 SI Pumps to RCS Cold Legs No j

8701 RCS to RHR System No 8100 RCP Seal Water Return Yes j

8803B Boron Injection Tank Inlet Yes FCV-431 CCW Heat Ex;; hanger Outlet No FCV-641A RHR Recirculation No 8716A RHR to Hot Legs No 80008 Pressurizer RV Isolation No FCV-439 S/G 2 Feedwater Isolation Yes 9003A RHR to Spray No FCV-95 Turb. Feedpump Steam Supply Yes 8994A Spray Additive Tank Outlet Yes 8703 RHR to Hot Legs No 8104 Emergency Borate No 8982A Containment Sump RHR Recirculation No LCV'-106 S/G 1 Aux. Feedwater Supply-No 4

LCV-107 S/G 2 Aux. Feedwater Supply No LCV-108 S/G 3 Aux. Feedwater Supply No LCV-109 S/G 4 Aux. Feedwater Supply No i

i

{

DIABLO CANYON - UNITS 1 AND 2 3/4 8-21

'I.

.~.

TABLE 3.8-1 (Continued)

MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION AND BYPASS DEVICES BYPASS DEVICE VALVE NUMBER FUNCTION-(YES/NO)

FCV-356 RCP CCW Supply Isolation Yes

^

I 8808C Accumulator 3 Isolation i

No FCV-641B RHR Recirculation No FCV-355 CCW Header C Isolation Yes l

90018 Spray Isolation Yes 89828

~ ~

Containment Sump RHR Recirculation No l

9003B RHR to Spray No 8976 tRWST to SI Pumps No j

88048 RHR to SI Pumps No l

8802B SI Pump 2 to Hot Legs No 8112 RCP Seal Water Return Isolation Yes FCV-357 RCP Barrier CCW Return Isolation Yes FCV-749 RCP Bearing Cooling H O Return Isolation 8702 RCS to RHR Suction

_ Yes 2

No FCV-440 S/G 3 Feedwater Isolation Yes 87168 RHR to RCS Hot Legs No FCV-37 Aux. Feedpump Steam Supply No 88218 - -

SI Pump 2 to Cold Legs No 88078 Safety Injection / Charging Suction Crosstie No 8000C Pressurizer RV Isolation No 89948 Spray Additive Tank Outlet Yes FCV-495 ASW Crosstie No FCV-496 ASW Crosstie No 87008 RHR Pump 2 Suction No 89748 SI Pumps Recirculation No 8809B RHR to Cold Legs No 8923B SI Pump 2 Suction No

?

t DIABLO CANYON - UNITS 1 AND 2 3/4 8-22

  • =*+*-e m.. _

.m

.w.