MONTHYEARHL-5845, Monthly Operating Repts for Sept 1999 for Ei Hatch Nuclear Plant.With1999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Ei Hatch Nuclear Plant.With HL-5836, Monthly Operating Repts for Aug 1999 for Edwin I Hatch Nuclear Plant.With1999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Edwin I Hatch Nuclear Plant.With HL-5818, Monthly Operating Repts for July 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With1999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5805, Monthly Operating Repts for June 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With1999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5795, Monthly Operating Repts for May 1999 for Ehnp Units 1 & 2. with1999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Ehnp Units 1 & 2. with HL-5784, Monthly Operating Repts for Apr 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With1999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5766, Monthly Operating Repts for Mar 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With1999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5755, Monthly Operating Repts for Feb 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With1999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5726, Monthly Operating Repts for Dec 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With1998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5714, Monthly Operating Repts for Nov 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With1998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5706, Monthly Operating Repts for Oct 1998 for Hatch Nuclear Plant Units 1 & 2.With1998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Hatch Nuclear Plant Units 1 & 2.With HL-5691, Monthly Operating Repts for Sept 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With1998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5675, Monthly Operating Repts for Aug 1998 for Ei Hatch Nuclear Plant,Units 1 & 21998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5667, Monthly Operating Repts for July 1998 for Ei Hatch Nuclear Plant,Units 1 & 21998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5653, Monthly Operating Repts for June 1998 for Ei Hatch Nuclear Plant,Units 1 & 21998-06-30030 June 1998 Monthly Operating Repts for June 1998 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5640, Monthly Operating Repts for May 1998 for Ei Hatch Nuclear Plant,Units 1 & 21998-05-31031 May 1998 Monthly Operating Repts for May 1998 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5628, Monthly Operating Repts for Apr 1998 for Ei Hatch Nuclear Plant1998-04-30030 April 1998 Monthly Operating Repts for Apr 1998 for Ei Hatch Nuclear Plant HL-5604, Monthly Operating Repts for Mar 1998 for Edwin I Hatch Nuclear Plant,Units 1 & 21998-03-31031 March 1998 Monthly Operating Repts for Mar 1998 for Edwin I Hatch Nuclear Plant,Units 1 & 2 HL-5585, Monthly Operating Repts for Feb 1998 for Ei Hatch Nuclear Plant,Units 1 & 21998-02-28028 February 1998 Monthly Operating Repts for Feb 1998 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5571, Monthly Operating Repts for Jan 1998 for Edwin I Hatch Nuclear Plant,Unit 11998-01-31031 January 1998 Monthly Operating Repts for Jan 1998 for Edwin I Hatch Nuclear Plant,Unit 1 HL-5551, Monthly Operating Repts for Dec 1997 for Ei Hatch Nuclear Plant,Units 1 & 21997-12-31031 December 1997 Monthly Operating Repts for Dec 1997 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5533, Monthly Operating Repts for Nov 1997 for Ei Hatch Nuclear Plant,Units 1 & 21997-11-30030 November 1997 Monthly Operating Repts for Nov 1997 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5514, Monthly Operating Repts for Oct 1997 for Edwin I Hatch Nuclear Plant,Units 1 & 21997-10-31031 October 1997 Monthly Operating Repts for Oct 1997 for Edwin I Hatch Nuclear Plant,Units 1 & 2 HL-5493, Monthly Operating Repts for Sept 1997 for Ei Hatch Nuclear Plant1997-09-30030 September 1997 Monthly Operating Repts for Sept 1997 for Ei Hatch Nuclear Plant HL-5475, Monthly Operating Repts for Aug 1997 for Ei Hatch Nuclear Plant,Units 1 & 21997-08-31031 August 1997 Monthly Operating Repts for Aug 1997 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5447, Monthly Operating Repts for July 1997 for Edwin I Hatch Nuclear Plant,Units 1 & 21997-07-31031 July 1997 Monthly Operating Repts for July 1997 for Edwin I Hatch Nuclear Plant,Units 1 & 2 HL-5416, Monthly Operating Repts for May 1997 for Ei Hatch Nuclear Plant Units 1 & 21997-05-31031 May 1997 Monthly Operating Repts for May 1997 for Ei Hatch Nuclear Plant Units 1 & 2 HL-5393, Monthly Operating Repts for Apr 1997 for Ei Hatch Nuclear Plant Units 1 & 21997-04-30030 April 1997 Monthly Operating Repts for Apr 1997 for Ei Hatch Nuclear Plant Units 1 & 2 HL-5364, Monthly Operating Repts for Mar 1997 for Ei Hatch Npp,Units 1 & 21997-03-31031 March 1997 Monthly Operating Repts for Mar 1997 for Ei Hatch Npp,Units 1 & 2 HL-5332, Monthly Operating Repts for Feb 1997 for Ei Hatch Nuclear Plant1997-02-28028 February 1997 Monthly Operating Repts for Feb 1997 for Ei Hatch Nuclear Plant HL-5314, Monthly Operating Repts for Jan 1997 for Ei Hatch Nuclear Plant1997-01-31031 January 1997 Monthly Operating Repts for Jan 1997 for Ei Hatch Nuclear Plant HL-5296, Monthly Operating Repts for Dec 1996 for Ei Hatch Nuclear Plant,Units 1 & 21996-12-31031 December 1996 Monthly Operating Repts for Dec 1996 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5283, Monthly Operating Repts for Nov 1996 for Edwin I Hatch Nuclear Plant,Unit 1 & 21996-11-30030 November 1996 Monthly Operating Repts for Nov 1996 for Edwin I Hatch Nuclear Plant,Unit 1 & 2 HL-5265, Monthly Operating Repts for Oct 1996 for Ei Hatch Nuclear Plant Units 1 & 21996-10-31031 October 1996 Monthly Operating Repts for Oct 1996 for Ei Hatch Nuclear Plant Units 1 & 2 HL-5249, Monthly Operating Repts for Sept 1996 for Ei Hatch Nuclear Plant Unit 1 & 21996-09-30030 September 1996 Monthly Operating Repts for Sept 1996 for Ei Hatch Nuclear Plant Unit 1 & 2 HL-5237, Monthly Operating Repts for Aug 1996 for Ei Hatch Nuclear Plant Units 1 & 21996-08-31031 August 1996 Monthly Operating Repts for Aug 1996 for Ei Hatch Nuclear Plant Units 1 & 2 ML20116J3821996-07-31031 July 1996 Monthly Operating Repts for Jul 1996 for Ei Hatch Nuclear Plant Units 1 & 2 HL-5202, Monthly Operating Repts for June 1996 for Ei Hatch Nuclear Plant Units 1 & 21996-06-30030 June 1996 Monthly Operating Repts for June 1996 for Ei Hatch Nuclear Plant Units 1 & 2 ML20112J0661996-05-31031 May 1996 Monthly Operating Repts for May 1996 for Ehnp ML20116J3971996-05-31031 May 1996 Revised MOR for May 1996 for Ei Hatch Nuclear Plant Unit 1 ML20112J0691996-04-30030 April 1996 Revised MOR for April 1996 for Ei Hatch Nuclear Plant ML20116J3901996-04-30030 April 1996 Revised MOR for April 1996 for Ei Hatch Nuclear Plant Unit 1 ML20111B0061996-04-30030 April 1996 Monthly Operating Repts for April 1996 for Ei Hatch Nuclear Plant HL-5144, Monthly Operating Repts for Mar 1996 for Ei Hatch Nuclear Plant1996-03-31031 March 1996 Monthly Operating Repts for Mar 1996 for Ei Hatch Nuclear Plant ML20111B0131996-03-31031 March 1996 Revised Pages E2-4 for March 1996 for Ei Hatch Nuclear Plant Unit 2 ML20101B1911996-02-29029 February 1996 Monthly Operating Repts for Feb 1996 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5111, Monthly Operating Repts for Jan 1996 for Ei Hatch Nuclear Plant1996-01-31031 January 1996 Monthly Operating Repts for Jan 1996 for Ei Hatch Nuclear Plant ML20101B2001996-01-31031 January 1996 Revised Page E1-2 for Monthly Operating Rept for Jan 1996 for Ei Hatch Unit 1 HL-5098, Monthly Operating Repts for Dec 1995 for Ei Hatch Nuclear Plant1995-12-31031 December 1995 Monthly Operating Repts for Dec 1995 for Ei Hatch Nuclear Plant HL-5085, Monthly Operating Repts for Nov 1995 for Ei Hatch Nuclear Plant1995-11-30030 November 1995 Monthly Operating Repts for Nov 1995 for Ei Hatch Nuclear Plant 1999-09-30
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20217D3061999-10-13013 October 1999 SER Accepting Licensee Proposed Changes to Edwin I Hatch Nuclear Plant Emergency Classification Scheme to Add Emergency Action Levels Related to Operation of Independent Spent Fuel Storage Installation HL-5845, Monthly Operating Repts for Sept 1999 for Ei Hatch Nuclear Plant.With1999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Ei Hatch Nuclear Plant.With ML20217A1691999-09-22022 September 1999 Part 21 Rept Re Engine Sys,Inc Controllers,Manufactured Between Dec 1997 & May 1999,that May Have Questionable Soldering Workmanship.Caused by Inadequate Personnel Training.Sent Rept to All Nuclear Customers ML20212A6641999-09-13013 September 1999 Safety Evaluation Authorizing Relief Request RR-V-16 for Third 10 Yr Interval Inservice Testing Program HL-5836, Monthly Operating Repts for Aug 1999 for Edwin I Hatch Nuclear Plant.With1999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Edwin I Hatch Nuclear Plant.With ML20210J9631999-08-0202 August 1999 SER Finding That Licensee Established Acceptable Program to Verify Periodically design-basis Capability of safety-related MOVs at Edwin I Hatch Nuclear Plant,Units 1 & 2 ML20210J9271999-08-0202 August 1999 SER Finds That Licensee Performed Appropriate Evaluations of Operational Configurations of safety-related power-operated Gate Valves to Identify Valves at Plant,Susceptible to Pressure Locking or Thermal Binding HL-5818, Monthly Operating Repts for July 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With1999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5805, Monthly Operating Repts for June 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With1999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With ML20207E7631999-06-0303 June 1999 Safety Evaluation Concluding That Licensee Proposed Alternative to Use Code Case N-509 Contained in RR-4 Provides Acceptable Level of Quality & Safety.Considers Rev 2 to RR-4 & RR-6 Acceptable HL-5795, Monthly Operating Repts for May 1999 for Ehnp Units 1 & 2. with1999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Ehnp Units 1 & 2. with ML20206G1691999-05-0404 May 1999 SER Approving Requirements of Istb 4.6.2(b) Pursuant to 10CFR50.55a(a)(3)(ii) HL-5784, Monthly Operating Repts for Apr 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With1999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5766, Monthly Operating Repts for Mar 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With1999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With ML20207M1891999-03-11011 March 1999 SER Accepting Relief Request for Authorization of Alternative Reactor Pressure Vessel Exam for Circumferential Weld HL-5755, Monthly Operating Repts for Feb 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With1999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Ei Hatch Nuclear Plant,Units 1 & 2.With ML20206P6981999-01-0707 January 1999 Ehnp Intake Structure Licensing Rept HL-5726, Monthly Operating Repts for Dec 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With1998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With ML20196J4931998-12-0707 December 1998 Safety Evaluation Accepting Proposed Alternatives in Relief Requests RR-V-12,RR-V-15,RR-P-15,RR-V-7,RR-V-12,RR-V-14 & RR-V-15 HL-5714, Monthly Operating Repts for Nov 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With1998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With HL-5706, Monthly Operating Repts for Oct 1998 for Hatch Nuclear Plant Units 1 & 2.With1998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Hatch Nuclear Plant Units 1 & 2.With ML20155B6121998-10-28028 October 1998 Safety Evaluation of TR SNCH-9501, BWR Steady State & Transient Analysis Methods Benchmarking Topical Rept. Rept Acceptable HL-5691, Monthly Operating Repts for Sept 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With1998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for Ei Hatch Nuclear Plant,Units 1 & 2.With ML20153G2481998-09-24024 September 1998 SE Concluding That Licensee Implementation Program to Resolve USI A-46 at Plant Adequately Addressed Purpose of 10CFR50.54(f) Request ML20239A2531998-09-0303 September 1998 SER Accepting Licensee Request for Relief Numbers RR-17 & RR-18 for Edwin I Hatch Nuclear Plant,Units 1 & 2.Technical Ltr Rept on Third 10-year Interval ISI Request for Reliefs for Plant,Units 1 & 2 Encl HL-5675, Monthly Operating Repts for Aug 1998 for Ei Hatch Nuclear Plant,Units 1 & 21998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for Ei Hatch Nuclear Plant,Units 1 & 2 ML20238F7131998-08-31031 August 1998 9,change 2 to QAP 1.0, Organization HL-5667, Monthly Operating Repts for July 1998 for Ei Hatch Nuclear Plant,Units 1 & 21998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5657, Ro:On 980626,noted That Pami Channels Had Been Inoperable for More than Thirty Days.Cause Indeterminate.Licensee Will Replace Automatic Function W/Five Other Qualified Pamis of Like Kind in Drywell & Revised Procedures1998-07-30030 July 1998 Ro:On 980626,noted That Pami Channels Had Been Inoperable for More than Thirty Days.Cause Indeterminate.Licensee Will Replace Automatic Function W/Five Other Qualified Pamis of Like Kind in Drywell & Revised Procedures ML20236W3441998-07-30030 July 1998 Safety Evaluation Accepting Relief Requests for Second 10-yr ISI for Plant,Units 1 & 2 ML20236V5191998-07-28028 July 1998 Safety Evaluation Accepting Proposed License Amend Power Uprate Review ML20236N6751998-07-0909 July 1998 Part 21 & Deficiency Rept Re Notification of Potential Safety Hazard from Breakage of Cast Iron Suction Heads in Apkd Type Pumps.Caused by Migration of Suction Head Journal Sleeve Along Lower End of Pump Shaft.Will Inspect Pumps ML20236L1821998-07-0707 July 1998 Safety Evaluation Accepting 980428 Proposed Alternative to ASME Boiler & Pressure Vessel Code,Section Xi,Repair & Replacement Requirements Under 10CFR50.55a(a)(3) HL-5653, Monthly Operating Repts for June 1998 for Ei Hatch Nuclear Plant,Units 1 & 21998-06-30030 June 1998 Monthly Operating Repts for June 1998 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5640, Monthly Operating Repts for May 1998 for Ei Hatch Nuclear Plant,Units 1 & 21998-05-31031 May 1998 Monthly Operating Repts for May 1998 for Ei Hatch Nuclear Plant,Units 1 & 2 ML20248B8651998-05-15015 May 1998 Quadrennial Simulator Certification Rept HL-5628, Monthly Operating Repts for Apr 1998 for Ei Hatch Nuclear Plant1998-04-30030 April 1998 Monthly Operating Repts for Apr 1998 for Ei Hatch Nuclear Plant HL-5604, Monthly Operating Repts for Mar 1998 for Edwin I Hatch Nuclear Plant,Units 1 & 21998-03-31031 March 1998 Monthly Operating Repts for Mar 1998 for Edwin I Hatch Nuclear Plant,Units 1 & 2 ML20216B2711998-02-28028 February 1998 Extended Power Uprate Safety Analysis Rept for Ei Hatch Plant,Units 1 & 2 HL-5585, Monthly Operating Repts for Feb 1998 for Ei Hatch Nuclear Plant,Units 1 & 21998-02-28028 February 1998 Monthly Operating Repts for Feb 1998 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5571, Monthly Operating Repts for Jan 1998 for Edwin I Hatch Nuclear Plant,Unit 11998-01-31031 January 1998 Monthly Operating Repts for Jan 1998 for Edwin I Hatch Nuclear Plant,Unit 1 HL-5551, Monthly Operating Repts for Dec 1997 for Ei Hatch Nuclear Plant,Units 1 & 21997-12-31031 December 1997 Monthly Operating Repts for Dec 1997 for Ei Hatch Nuclear Plant,Units 1 & 2 ML20199B0561997-12-31031 December 1997 Rev 0 GE-NE-B13-01869-122, Jet Pump Riser Weld Flaw Evaluation Handbook for Hatch Unit 1 HL-5581, Annual Operating Rept for 1997, for Ei Hatch Nuclear Plant Units 1 & 21997-12-31031 December 1997 Annual Operating Rept for 1997, for Ei Hatch Nuclear Plant Units 1 & 2 HL-5533, Monthly Operating Repts for Nov 1997 for Ei Hatch Nuclear Plant,Units 1 & 21997-11-30030 November 1997 Monthly Operating Repts for Nov 1997 for Ei Hatch Nuclear Plant,Units 1 & 2 HL-5514, Monthly Operating Repts for Oct 1997 for Edwin I Hatch Nuclear Plant,Units 1 & 21997-10-31031 October 1997 Monthly Operating Repts for Oct 1997 for Edwin I Hatch Nuclear Plant,Units 1 & 2 ML20212A1981997-10-16016 October 1997 Safety Evaluation Denying Licensee Request for Relief from Implementation of 10CFR50.55a Requirements Re Use of 1992 Edition of ASME Code Section XI for ISI of Containments ML20211M6491997-10-0808 October 1997 Addenda 1 to Part 21 Rept Re Weldments on Opposed Piston & Coltec-Pielstick Emergency stand-by Diesel gen-set lube-oil & Jacket Water Piping Sys.Revised List of Potentially Affected Utils to Include Asterisked Utils,Submitted ML20211H5311997-10-0101 October 1997 Rev 2 to Unit 1,Cycle 17 Colr ML20211H5251997-10-0101 October 1997 Rev 3 to Unit 1,Cycle 17 Colr 1999-09-30
[Table view] |
Text
-- -. _ -_ -
l OPERATING DATA REPORT 9
DOCKET NO. 50-321 -
DATE 10-03-86 COMPLETED BY: J. H. Richardson TELEPHONE (912) 367-7781 x 2360 OPERATING STATUS
- 1. Unit Name: E. I. Hatch Nuclear Plant Unit 1 2 Reporting Period: 09-86
- 3. Licensed Thermal Power (MWt): 2436
- 4. Nameplate Rating (Gross MWe): 809.3
- 5. Design Electrical Rating (Net MWe): 777.3
- 6. Maximum Dependable Capacity (Gross MWe): 801.2
- 7. Maximum Dependable Capacity (Net MWe): 768.0
- 8. If changes occur in capacity ratings (Items Number 3 through 7) since last report, give reasons: N/A
- 9. Power level to which restricted, if any (Net MWe): No restrictions
- 10. Reasons for restrictions, if any: N/A This Month Yr-to-Date Cumulative
- 11. Hours In Reporting Period 720 6551 94222
- 12. Number of Hours Reactor was Critical 663.6 3443.2 65569.4
- 13. Reactor Reserve Shutdown Hours 0 0 0
- 14. Hours Generator On-Line 645.1 3133.0 61694.1
- 15. Unit Reserve Shutdown Hours 0 0 0
- 16. Gross Thermal Energy Generated (MWH) 1515578 7133354 131764844
- 17. Gross Electrical Energy Generated (MWH) 488110 2288340 42530470
- 18. Net Electrical Energy Generated (MWH) 465300 2160652 40374740
- 19. Unit Service Factor (%) 89.6% 47.8%- 65.5%
- 20. Unit Availability Factor (%) 89.6% -
47.8% 65.5%
- 21. Unit Capacity Factor (% Using MDC Net) 84.1% 42.9% 57.2%
- 22. Unit Capacity Factor (% Using DER Net) 83.1% 42.4% 54.8%
- 23. Unit Forced Outage Rate 0.0% 5.2% 16.9%
- 24. Shutdowns scheduled over next 6 months (Type, Date, and Duration of Each): N/A
- 25. If shutdown at end of report period, estimated date of startup: N/A
- 26. Units in Test Status (Prior to Commercial Operation): N/A
~
w
/ ,e E-2 8701060339 860930 "
DR ADOCK 05000321 PDR
_ _ . - . -- ~. . .. . . . . . _ . . - . - . . .. . - - . . -. . -. .. ... - . . - - , = . . .
! AVERAGE DAILY UNIT POWER LEVEL J
DOCKET NO. 50-321 1 DATE: ' 10-05-86 I COMPLETED BY: J. H. Richardson i TELEPHONE (912) 367-7781 x 2360 MONTH: SEPTEMBER 86 s
DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net) (MWe-Net)
. 1 753 17 591 3 2 752 78 730 3 751 19 749 4
4 748 20 744 5 748 21 725
- 6 747 22 750 i
. 7 753 23 750 8 753 24 750 i 9 751 25 747 l 10 746 26 747 1 11 752 27 747
- 12 700 28 749 j 13 0 29 745 ,
i 14 0 30 745
, 15 0
} 16 216 i
1 l
,I i
i l
t E-3 -
/ .
UNXT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-321 UNIT NAME HATCH ONE COMPLETED BY J. H. Richardson TELEPHONE (912) 367-7781 (2360) DATE OCTOBER 01, 1986 REPORT MONTH SEPTEMBER 1986 R S E Y T A METHOD OF LICENSEE SC Y S SHUTTING EVENT TO CAUSE & CORRECTIVE P DURATION O DOWN REPORT ED COMPONENT ACTION TO NO. DATE E (HOURS) N REACTOR NUMBER ME CODE PREVENT RECURRENCE 86-035 860906 S 1.92 B 5 N/A HA TURBIN Load reduction for weekly turbine testing 86-036 860912 S 4.43 A 5 N/A CI VALVEX Reducing power for shutdown to repair leakage inside drywell.86-037 860913 S 74.95 A 2 N/A CI VALVEX Shutdown to repair leakage inside drywell.86-038 860916 S 61.30 A 5 N/A CI VALVEX Ramping in power from shutdown.86-039 860920 S 14.03 B 5 N/A HA TURBIN Load reduction for weekly turbine test and rod pattern adjustment.86-040 860927 S 1.05 B 5 II/A HA TURBIN Load reduction for weekly turbine test F: Forced Reason: Method: Events reported involve S: Scheduled A-Equipment Failure (Explain) 1-Manual a greater than 20% reduction B-Maintenance or Test 2-Manual Scram in average daily power level C-Refueling 3-Automatic Scram for the preceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
D-Regulatory Restriction 4-Continuations E-Operator Training & License 5-Load Reduction Examination 9-Other (Explain)
F-Administrative G-Operational Error (Explain)
H-Other (Explain)
E-4
NARRATIVE REPORT UNIT 2 September 1st 0000 Unit critical, in start-up, following I scram on 8/29/86. l 1713 Unit tied to line.
l 1807 Turbine trip on MSR high level, due to l
transmitter problems (no scram). '
1852 Unit tied to line.
September 2nd 0154 Unit off line to repair EHC oil system.
1603 Unit tied to line.
l September 3rd 0352 Reactor scram on turbine stop valve fast closure due to leak in EHC oil system.
0904 Unit start-up in progress.
1100 Reactor critical.
September 4th 0015 Reactor scram on low water level, due to RFPT trip on loss of condenser vacuum.
1600 Unit start-up in progress.
1740 Reactor critical.
September 5th 0603 Turbine trip on MSR high level due to air sensing line leak (no scram).
1426 Unit tied to line.
September 7th 0900 Unit operating at 85% thermal power.
September 8th 1540 Increasing load using recire flow to go to 105% core flow.
E-5
- I NARRATIVE REPORT UNIT 2 (Continued)
September 10th L415 Unit operating at 904 thermal power, 105% core flow, Unit in cycle coastdown.
September 17th 1000 Unit shutdown in progress, for end of cycle 6.
September 18th 0351 Generator off line.
0858 Reactor manual scram beginning end of cycle 6 refueling outage.
September 30th 2400 Unit in refueling outage.
4
- e-6 4
l I
J I
I
OPERATING DATA REPORT ,
DOCKET NO. 50-366 DATE 10-05-86 COMPLETED BY: J. H. Richardson TELEPHONE (912) 367-7781 x 2360 OPERATING STATUS
- 1. Unit Name: E. I. Hatch Nuclear Plant Unit 2
- 2. Reporting Period: 09-86
- 3. Licensed Thermal Power (MWt): 2436
- 4. Nameplate Rating (Gross MWe): 820.0
- 5. Design Electrical Rating (Net MWe): 784.0
- 6. Maximum Dependable Capacity (Gross MWe): 803.9
- 7. Maximum Dependable Capacity (Net MWe): 777.0
- 8. If changes occur in capacity ratings (Items Number 3 through 7) since last report, give reasons: N/A
- 9. Power level to which restricted, if any (Net MWe) No Restrictions
- 10. Reasons for restrictions, if any: N/A This Month Yr-to-Date Cumulative
- 11. Sours In Reporting Period 720 6551 61848
- 12. Number of Hours Reactor was Critical 392.4 5877.9 43449.4
- 13. Reactor Reserve Shutdown Hours 0 0 0
- 14. Hours Generator On-Line 321.9 5709.4 41577.9
- 15. Unit Reserve Shutdown Hours 0 0 0
- 16. Gross Thermal Energy Generated (MWH) 610582 11085658 89268864
- 17. Gross Electrical Energy Generated (MWH) 190690 3545200 29326700
- 18. Net Electrical Energy Generated (MWH) 176681 3366112 27904766
- 19. Unit Service Factor (%) 44.7% 87.2% 67.2%
- 20. Unit Availability Factor (%) 44.7% 87.2% 67.2%
- 21. Unit Capacity Factor (% Using MDC Net) 31.6% 66.1% 58.1%
- 22. Unit Capacity Factor (% Using DER Net) 31.3% 65.5% 57.6%
- 23. Unit Forced Outage Rate 21.8% 6.2% 10.5%
- 24. Shutdowns scheduled over next 6 months (Type, Date, and Duration of Each):
Refueling Outage-began September 18, 1986
- 25. If shutdown at end of report period, estimated date of startup: 11/7/86
- 26. Units in Test Status (Prior to Commercial Operation): N/A E-7
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 50-366 DATE: 10-05-86 COMPLETED BY: Jody Richardson TELEPHONE (912) 367-7781 x 2360 MONTH 09-86 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net) (MWe-Net) 1 7 17 487 i
2 58 18 13 3 36 19 0 4 0 20 0 5 44 21 0 6 369 22 0 7 607 23 0 8 622 24 0 9 651 25 0 10 665 26 0 11 661 27 0 12 658 28 0 13 656 29 0 14 652 30 0 15 645 31 0 16 642 E-8
. b UNIT SHUTDOWNS AND POWER REDUCTIONS.
DOCKET NO. 50-366 UNIT NAME HATCH TWO COMPLETED BY J. H. RICHARDSON TELEPHONE (912) 367-7781 (2360) DATE OCTOBER 01,'1986 REPORT MONTH SEPTEMBER 1986 R S E Y T A METHOD OF LICENSEE SC Y S SHUTTING EVENT TO CAUSE & CORRECTIVE P DURATION O DOWN REPORT ED 00MPONENT ACTION TO NO. DATE E (HOURS) N REACTOR NUMBER ME CODE PREVENT RECURRENCE 86-057 860901 F 17.22 H 4 2-86-22 CD INSTRU Continuation of outage l from scram associated with level instrumen-tation.86-058 860901 S 0.87 H 5 N/A CD INSTRU Ramping in power from outag e.
l 86-059 860901 F 0.78 A 9 N/A HJ HTEXCH Turbine trip on high l MSR hotwell level l while at low power I (no scram).86-060 860901 S 7.05 A 5 N/A HJ HTEXCH Ramping in power from turbine trip.
l F: Forced Reason: Method: Events reported involve S: Scheduled A-Equipment Failure (Explain) 1-Manual a greater than 20% reduction B-Mai 'anance or Test 2-Manual Scram in average daily power level C-Ref ur ling 3-Automatic Scram for the preceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
D-Regulatory Restriction 4-Continuations E-Operator Training & License 5-Load Reduction Examination 9-Other (Explain)
F-Administrative G-Operational Error (Explain)
H-Other (Explain)
E-9
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-366 UNIT NAME H ATCH ' 'NO COMPLETED BY J. H. RICHARDSON TELEPHONE (912) 367-7781 (2360) DATE OCTOBER 01, 1986 REPORT MONTH SEPTEMBER 1986 R S E Y T A METHOD OF LICENSEE SC Y S SHUTTING EVENT TO CAUSE & CORRECTIVE P DURATION O DOWN REPORT ED COMPONENT ACTION TO NO. DATE E (HOURS) N REACTOR NUMBER ME CODE PREVENT RECURRENCE 86-061 860902 P 14.13 A 9 N/A HB TURBIN Unit in hot standby for repair of EHC oil leak.86-062 860902 S 11.82 A 5 N/A HB TURBIN Ramping in power from above repair.86-063 860903 F 18.13 H 3 2-86-23 HB TURBIN Scram due to turbine trip from low EHC oil pressure.86-064 860903 F 31.27 A 3 2-86-24 HC HTEXCH Scram on low reactor water level due to RFPT trip on low condenser vacuum.
F: Forced Reason: Method: Events reported involve S: Scheduled A-Equipment Failure (Explain) 1-Manual a greater than 20% reduction B-Maintenance or Test 2-Manual Scram in ay9 rage dnily power level C-Refueling 3-Automatic Scram for the preceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
D-Regulatory Restriction 4-Continuations E-Operator Training & License 5-Load Reduction Examination 9-Other (Explain)
F-Administrative G-Operational Error (Explain)
H-Other (Explain)
E-10
UNIT SHUTDOWNS AND POWER REDUCTIONS r
DOCKET NO. 50-366 UNIT NAME HATCH TWO COMPLETED BY J. H. RICHARDSON TELEPHONE (912) 367-7781 (2360) DATE OCTOBER 01, 1986 REPORT MONTH SEPTEMBER 1986 R S E Y T A METHOD OF LICENSEE SC Y S SHUTTING EVENT TO CAUSE & CORRECTIVE P DURATION O DOWN REPORT ED COMPONENT ACTION TO NO. DATE E (HOURS) N REACTOR NUMBER ME CODE PREVENT RECURRENCE 86-065 860905 S 0.78 A 5 N/A HC HTEXCH Ramping in power from scram.86-066 860905 F 8.38 A 9 N/A HJ HTEXCH Turbine trip on MSR high level while at low power (no scram).86-067 860905 S 97.07 A 5 N/A HJ HTEXCH Ramping in power from turbine trip.86-068 860909 S 204.35 H 9 N/A RC FUELXX End of cycle coastdown 86-069 860918 S 308.15 C 2 N/A RC FUELXX Unit shutdown for refueling outage.
F: Forced Reason: Method: Events reported involve S: Scheduled A-Equipment Failure (Explain) 1-Manual a greater than 20% reduction B-Maintenance or Test 2-Manual Scram in average daily power level C-Refueling 3-Automatic Scram for the preceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
D-Regulatory Restriction 4-Continuatio".s E-Operator Training & License 5-Load Reduction Examination 9-Other (Explain)
F-Administrative G-Operational Error (Explain)
H-Other (Explain)
E-ll E
4 .. . _ _ _ ._ _
r Georgia Power Company
.' 333 Piedmont Avenue 4
.% Atlanta. Georgia 30308 s Telephone 404 526-6526 ,
Maihng Address:
Fbst Ottice Box 4545 Atlanta. Georgia 30202 1
- Georgia Power i L T. Gucwe IN souhern entrc system .
I Manager Nuclear Safety and Ocensing October 9,1986 h Nuclear Operations
- NRC Monthly Operating Report +
File: X7GJ10-H000 j Log: SL-1396 Director, Office of Management and Program Analysis U. S. Nuclear Regulatory Conunission Washington, D. C. 20555
Dear Sir:
Enclosed is the Monthly Operating Report for Hatch Unit 1, Docket
' Number 50-321, and for Hatch Unit 2, Docket Number 50-366. This report is submitted pursuant to Technical Specifications Section 6.9.1.10.
l Sincerely,
)
- L. T. Gucwa MJBlackwood/lc Enclosure ,
c: Georgia Power Company U. S. Nuclear Regulatory Commission jl Mr. i . P. O'Reflly Dr. J. N. Grace, Regional Administrator i
Mr. J. T. Beckham, Jr. Mr. P. Holmes-Ray, Senior Resident Mr. H. C. Nix, Jr. Inspector - Hatch
! Mr. C. Tabet Mr. G. Rivenbark, Hatch Licensing i
GO-NORMS Project flanager i
3 1
1 0798C 9 t
- - - , --yem- y r e-r-e m - e v w- e ----c-- --r-- -w ~~ ---- -<w-~ -c r y , w -- - --~rw--- - - . . - _-,-,-w--mm,- --
&m- n -- - m-
NARRATIVE REPORT UNIT 1 September lat 0000 Unit operating at 100t thermal power.
September 6th 0035 Unit power decreased to 720 MWE to perform weekly turbine testing.
0400 Unit returned to 1004 power.
September 12th 2015 - Beginning load reduction for plant shutdown to repair drywell valve leaks.
September 13th 0045 Reactor manual scram.
September 15th 0813 Pulling rods.
1010 Reactor critical.
September 16th 0342 Unit tied to line.
September 18th 2100 Unit at 100% power,103% core flow.
September 20th 2255 Beginning load reduction for pattern adjustment.
September 21st 0248 Pattern adjustment crosplete increasing to full power.
1300 Unit returned to 1004 power.
September 27th 0057 Dropping load for weekly turbine testing.
0311 Unit returned to 100t power.
September 30th 0000 Unit operating at 100% power.
E-1