ML20202J848

From kanterella
Jump to navigation Jump to search
Change Notice 001 to Rev 1 to Quality Instruction QI-053, Reinsp of Category I Conduit Supports/I-S-COSP
ML20202J848
Person / Time
Site: Comanche Peak  
Issue date: 06/11/1986
From: Hansel J, Kaufman A, Patterson A
EVALUATION RESEARCH CORP.
To:
Shared Package
ML20202J051 List: ... further results
References
QI-053, QI-53, NUDOCS 8607170156
Download: ML20202J848 (2)


Text

,

I.

'[

Pcg3 1 cf 2 4

EVALUATION RESEARCH CORPORATION gR COMANCHE PEAK RESPONSE TEAM QUALITY INSTRUCTION FOR ISSUE-SPECIFIC ACTION PLAN VII.c.

CHANGE NOIICE: 001 INSTRUCTION NO.: QI-053 REVISION NO.:

1 ISSUE DATE:

06/11/86 i

REINSPECTION OF CATEGORY I CONDUIT SUPPORTC/I-S-COSP O

The QI identified above is hereby changed as shown on the attached page of this notice.

Prepared by:

2,f Date:

$/ FG

/ /

aft M J,./// h Date:

M/a/#4 l

Approved by:

IssueCgdibator'

[!// ((

Approved by:

Date-On-diite Qiypresentative Approved by:

Date:

dP o 8d QA/

Review Team Leader 0607170156 860711 PDR ADOCK 05000445 A

PDR

i i)'.

Chnngs Notico 001 i

QI-053 Rev. 1 (s

1.

Add the following paragraph under the Material Verification Section t,,)>

(5.4.0) of the QI:

5.4.2 Verify material for bolting attachments is as shown on the generic / design drawing. See Attachment 6.16 for bolt markings.

2.

Add the following criteria to the end of paragraph 5.6.2

'Embedment':

In floor and roof areas where topping has been placed, the thickness of the topping shall be taken into account in determining the projected length unless shown on design drawing.

In these areas the thickness of the topping shall be added to measured length taken from the concrete surface. The inspector shall ensure that the thickness for topping is provided by the engineer and included in the verification package.

3.

Change paragraph 5.3.le to read:

For suspended supports with conduits carrying LED's, verify that there are no threaded conduit sections within 2" of these supports.

(

O

_.