ML20202J474

From kanterella
Jump to navigation Jump to search
Change Notice 001 to Rev 1 to Quality Instruction QI-066, Reinsp of Equipment Supports
ML20202J474
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 02/12/1986
From: Patterson A, Ross G
EVALUATION RESEARCH CORP.
To:
Shared Package
ML20202J051 List: ... further results
References
QI-066-01, QI-66-1, NUDOCS 8607170087
Download: ML20202J474 (4)


Text

_

l H

Pago 1 of 4 i

O EVALUATION RESEARCH CORPORATION 9

COMANCHE PEAK RESPONSE TEAM QUA1!rY INSTRUCTION FOR ISSUE-SPECIFIC ACTION PLAN VII.c gotED COPY.

CHANGE NOTICE 001 CONTROL NO O F e N INSTRUCTION NO.: QI-066 REVISION:

1 ISSUE DATE: 02/12/86 REINSPECTION OF EQUIPMENT SUPPORTS The QI identified above is hereby changed as shown on the attached pages of this notice.

Prepared by: Ab MA Date:

'2 b *vaa-Y 66 Q\\

Approved by:

M /'#A '

M* -

Date:

4 #

Issue Coordinator Approved by:

A Date:

j -/d -

On-Site QA Representative O

e "Afs.A/$1 Approved by:

lg\\

Date:

QAfl$C Review Team Leader

/

~

0607170087 860711 PDR ADOCK 05000445 A

PDR

4 Changs Notica 001 q

QI-066 y

Rev. 1 Change Paragraph 5.5.B From:

"Where threaded rod material is indeterminate, this attribute is still acceptable."

To:

i "Where threaded rod material is indeterminate, this attribute or portion thereof shall be N/A."

Change Attachment 6.5 Replace pages 1 and 2 of Attachment 6.5 with pages 3 and 4 of this change notice.

i l

lO O

i 2

,n--,en,-

-,-~

n._

-n,---_-war,,,_,_--,____

,_,,-,-,,,g,

,n, mw

,n,,---,,-

r Chings Notica 001 j

Attechxnt 6.5 QI-066 Rev.-1

(

Page 3 of 4 HILTI ANCHOR DESIGNATION AND SETTING REQUIREMENTS

~'

Minimum Embedment (Before Torque)

Stamp on Actual Length Nut Anchor Bolts Sizes KWIK Super Kwik of Threads Thickness 3/4 7/32 A.

1/4 x 1 5/8 1 1/8 3/4 7/32 B.

1/4 x 2 1/4 1 1/8 7/8 11/32 3/8 x 2 1/8 1 5/8 7/8 11/32 c.

3/8 x 2 3/4 1 5/8 1 1/4 7/16 1/2 x 2 3/4 2 1/4 3/4 7/32 D.

1/4 x 3 1 1/8 3/4 7/32 E.

1/4 x 3 1/2 1 1/8 1 1/8 11/32 3/8 x 3 1/2 1 5/8 1/2 x 3 3/4 2 1/4 1 1/4-7/16.

4

'5/8 x 3 1/2 2 3/4 1 1/2 17/32 I

F.

3/4 x 4 1/4 3 1/4 1 1/2 5/8 O

1 1/2 17e>2 c-

><8 4 1/2 2 ><4 1 1/2 5/8 3/4 x 4 1/2 3 1/4 1 1/8 11/32 H.

3/8 x 5 1 5/8 1

1 1/4 7/16 1.

1/2 x 5 1/2 2 1/4 1 1/2 5/8 3/4 x 5 1/2 3 1/4 1 1/2 17/32 i

J.

5/8 x 6 2 3/4 2 1/4 27/32 1x6 4 1/2 j

K.

L.

1/2 x 7 2 1/4 3 1/4 1 1/4 7/16 1 1/2 5/8 3/4 x 7 3 1/4 2 1/4 27/32 1x7 4 1/2 l

M.

i N.

i 1 1/2 17/32 o.

5/8 x 8 1/2 2 3/4 1 1/2 5/8 3/4 x 8 1/2 3 1/4 j

I P.

1/2 x 9 3 1/4 1 1/4 7/16 l

1x9 4 1/2 6 1/2 2 1/4 27/32 3 1/4 1 1/32 1 1/4 x 9 5 1/2 Q.

I

\\

!J.

Ching2 Notica 001 Attschment 6.5 i

QI-066 Rev. I Page 4 of 4 HILTI ANCHOR DESIGNATION AND-SETTING REQUIREMENTS Minimum Embedment (Before Torque)

Stamp on Actual Length Nut Anchor Bolts Sizes KWIK Super Kwik of Threads Thickness 1 1/4 7/16 R.

1/2 x 10 2 1/4 1 1/2 5/8 3/4 x 10 3 1/4 S.

T.

1/2 x 12 3 1/4 1 1/4 7/16 1 x 12 4 1/2 6 1/2 2 1/4 27/32 1 1/4 x 12 5 1/2 8 1/8 3 1/4 l'1/32 i

U.

1 x 13 1/2 4 1/2 6 1/2 2 1/4 27/32 1 1/4 x 13 1/2 5 1/2 8 1/8 3 1/4 1 1/32 i

v.

4 6 1/2 2 1/4 27/32 W.

I x 15 1 1/4 x 15 5 1/2 8 1/8 3 1/4 1 1/32 4

()

K.

I 1/4 x 16 1/2 5 1/2 8 1/8 3 1/4 1 1/32 T.

Z.

I 1/4 x 18 5 1/2 8 1/8 3 1/4 1 1/32 l

DD.

I 1/4 x 22 8 1/8 3 1/4 1 1/32 8 1/8 3 1/4 1 1/32 EE.

1 1/4 x 23 i

1

  • Bolts of 19-inch length and greater may be stamped with number corresponding to the bolt length in inches in the same manner instead of the stamped letters as listed above and Attachment 6.13.

i 1

O I

i i

. - - -