ATTACHMENT 2 D6@OR Edison Date:
December 23, 1987 To:
S. K. Sharma Fermi 2 From:
R. L. Colwell
/
P. M. Beckwith, " +
Engineering Research Subj ect:
Chemical and Physical Testing of Fasteners for Fermi 2 Fermi Test Req. 610144 Engineering Research Report 87C71-23, Revision 2 Ten items were delivered to Engineering Research for material analysis. They are described as follows.
Item i DEQN i Description 9 Nut SA194 Gr. 2K I
1 7/8" 2
2 3/4"
- 10 Nut SA194 Gr. 2H 3
9 9/16" - 12 Nut A563 Gr. A 4
4 3/8"
- 16 Nut SA194 Gr. 2H 5
5 1-1/4" - 7 Nut A194 Gr. 2R 6
6 1-1/8" - 7 Nut A194 Gr. 2H
{
7 7
1-1/4" - 8 Nut SA194 Gr. 2H 3/4"
- 10 Nut A563 Gr. C 8
11
~ 3/4"
- 10 Nut A194 Gr. 2H 9
12 10 13 7/8"
- 9 Nut A194 Gr. 2H The test results are displayed on attached NRC Data Summary Form along with the appropriate specifications for each item.
Test Procedures 1.
TP-FL-009 Rev. O Test Procedure for the Determination of Carbon in Steel.
i
)
2.
TP-FL-032 Rev. O Test Procedure for Dissolution of Material by Acid Digestion for Total Metals I
Analysis l
3.
TP-FL-045 Rev. O Test Procedure for Determinstion of Sulfur in Steel and Cast Iron.
4.
TP-FL-046 Rev. O Test Procedure for the Analysis of Steel and Cast Iron Samples by Inductively f
Coupled Plasma Spectroscopy 5.
TP-AM-003 Rev. 2 Test Procedure for Material Evaluation in Accordance with ASTM, ANSI, ASME, AWS, and SAE Test Methods.
PE.14/21 8801200250 800114 PDR ADDCK 05000341 0
ATTACHMENT 2 87C71-23 Rsv. 2 2.
Test Requisition #610144
[
i DATA SUMARY Mechanical Analysis Chemical Analysis (wt. %)
Itea #
Crade Eerdness UTS C
P, ji 1
SA194 Gr. 2H 27.1 HRC N/A - 0.444
<0.020 0.030 2
26.3 N/A 0.458 0.019 4
29.5 N/A 0.438 0.021 5
A194 Gr. 2H 31.3 N/A 0.449 0.035 6
33.0 F/A 0.499 0.030 7
SA194 Gr. 2H 27.5 N/A 0.475 0.046 9
A194 Gr. 2H 30.3 N/A 0.459 0.022 0.014 10 27.0 N/A 0.405
<0.020 0.017 Spee.
(24-38 HRC)
N/A (0.40 min)
(0.040 max)
(0.050 max) l 3
A563 Gr. A 98.8 HRB N/A 0.168
<0.020 0.027 Spee (B68-C32)
N/A (0.55 max)
(0.12 max)
(0.15 max) 8 A563 Gr. C 28.9 HRC N/A 0.338 0.017 l
Spec (B78-C38)
N/A (0.55 max)
(0.12 max)
(0.15 max)
PE.14/21 l
l l
i ATTACHMENT 2 87C71-23 Rsv. '2 3.
MT&E Equipment ER0013 Wilson Rockwell Hardness Tester ER7025 LECO Carbon Analyzer ER7027 Sulfur Analysis System ER7000 Analytical Balance ER0553 Balance W5ights ER7002 Inductively Coupled Plasma Spectrometer All work was performed in accordance with the Engineering Research Quality Assurance Program.
Approvedby:h,h
[ )/
/
/J. D. C'yrulewski g
i
. C. Guillaumin Supervisor QA Administrator:
R. L. Gamble Copies to:
R. L. McIntyre (File)
Fermi 2 Dist.
l l
l RLC/gc PE.14/21 l
-