ML20138M820

From kanterella
Jump to navigation Jump to search
Rev 19 to Instruction QI-QP-11.4-10, Insp of Concrete Substrate Surface Preparation & Coatings Application & Repair
ML20138M820
Person / Time
Site: Comanche Peak, 05000000
Issue date: 06/13/1984
From: Bielfeldt L
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
Shared Package
ML20138M609 List: ... further results
References
FOIA-85-59 QI-QP-11.4-10, NUDOCS 8511040433
Download: ML20138M820 (20)


Text

o.

O g

f.

! INSTRUCTION ISSUE TEXAS UTILITIES GENERATING CO.

NUMBER

, REVISION OATE PAGE l

CPSES l

i i

I Qk-QP-11.4-10 19 JUN1li 1984' 1 of to PREPARED BY:

//

w

['/[

SU FAC APPROVED BY:

4 0, L -

[ -/YSY '

PREPARATION AND C0ATINGS APPLICATION AND REPAIR APPROVED BY: M a k h l_ / e l d V- -

6 - a.f g.

ui

/~ g DATE i

1.0 REFERENCES

I 1-A Gibbs and Hill Specification 2323-AS-31, " Protective Coatings" 1

1-B CEI-20, " Field Installation of Hilti Bolts"

,l l

1-C CCP-12

" Concrete Patching, Finishing, and Preparation of l

Construction Joints" i

1 i

1-0 CCP-40, " Protective Coating of Concrete Surfaces" 1-E QI-QP-11.0-5, " Inspection of Concrete Repair" t

i 1-F QI-QP-11.4-2 4,

" Reinspection of Protective Coatings on Concrete Substrates for Which Documentation is Missing or Di sc repant" 1-G CP-QP-18.0, " Inspection Reports" 1-H CP-QP-15.0, " Tagging Systens"

'aOST E!!' WO' 7 6 ' C 6 0 l

7 i

1-I CP-QP-16.0, "Nonconfonnances" f

2.0 GENERAL 2.1 PliRPOSE AND SCOPE This instruction shall describe the methods used by Quality Control personnel while perfonning inspections of applica-tion of coatings on a concrete substrate in all areas other i

than Unit 1.

3.0 INSTRUCTIONS Application of f.utec 10, 11, 115 and 1201 shall be per Sectiors 3.1 through 3.9.

l 8511040433 851016 PDR FOIA GARDEOS-59 PDR 6

Tucco c4

TEXAS UTILITIES GENEFIATING CO.

CPSES QI-QP-11.4-10 19 JUN 1 a 1984 2 of 20 Visual ins pection of su rf aces as addressed by this instruction shall be made at approximately an arm's length from the surface being inspected (where applicable).

The l

area of inspection shall be adequately lighted during the inspection activi ty.

Adequate lighting is defined as the minimum light produced by a two (2) cell battery flashlight.

If a conflict arises between the requirenents of this procedure and the requirements of the site specification, Reference 1-A, the requirenents of the site specification shall prevail.

3.1 SURFACE PREPARATION The concrete surface shall be cured a minimum of 28 days prior to application of protective coatings.

If the concrete surface is cured with NUTEC 10, coating may be perfonned after a minimum of 6 days after application of NUTEC 10.

Tie holes, abandoned Hilti bolt holes and spalled concrete as defined in Reference 1-B, and patched per Reference 1-C and l

grout under base plates which has 3 square feet or less of exposed surface to be coated, may be coated af ter a 48 hour5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> cure.

3.1.1 Preblast Cleaning Operations Prior to su rface prepa ration, the QC inspector shall visually examine the surface to be water blasted for heavy deposi ts of oil and grease.

Any heavy oil or grease deposits shall be removed by steam cleaning, tri sodium phosphate washing wi th a mixture of 3-6 pounds TSP per gallon of water, or use of an Imperial recommended detergent.

The QC inspector shall alto verify tnat any detrimental surface irregularities such as projections, fins, or ridges shall be renoved by bush hammering, hand or power tooling, grinding, or stoning.

NOTE 1:

The preblast visual inspection is required only when surface preparation is by one of the following methods:

a.

Water blasting b.

Water blasting with sand injection c.

Dry sandblasting d.

Bush hammering TuGCO OA e~....

TEXAS UTILITIES GENERATING CO.

CPSES i

QI-QP-11.4-10 19 i g3 i, 3 13g4 l 3 of 20 3.1.2 Methods of Surface Preparation Water blasting, water blasting with sand injection, acid i

etching, sand blasting, and power tooling are all acceptable methods of surface preparation.

If NUTEC 10 curing menbrane

- ~~

~

~

has been applied and gives a " glos sy" appearance, - the surface shall be abraded without completely removing the NUTEC 10 prior to application of the surfacer.

The QC inspector shall note the method (s) used on the Inspection Report (IR), Attachment 1.

The inspector shall verify' that the method (s) used are in compliance with Reference 1-0.

In the event TSP is used, the QC inspector i

shall verify that the area is flushed with clean water.

If sand blasting is used, the QC inspector shall verify that a trap, filter, or separator is installed in the air line.

3.1.3 Post Surface preparation Operations Af ter surface preparation, the QC inspector shall visually examine the si.rface to verify the following:

a)

The surface shall be free of construction dust, laitance, and loose deposits, and all adjacent areas cleaned to avoid contamination.

b)

All holes greater than 1/2 inch in depth or greater than 2"

diamettr and cracks greater than 1/32" width are repaired prior to surfacer application.

c)

All sharp projections removed.

d)

Markings ('nk, pencil, chalk, fel t tip marker, etc.)

solvent wiped in accordance with Reference 1-0.

l e)

Marking pairt renoved, f)

Objects protruding fran surface are ground or cut smooth until object is flush, g)

Al l loosely adhering objects enbedded are renoved,

h)

Snooth enbedded objects such as plastic or steel roughened.

Petal objects are power tool cleaned and solvent wiped.

I nint n n.

l PROCEDURE ISSUE REVISION PAGE TEXAS UTILITIES GENERATING CO.

~

CPSES

.QI-QP-11.4-10 19 JUN 131964 4 of 20 i)

Metal objects larger than 4 square inches are primed.

l j)

Surface is free of grease, oil, and curing menbranes.

If grease and oil renain af ter TSP cleaning, the area shall be chipped out and repaired with dry pack or epoxy grout and insp2cted by Civil QC in accordance with Reference 1-E.

l 3.2 MIXING OPERATIONS 3.2.1 Materials The QC inspector shall verify' that the materials to be used are in accordance with Reference 1-D and that each component is identi fied by a ba tch ntsnbe r.

The QC inspector shall also verify that the shelf life (See Attachment 2) has not expired.

NUTEC 10 has an expiration date marked on the container and it shall not be used after that date.

3.2.2 Mixing / Thinning The QC inspector shall wi tness all mixing / thinning operations, and verify that mixing / thinning is performed in accordance with Reference 1-0.

Induction times for finish mixes are shown in Attachment 2.

3.3 SURFACER APPLICATION 3.3.1 Ambient Conditions The inspector shall detennine air tenpe ra tu re, rela tive humidi ty, dew poin t, and su rface temperature of concrete substrate.

A calibra ted non-me rcury filled dry bulb thennometer or a calibrated tenperature recorder (Bristol 4069 TH or equivalent) shall be used for air tenperature detennination.

A calibrated non-mercu ry filled wet bulb thennome ter or a calibra ted humidi ty recorde r (Bristol 4069 TH or equivalent) shall be used to determine rela tive humidi ty.

The dew point shall be detennined by the dif ference in dry and wet bulb temperature using the U.S.

Department of Commerce Weather Bureau Psychrometric Tables, W.B. No. 235. When dry bulb readings are greater than 100*F, the dew point and relative humidity should be detennined using the 100'F reading (note in Remarks Section).

The surface tenperature shall be detennined by placing a calibrated Range 0-250'F thermometer or equivalent in contact with the surface to be coated.

The thennometer probe shall renain in contact with the surface until the tenperature reading stabilizes.

TuGCO CA p.,. u,3

i PROCEDU REVISION PAGE I

g gR TEXAS UTILITIES GENERATING CO.

5 of QI-QP-11.4-10 19

, JUN 13 1984 20 1

p I

Minimum and maximum values of su rface and ambient tempera tures shall be 50'F and 100'F respectively.

Infrequent dips in tenperature to 40*F is pennissible during application and/or cure; however, the elapsed tine the tenperature is below 50*F shall be added to the cure time.

Application of the coating shall not begin unless the surface tenperature is 5'F above the dew point.

Humidity may vary as high as 100%; however, free standing water shall be renoved.

Coating application over a damp surface is permissible. Under no conditions shall NUTEC 115 be applied to a surface Containing free standing wa ter.

Methods of identifying free standing water are shown in Reference 1-D.

3.3.2 Surface Acceptability The QC inspector shall vi sually examine the substra te surface immediately prior to surfacer application to verify that it is free of contaminat_ ion (dust, laitance, loose I

deposits and markings).

3.3.3 Air Supply Acceptability The inspector shall ins pect the air supply systen for l

suitable filters / traps / separators.

The effectiveness of these itens shall be verified by exposing a piece of white cloth to a blast of air for approximately 30 seconds.

The cloth shall show no evidence of moisture, oil or foreign matter when examined.

3.3.4 Pot Life The QC inspector shal'l verify that the pot life as shown in is not exceeded.

3.3.5 Qualification of Applicator (s)

The Inspector shall verify (by Qualification Record or list of quali fied applica tors fran QA file) that the coating applicators on each shift are qualified for safety-related coating work.

TUGCO OA

,,, 3

I PROCEDURE ISSUE REVISION PAGE NUMBER TEXAS UTILITIES GENERATING CO.

CPSES d' I ' E 6 of 20 QI-QP-11.4-10 19 i

3.3.6 Dry Film Thickness The QC inspector shall detennine the DFT of the applied surfacer by taking wet film thickness spot measurements at:

multiplying each reading by the *. volume solids (taking i-account any thinner used).

A minimum of five (5) separate spo t wet film thickness (WFT) neasu renents (See Note 1) spaced evenly over the coated area (See Note 2) shall be taken.

NOTE 1:

A spot measu renent is a series of three gage readings in the same general area.

The WFT gage should be nuved a short distance for each gage reading.

Discard any unusually high or low gage reading that cannot be repeated consistently. Take an average of these three gage readings as one spot measurenent.

NOTE 2:

For small areas of coating, five (5) spo t measurements shall be taken.

For larger areas, 5 spot measurements shall be taken for each 100 square feet (or fraction thereof) of coating.

Thickness of surfacer may vary betwer.n 10 and 35 mils.

(See for method of dete rmining percent volume solids.)

3.3.7 Surfacer Repair Work 3.3.7.1 Repair of Runs and Sags Runs and sags which show evidence of nudcracking shall be abraded flush with the surrounding su rface.

If after abrading, surfacer is unsatisfactory, renove unsatisfactory, coating to substrate and reapply the surfacer, if after abrading the surfacer is satisfactory, no further repair is necessary.

3.3.7.2 Repair of Contamination Contamination shall be renoved by abrading.

If unsatisfactory coating still exists, then the area shall be repaired in acconiance wi th Section 3.3.7.3.

NOTE:

Rust stains residue, not necessarily the stain, shall be renoved with bristle brush and water or Imperial Thinner #0L-54 TUGc0 0A

,,, e 3

PROCEDURE gE Wlh PAGE R

texas uriurigG,ENERArlNG CO.

lQI-QP-11.4-10 19 JUN 131984 7 of 20 3.3.7.3 Repairs When Touch Up or Recoating is Necessary For repairs that require either touch up or recoating with NUTEC 115, NUTEC 11 or NUTEC 1201, the QC inspector shall:

a)

Verify ambient conditions are acceptable per Section 3.3.1.

b)

Virify surface has '6een prepa red in accordance with Referen~ce 1-D and is free from loose and foreign materials as per Section 3.3.2 c)

Veri fy acceptable materials (per Reference 1-D),are l

used, and shelf life is not exceeded, d)

Verify that NUTEC 115, NUTEC 11 or NUTEC 1201 is mixed / thinned in accordance with Section 3.2.

e)

Veri fy pot li fe is ' not exceeded per Attachment 2.

f)

Verify qualification of applicator (s) per Section 3.3.5.

~

g)

Visually inspect per Section 3.4.2.1.

h)

Ve rify that curing is in accordance wi th Section 3.4.2.2.

1)

Ve r.fy dry film thickness in the repair area is in accordance with the following millage requirements:

NUTEC 115 10 - 35 mils NUTEC 11 3 - 20 mils NUTEC 1201 3 - 16 mils NOTE 1:

See Section 3.3.6 and Attachment 4 for UFT calculation using Wet Film Thickness measurenent and percent volume solids.

3.4 FINISH C0AT APPLICATION 3.4.1 Preapplication Inspection 3.4.1.1 Ambient Conditions Prior to finish coat application, the QC inspector shall detemine ambient conditions in accordance with Section 3.3.1.

TUGCO CA pp,., g y w

PROCEDURE ISSUE

^

TEXAS UTILITIES GENERATING CO.

CPSES Ql-QP-11.4-10 19 JUN14 IBM l 8 of 20 3.4.2 Surf acer Post Application Operation l

3.4.2.1 Visual Defects Inspection The inspector shall perfo nn a vi sual inspection of the surfacer coat NUTEC 115 and NUTEC 11 prior to the finish coat application for the following defects:

a)

Runs or sags which show no evidence of nudcracking shall be abraded down to adjoining coating thickness, I

b)

Stains - rust (red) and zinc oxide (white) stains are acceptable provided loose particles are renoved fran NUTEC 115 or NUTEC 11 surfaces prior to application of finish coat, c)

Dry spray, over spray, damaged areas, skips, holidays, blisters, bubbling, mudcracking, oil and grease, and contamination are all unacceptable.

Contamination is not allowed.

Unacceptable conditions will be repaired in accordance with l

Reference 1-0.

3.4.2.2 Surfacer Cure The inspector shall unitor ambient tenperature af ter the surfacer is applied to detennine when cure is adequate for topcoating operations to commence. A calibrated non-mercury filled dry bulb thermometer, calibrated temperature recorder shall be ued for air tenperature detennination.

Curing time shall be as follows:

Curing Time Before Tempera ture O'F_

Topcoating with 1201_

50-59 72 hrs.

60-69 48 hrs.

70-79 24 hrs.

80-89 18 hrs, e

90-100 12 hrs.

l Tenperature durations below 50*F will be added to the cure time on an hour by hour basis.

l TUGCO OA f or* m 3

I PROCEDUHE ISSUE

~

REVISION PAGE NUs.!BE9 DATE TEXAS UTILITIES GENERATING CO.

CPSES 9 f QI-QP-11.4-10 19 JUN1o $64 20 l

l I

NtfTE'C 115 may be touched up or recoated with #11 or #115 as soon'as the initial coat his dried such that the paint shall not adhere to the thunib wh n downward pressure is exerted on

- the paint film while turn mg a 90* angle.

(This does not refer to the two pass appli ation method.)

[

3.4.2.3 Air Supply Acceptability The,QC inspector shall veriff the air supply is acceptable l

per Section 3.3.3.

3.4.2.4 Qualification of Applicator (s)

The Inspector shall verify (by Qualification Record or list of qualified applicators fran QA file) that the coating applicators on each' shift are qualified for safety-related coating work.

3.4.2.5

'lerify that. tfutec 1201 is mixed / -hinned per Section 3.2.

iFinishCoatkoplication 3.4.3 3.4.3.1 Pot Lit'e T1e QC inspecto'r shall verify that.he pot life of NUTEC 1201 has not been exceeded.

Pot life is shown on.

3.4.3.2 Ory Film Thickness The inspector shall detennine the DFT of the applied finish coat by taking wet film thickness spot measurements and multiplying each reading by the % volume solids.

A minimum of five (5) separate spot wet film thickness (WFT) measurenents (See Note 1) spaced evenly over the coated area (See Note 2) shall be taken.

1 NOTE 1:

.A spot measurenent is a

series of three

, measurements in the same general area.

The WFT gage should be moved a short distance for each gage reading.

Discard any unusually high or low gage reading that cannot be repeated consistently.

Take an average of these three gage readings as one spot measurenent.

TUGCO OA Form No 3

i REVISION PAGE NUMBER TEXAS UTILITIES GENERATING CO.

CPSES QI-QP-11.4-10 19 JUN 13 Igg 4 10 of 20 l

i NOTE 2:

For small areas of coating, five (5) spot t

measurements shall be taken.

For larger areas, 5 spot measurenents shall be taken for each 100 square feet (or fraction thereof) of coating.

(See Attachment 4 for nethod of detennining percent volume solids.)

The total DFT of NUTEC 1201, recoat and existing coat shall not exceed 16 mils.

3.5 FINISH C0AT REPAIRS For repairs in the NUTEC 1201 Finish Coat, the QC l

Inspector shall verify the following:

a)

The inspector shall detennine the DFT of the existing I

coated surfa'ce (prior to recoating) by either, or one I

of the two following methods.

1)

Using the DFT readings acquired during the backfit I

docunentation (Reference 1-F).

2)

The scra tch test of the Nutec 1201 finish coat l

shall be perfonned using a

Mark II Tooke Inspection Gage equipped with a 2x tip.

Five l

separate readings spaced randomly over each finish coated area of 100 square feet or less shall be l

taken.

b)

Verify that the surface is prepared as requi red by Reference 1-D.

I c)

Verify that runs and sags which show evidence of mudcracking are abraded flush with the surrounding su rface.

If af ter abrading the finish coat is still unsatisfactory, verify that unsatisfactory coating (d)is renoved to the substrate and repaired per Steps through (k) below, g

d)

Verify that all contamination is renoved fran surface.

l l

l e)

Verify that the surface is solvent wiped.

l I

f)

Veri fy that NUTEC 1201 is mixed / thinned per Section 3.2.

i l

1 TUGCO OA FWm No 3

4 PROCEDURE ISSUE TEXAS UTILITIES GENERATING CO.

CPSES JUN 1 a 1984 11 of QI-QP-11.4-10,

19 20 g)

Verify air supply acceptabili ty per Section 3.4.2.3.

h)

Verify that pot life is not exceeded per Section 3.4.3.1.

i)

Verify applicator (s) qualification per Section 3.4.2.4.

j)

Verify cure time for recoat.

Recoating tine for NUTEC 1201 is 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

k)

Verify dry film thickness of the recoat per Section 3.4.3.2.

NOTE:

If present, the tie in interface between concrete coatings and steel coatings shall be inspected during the finish coat final acceptance of both systems.

FINISH C0AT FINAL ACCEPTANCE INSPECTION PRIOR TO AREA TURNOV 3.6 Immediately prior to turnover of each area within the RCB, a final visual inspection in accordance with the following subsections shall be perfonned on exposed finish coated concrete substrates.

3.6.1 Finish Coat Cure Prior to perfonning finish coat final acceptance inspections, the inspector shall verify that the finish coat has cured for the minimum of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

3.6.2 Finish Coat Continuity inspection The QC inspector shall visually inspect the continuity of the finish coat af ter a minimum cure of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

The maximum ntsnbe r of penni ssible pinholes is shown on.

No more than 2 points of discontinuity shall occur within an area having a radius of six inches (using a point of discontinuity as the center of the circle).

No more than 40% of the total number of allowable points of discontinuity shall occur within any one area equal to 25%

of the total area.

The pinholes that are beyond the acceptance of Attachment 3. shall be repaired in accordance wi th Section 3.5 and 3.6.3.

TUGCO CA po,m no 3

REVISION PAGE NUMBER TEXAS UTILITIES GENERATING CO.

CPSES

, QI-Q P-11.4-10 19

,jgN 13 1984 12 of 20 3.6.3 Visual Examination The QC inspector shall visually examine the finish coated surface for the following defects:

a)

Runs and sags which show no evidence of mudcracking i

are acceptable.

Unacceptable runs and sags will be i

repaired in accordance with Section 3.5.

b)

At the time of the final inspection, pinholes and j

smal1 discontinuities may be repaired wi th no reinspection required of these areas.

I c)

Skips, holidays, damaged areas, blisters, bubbles, and fish eyes will be repaired in accordance with Section 3.5.

l f

d)

Contamination detrimental to the coating film is unacceptable.

Area must be repaired per Section 3.5.

e)

Color and Gloss Unifonnity - the coated surface shall have unifonn color and gloss. Those surfaces which are nonunifonn shall be repaired in accordance with Section 3.5.

This requirement shall not be applicable to areas exhibiting runs and sags which have been abraded.

i 3.7 APPLICATION OF NUTEC 10 CURING COMPOUND 3.7.1 The QC Inspector shall verify that the green concrete has been cleaned per Reference 1-0.

3.7.2 The QC Inspector shall verify that NUTEC 10 is not applied under inclement conditions and that the surface tenperatures are above 50*F.

Areas of visible moisture or standing water are unacceptable.

3.7.3 The QC Inspector shall verify that the NUTEC 10 air supply and equipment shall be in accordance with Paragraph 3.3.3.

NUTEC 10 may also be applied by brush or roller.

3.7.4 NUTEC 10 shall be mixed per Paragraph 3.2.

The NUTEC 10 has a pot life of (1) one hour at 75'F.

If the NUTEC 10 l

I ;

gives the appearance of crawling and does not penetrate the concrete, the material shall be renoved fron the concrete f

by sol vent and a clean cloth.

All the expired material ll' shall be discarded.

l i

TUGCO OA

4 r

REVISION PAGE NUMBER TEXAS UTILITIES GENERATING CO.

CPSES 13 of QI-QP-11.4-10 19 gg3q N 20 l

3.7.5 NUTEC 10 shall be applied in acconiance with Reference 1-D.

Apply NUTEC 10 at a spreading rate of approximately 350-400 sq. f t./ gal.

3.7.6 The QC Inspector shall verify that during application of NUTEC 10, areas with sags, su rface irregularities or l

excessive buildup shall be renoved wi th solvent and a clean cloth, and material reapplied.

3.8 DOCUMENTATION Results of all inspections discussed in Sections 3.1 through 3.5 shall be documented on an Inspection Report, Attachment 1,

in acconiance wi th Reference 1-G.

Results of the k

inspections discussed in Section 3.6 shall be documented on an Inspection Repo rt, Attachment 5 in accordance wi th l

Reference 1-G.

Results of all inspections discussed in Section 3.7 shall be docunented on an Inspection Report (Attachment 6) in accordance with Reference 1-G.

NOTE:

A reject tag will be applied to any unsat area, with the inspection report, inspector's name, and phone extension listed per Reference 1-H.

l 3.9 MAPPING For each IR generated in accordanc'e with Section 3.'i, 3.4 and 3.6, a sketch shall be attached to indicate the location and size of the applicable coating application (See hate 3).

The individual sketches fran each IR shall be used to prepare canposite maps which shall cover in scope a specific roon, compartment, quadrant or cavity within the Reactor Containment Building.

For concrete surfaces Sich have received coatings prior to 11/11/81 (issuance date of Rev. 2 of this procedure) a unique nunber shall be assigned to the original inspection checklist.

This number shall be transferred to the applicable area on the conposite map in order to provide traceability to the original checklist. For any coatings applied af ter 11/11/81, the IR nunbe r shall be trans ferred to the area on the composite map.

l l

TUGCO OA

,,. u 3

l t-PROCEDURE ISSUE TEXAS UTILITIES GENERATING CO. '

CPSES Ql-QP-11.4-10 19 JUN 131984 14 of 20 The cmposite maps shall be ma'intained by the QC Supervisor, or his designee, until the entire surface in a given area has been coated, at which time, the completed map shall be transmitted to the PPRV.

NOTE 1:

Separate caposite maps shall be maintained for the surfacer and finish coats.

NOTE 2:

Coa ting repairs requi ring recoating shall be mapped but repairs requiring only touch up need not be mapped.

NOTE 3:

The following parameters (as necessary) should be considered for descriptions of test areas on the ske tch.

a.

Bottom and Top Eleva tions (vertical and diagonal surfaces) or Elevation of Surface (horizontal surfaces).

b.

Dimensions in relation to Azimuths, column lines, reactor centerline or other caponents of known location.

c.

Whether concrete substrate is wall, ceiling, floor, beam or colum.

d.

Quad rant, capa rtment, cavi ty or room in which inspection area is located.

e.

Unit number.

f.

Relation of su rf ace to Cardinal Directions (i.e. North, South, etc.).

3.10 NONCONFORMANCES Noncunfoming conditions such as coating failure due to loss of adhesion or indeterminate / unacceptable conditions which cannot be repaired or corrected as per existing procedures shall be documented on a Nonconformance Report (NCR) in accordance with Reference 1-I.

The NCR neber shall be referenced un the inspection Report, if applicable.

TUGCO UA p.,. % 3

3:

ISSUE INSTRUCTION REVISION PAGE

^

TEXAS UTILITIES G2NERATING CO.

[JUN1368L CPSES 15 of 20 QI-QP-11.4-10 19 ATTACHMENT 1 COnsANCxt Max $ TEAM E:.!CTAlc STAncN 1

2 n.ar-INSPECTION REPCRT l=

o w asica ar:ca g<o r,rcar.cn gs.sra/srn w.as m.unca a

NOTECilVE CdATINGS e

ccer ao gav u cec. a etw a cuac4 so pwt u ur m.a

.m so.

.m 45 31 d

o Ql-QP-ll. 4 -10 Re v.

n t

Mses.No'n 3*dMI.MS"*" CTNIlfiN CI,"#,c rion CE*=9Enom asp. *tsutts O =enerio ca ater o. act., ucasts rt=. san,actoa,

  1. 8 O e c90a cowautto, unsanwactone ertus usrto enow

,,,y,,un

~.

INSMCTION ATTA18uTES e

garg 3

l COAT NO.:

SURFACER FINISH C0AT l

l l

l ORIGINAL REPAIR l

l 1

l. ' VERIFY SURFACE FREE OF GREASE AND Olt PER PARA. 3.1.1 l l!

l (REQUIRED ONLY IF SURFACE PREPARATION 15 BV ONE OF THE l l j

I l

FOLLOWING:)

I

n. WATER BLASTING l

l l

t I

WATER BLASTING WITH SAND IPUECTION DRV SAMO BLASTING ll l

l t.

IUSN HANIERING l l 6 l

1

2. I L
  • CE PREPARATION IN ACCORDANCE WITH CCP-40. LIST l 1 ! l l 6I I

8 ** 35 0F SURFACE PREPARATION:

I l ll l

3. I VE?l'Y SURFACE PREPARATION ACCEPTABLE AND ALL LOOSE AN6 i l i

FOREIGN MATERI AL REMOVED PER PARA. 3.1.3 l

l l

4 VERirv CONCRETE CURING / REPAIRS COMPLETE (SURFACER ONLVI I

l PER PARA. 3.1. and 3.1. 3 )

l e l

l t

I

5. I VERIFf CURE TIME OF PREVIOUS COAT BEFORE FIN 15H COAllN$ (

l i PER PARA. 3.4.2.2 (FINISH COAT ONLV) l l l

6. I RECORO T00K GARGE READINGS PER PARA. 3.5 f!NISH C0AT l l l l

I l

g l REPAf R$ O'tLY)

MIN. OFT!

l I (

l l

l MAX. OF T:

AVG. DFT:

l l l

(

i e I f

1. I VERIFY COATED SURFACER FREE OF UNACCEPTABLE DEFECIS l PRIOR TO FI'al5H COAf ONLY PER PARA. 3.4.2.1 l l l l

I l I l I

8. I VERIFY MIXtre OPERATIONS PER PARA. 3.2 l } l i

a-t157 MATE 0 fat NAMf-I b.

BATCH Nt;MMER(5) 0F MATERI AL:

l l l l

I

__ THINNER

____ CURING AGENT l l I

I BASE _. _, _ _ _

FILLER l l t

l I ' t 9, ! VERIFY THAT Slitte LIFE OF COAflNG MATERIALS HAS NOT l EXPIRED.

l a

l (CONTINUtt ON NEXT PAGE) i t

i

- TUGCO CA Pe.we see s

~

7,,-,-

INSTRUCTION I

WSION PAGE NW8ER O

TEXAS UTiunES GENERATING CO.

CPSES QI-QP-11.4-10,

19 JUN1' N 16 of 20 ATTACHMENT 1 (Continued)

CCM ANCHE PCAM 3? TAM ELECTRIC STATICN INSPECTION REPQRT Q!-QP-11.4-10. R.

(supott.wsNTAu theet 2 of 1

FOR F1,'LL HEACINGS. SEE SHEET I NO.

3

'#((

INSFECTICN ATTa18UTES tuu s

10 lVC RIFY 01)Al f f !C ATi0tl 'W APPtfCAT005 ftl5T APPtfCAT095) i i i l

i i l 4 6

i t I i i

11.

IVERIFY AMBfFNT rnN"Iff0NS PER DADA. 3.3_1 1 I l l

InDY Ri!t R-WFT R!!! n -

1 1 1 ISDPFAff TFMP nFU PnfMT-0 l IREt4TIVE WUMfDffY-I !

l 11 VFRf FY Af R t'IPPI Y FRFr OF enNTAMf MAf f nN AND THAT TTAP i l i

FffTERS. AND SEPARATOR $ ARE INSTAffFD 1 1 1

l 13_

IRECORD WET FftM THICrfitss i I i l I t

14 Vo!!!MF $0!fnt-6 1 1 6

0FT

  • WFT v
  • YOf int t 1 i i

Mf9_ WFT*

MIN _ 0FT*

  • I I I

mat _ WFT!

MAN OFT!

I i l l

AVG. WFT AVG, OFT!

l i l

i

-(REGORD ADDITIONAL SETS OF READINGS IN REMARKS) e i i

e#

} l REMAAN38 (Owet.5PECS.tTCJ i

a i

i I

I I

I en I

gg g.

gg 9

$1@e S.@ $

M

=

OC 9fet?";8 el 9

Pupuut ME t

e ISSUE INSTRUCTION REVISION PAGE TEXAS UTILITIES GENERATING CO.

CPSES Q!-QP-11.4-10 19 JUN 131984 17 of 20 ATTACHMENT 2 Shelf Life fia teria,1, flutec 11 Base & Curina Acent 12 months

'futec 11S Base & Curing Agent 12 months Nutec 1201 Gase & Curing Agent 12 months Thinnners and Sand Filler Unlimited POT LIFE NUTEC 115 and 11

,$5 N

.w.

i&

elf

  • w so so p
  • 80 mo too TEnPERATURE *F 2+

fiUTEC' 1201

/6 FCTLlH b 445 /0i

+-

..t..

~

Jo*

so*

m*

so*

g ace

  • TEnPERATURE 4 (NDUCTION TIMES FOR NUTEC 1201 Temn. (*F) 50-59 45 min.

60- M 30 min.

70-79 20 min.

l P.0-90 10 min.

t 91-100 fione

- TUGCO CA rom w.*

i.

4 I

INSTRUCTION ISSUE

, REVISION PAGE l

DATE TEXAS UTILITIES GENERATING CO.

I CPSES QI-QP-11.4-10 19 JUN 131984 18 of 20 l

ATTACHMENT 3 Total Allowable Number of Surface Area,(s.g.,f_t_.,

Points of, Olscontinul_ty, j

Up to 10 1

10-50 2

50-100 5

100-500 10 500-1000 15 1000-5000 25 No gross discontinuities are acceptable.

I

~

L.-

ATTACHMENT 4 u

l' Percent volume solids for unthinned concrete coatings are i

as follows:

78%

NUTEC 11 88%

NUTEC 115 54%

tlVTEC 1201 i.

EXAMPLE:

11 mils WFT X 54% = 5.94 mils 0FT l

For thinned nixes:

V.o.l.u.m.e,p,,un,(h.i.nn.e.d. coa t,1.ni-- -- - -

- X

1. Volume Solids = VoTume-of unthinned coating + Volume thinner i

4 Volume Solids (anthinned)

I l

NOTE:

let above equation, volume must be expressed in the same Unit of measure.

l 1

i i

TUGcoCA

~~~

l

%=i

Y. Y. N ISSUE-INSTRUCTION REVISION PAGE DATE NUMBER I

TEXAS UTILITIES GENERATING CO.

CPSES 01-QP-11.4-10 l19 MI 19 of 20 ATTACHMENT 5 COMANCnt FtAM STtAM Et.EC TRIC S TATtong senn

  • INSPECTION REPORT jao

,3,3aw,srnucr =t :ssionar<m irtw assenier.c= T ?it:5

)w.r.r.c.rs=

w,,

PROTECTIVE COA a caa=Gt so 6 wusw s cm isu tau.* osv.no.

a gaar o c ;cc e at,

,Iarv wuc me.

.. :. n. n.4.to. e...

C N:ni'c',

CSS 'mht'* C$J#dM:

C ' h eto.

OP'EsEl'rc>e asp atsusrs

].nspectics c:wntrio, ask ses casts artus sarssacre**

  • * '" 5 '5 5 ' '"

^

I O.= sat:rm ::wnttro. wasarivacroa,.rews vitro er.e.

k IN SPC *. TION ATTRIBU TES

.,,t,catt gigyaggag 6 r!MI54 C0AT F!.!AL ACCEPTANCE l l8 l

II Verify cu e of fintsn coat per 7sra. 3.6.1.

I I i

t.

! I I i

2... + yectfv finish coat centimaity car Para. 3.6.2.

l 1 i

,i i

l 1 1

l l

l J.

[

visi, ally inspect finisn coat per Para 3.6.3.

} }

I l 8

l t 8 l

t 4

l t l I

I i Ii l

i t

! I i

l f

9 I

i I

i I

8 i

I i i t

i e

' I l

i i

l l

I !

3 I

eseaans e esos.setts. t't #

4

(

st.arte gcn,c

'1A C EO 9

8 'ad ' 8 CC ' '55'48

'e SI TUGCC CA

1 INSTRUCTION ISSUE PAGE REVISION M SER MTE TEXAS UTluTIES GENEMATING CO.

CPSES 0

M3' 20 of 20 QI-QP-11.4-10 ATTACHMENT 6 oasassCsed POnat S TEA 48 Es.EC?Asc $ FAT 10N g

g INSPECTION REPORT 1713 M9eAIPT10st gun w e rmus E avai sms / BTWuGTW81 L esasemaTips WTEC 10 m

s wur,.ma e

nur ac set a suv e r-so

= r --

we rm reuse eser.sa AS.31 e

a Of OP 11.4 10 Rev.

a Ci" :st,"a, OP"&1tMd,"a O r5.'.m".".

0 %,,

O P",,,;g, WIER ASSulf8 a

c,=

um..u.

ucA ur=<r, c

=vi une.

e==v

,.== ue=

j marterion arraisures r

L1 (E

  • g 1.

Verify concrete has been cleared ner Para. 1.7.1 2.

Verify that WTEC to is not analted under inelmansat conditions ner Para. 3.7.2 3.

Verify that the WTEC to air tunolv and soutament it in f

accordance with Ref,1 A. Der Para. 3.7,3.

4.

Verify mining operations per Para. 3. 7.4.

5.

Verify aualification of ancileators f ttte annif eators) oer Para. 3.3.5.

6.

Verify the acolleation rate of WTEC 10 car Para.1.7.5.

7.

Verify coated surface free of unacceptable defectstags.

surface irreaularities or eacessive build un ner Para.

1.7.8.

l g

g e

I l

I aum "a a a ctoun a

e,. u,s.

.t t

Mh

..