ML20138N876
| ML20138N876 | |
| Person / Time | |
|---|---|
| Site: | South Texas, 05000000 |
| Issue date: | 01/25/1978 |
| From: | Gary Arnold IMPERIAL PROFESSIONAL COATINGS |
| To: | |
| Shared Package | |
| ML20138M609 | List:
|
| References | |
| FOIA-85-59 215-78-G, NUDOCS 8511060097 | |
| Download: ML20138N876 (7) | |
Text
.. __
.- ;;. 3
,.e., ;c. - 7,y a - -, -~.. - - ~ -.- - - - ;; m -.. r.__. --,.
t l
3 l
TECHNICAL REPORT I
I NUMBER 215-78-G TITLE COMPATIBILITY TESTING - CONCRESIVE 1411 EPOXY MORTAR FOR CUSTOMER BROWN Ts ROOT Submitted by: Gerald E. Arnold Approved: y Date: 1/25/78 SOUTHERN LMPERIAL COATINGS CORPORATION,INC.
New Orleans, Louisiana 70189 P. O. Box 29077,
+
Phone: (504) 254-1433 i
L a
n.
he, e
.nf t.
,,,,..,,,-,..e.neH.
8511060097 851016
- - ~
~~
~~
GARDEBS-59 PDR
- ~a
..w ~ : n :,-
- . 297.
,. ~.. - -. -.
w
~ i
(
T.R.#215-78-G
- 1 Page 1.
i 1
stnogutY - Compatibility testing was initiated at the request of Brown I
and Root engineers relative to the South Texas Project. E1cometer adhesion and DBA tests were conducted to demonstrate the compatibility of Concresive 1411 to Imperial's NUTEC 11S/REACTIC 1201 system. The results of these tests indicate that the Concresive 1411 is compatible with the Ispecial products.
L Ilfrn0 DUCTION - Concresive 1411 is a 100% epoxy masonry and concrete mortar which is designated for use in repairing concrete damage at the South Texas Project. Brown and Root engineers requested that Imperial conduct tests to dem nstrate that the proposed NUTEC llS/REACTIC 1201 g
coating system and Concresive 1411 are compatible.
METHODS -
a) Specimens - 2" x 3 " x 2" concrete specimens prepared in accordance with Bechtel CP956 l
Coupon No.
Batch Pour Date Curing Compound 478, 479 1-53
.5-6-76 NOTEC #10 (5606/5607) s 486 509, 512, 1-53 5-6-76 NONE
& 513 b) Surface preparation - 100 psi compressed air c) Application and Curing Data I
Product Batch #
Date and Time F/% R.H.
DET Cure Data Applied Concresive Lot 77654 1-5-78 70 F/64%
Fill 4 days 9 70-80*
1411 9:30 a.m.
Voids
- 45-65% R.H.
NUTEC #11S 3227/3228/
1-9-78 58 F/46%
.020".025" 3 days 9 70-80' 3229 1:30 p.m.
45-65% R.H.
REACTIC #1201 2467/2568 1-12-78 58 F/66%
.005".006" 4 days 9 70-80' 10:00 a.m.45-654 R.H.
- Concresive 1411 was applied to the entire surface - not just voids.
I I
An approximate DFT of 5-10 mils was obtained.
d) Testing v
1.
Elcometer adhesion testing was performed in accordance with Imperial Test Method 03.
-v
.-.--.,,-_-.,,7
> a;.
__.w y.v
- y.. -. -.. c.. r.-.,,......
3 T.R. 8215-78-G Page 2.
1 High strength aluminum dollies were applied to the mated spec 4==n= by means of an epoxy resin-type adhesive.
i The dollies were placed 1-13-78 at 11:00 a.m. and removed with an E1cometer adhesion testar 1-16-78 at 9:00 a.m.
2.
two of the six concreta specimens were then submitted to Coastal Science Associates for DBA testing in accordance with the test parameters established for the South Texas Project. The concrete coupons were subjected to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> i
of LOCA simulated conditions with a==w4==
temperature of j
307 F. and a =mwi=ina pressure of approximately 57 psig.
The coating damage inflicted by the Elcometer testing was J
not repaired prior to IBA testing.
i RESULTS -
a) Elcometer Adhesion i
i l
Lab. Panel #
Concrete Coupon 9 Form required Mode of I
to remove dolly Failure 3706 478 350 psi 100% concrete failure l
3707 479 500 psi 80s 1411/concr.
f 20tconcrete 3708 486 475 psi 100% concrete failure 3709 509 450 psi 100% concrete failure
.3710 512 500 psi 100% concrete failure 3711 513 400 psi 1004 concrete failure b) DBA Lab. Panel #
Concrete Coupon #
Results i
3710 479
- Coating intact. Some delamination on broomed and smooth surfaces.
3707 512 No Defacts.
- Delamination was determined by " sounding" the test specimen. This....
N*'
WW-
_ eB N&4e nese he.
m--,,.
. ~. -. -
. v. --:.s +-.m w om Y: y:m.: :.yfN" Tr4 wMM' ~":'"qq.7%-Tf:' -:- ^*'
l_
j i
4 Or%
T.R.9215-78-G Page 3.
i observation was confirmed by removing the coating in the
" defective" areas. The failure was found to occur betwoen the Concresive 1411 and the concrete surface.
CONCLUSIOBIS - The results of the Eloometer adhesion and DBA testing demonstrates the campatibility of Concresive 1411 with the Imperial coating system. In all tests, the bond between the Concresive 1411 and the NOTEC #11S was excellent.
Some failures, however, did occur between the concrete surface and the Concresive 1411. Speciman # 3707 exhibited scoe loss of adhesion at the substrate in the adhesion test and specimen #3710 exhibited signs of
}
delanination in the ImA test. This potentimi problem can be avoided by good surface preparation practices. The concrete speci==n= used had aged for 20 months. Apparently some con *==ination was present which was not readily removed by 100 psi compressed air. Use of Concresive 1411 should be restricted to damaged concrete, voids, and tie holes where a " physical bond" will be achieved and improve the performance of the overall system.
Excess Concresive 1411 should be removed to avoid any potential adhesion problems.
REFERENCE - Lab. Notebook #56, p.39 Q+
3 l
]
1
/-
i 4
-~
n,,---
r.-
,.,,..n,
- -... - - - ~. - -,...
---.r,,,
,,,,nm,-,_,--,,,,n
, - - ~ ~ - -. - - - -.. -
1
-(
.m.
..~ m y ae m.y._. v-g..
,s.,
..,...,,_,7 j
ti '
~@
COASTAL SCIENCE ASSOCIATES, INC.
6999 CANAL BLVD.
NEW ORLEANS, LOUISIANA 78124 TEL. 584-283-7251 a
SUBJECT:
DESIGN BASIS ACCIDENT COATINGS TEST REPORT.
DATE:
1/18/78 DBA TEST CONDITIONS:
HOUSTON LIGHT AND POWER, 24 HR. SCREEN TEST HIGHEST TEMPERATURE CDEG. F) REACHED DURING RUN 307 SAMPLE NUMBER:
3787 SAMPLE TYPE:
CONCRETE COUPON SAMPLE #
DESCRIPTION o
3787 SIDE la NO DEFECTS SIDE 2: NO DEFECTS SIDE 3: NO DEFECTS en SIDE 4: NO DETECTS REPORT VRITTEN FOR:
SOUTHERN IMPERIAL COATINGS REPORT #
059811778 APPROVED BY....
I I
i v
,m#
. x.. 7.
..g. ~. i n.p..
- g. m -:g y z,.
~
..e 4
4 O
COASTAL SCIENCE ASSOCIATES, INC.
6989 CANAL BLVD.
NEW ORLEANS, LOUISIANA 79124 TEL. 594-283-7251
SUBJECT:
DESIGN BASIS ACCIDENT COATINGS TEST REPORT.
DATE:
1/18/78 DBA TEST CONDITIONS:
HOUSTON LIGHT AND POWER, 24 HR. SCREEN TEST HIGHEST TEMPERATURE (DEG. F) REACHED DURING RUN 387 SAMPLE NUMBER:
3719 SAMPLE TYPE:
CONCRETE COUPON SAMPLE #
DESCRIPTION 3718 SIDE'1: ( SIDE WITH SAMPLE #3 NO DEFECTS SIDE 2: DELAMINATION OVER MOST OF SIDE. NO CRACKS OR BLISTERS.
SIDE 3: NO DEFECTS SIDE 4: DELAMINATION BELOV ADHESION TEST CUT. NO OTHER DEFECTS i
i REPORT VRITTEN FOR:
SOUTHERN IMPERIAL REPORT #
85991 778 i-APPROVED BY...
5 s
O O*O S
_ MW O'
'-_S'h-+
7g
- m 3
- e.. : e.
- s.. a a,' g yjs...y..y
- 2...=,
4
~ '
d
.r#
Box 2907' New Orleans. l.ou s,ana 70189 U S A 504-2541433 i
'T; ~
qi
. PROFESSIONAL COATINGS w
'~
February 24, 1978 1
1 j
Commanche Peak Steam Electric Station j
Brown & Root, Inc.
P.O. Box 1001
{
GLEN ROSE, TX 76043 v
l ATTENTICN: Mr. Don Sutton Dear Mr. Sutton l
Enclosed is a copy of Imperial's Technical Report #215-78-G demonstrating the compatibility of Concresive 1411 Epoxy Mortar, with Imperial s NtTTEC WilS/
REACTIC #1201 System.
Sincerely, s
1 41/42 GIraldE. Arnold t
Technical Support Representative i
Nuclear i
t GEA/nd Enclosure i
h
.....