ML20080H541

From kanterella
Jump to navigation Jump to search
Special Rept Spr 84-001:on 840110,licensee Entered Action Statement of Tech Spec 3.7.10 by Opening Fire Doors to Chilled Water Pump Rooms.Evaluation Determined Enough Cross Ventilation Would Occur to Ensure Cooling
ML20080H541
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 02/09/1984
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To:
NRC OFFICE OF ADMINISTRATION (ADM)
References
SPR-84-001, SPR-84-1, NUDOCS 8402140235
Download: ML20080H541 (2)


Text

~

l o

o NRC Document Control Desk Special Report (SPR 84-001)

February 9, 1984 Page #2 EVENT DESCRIPTION On January 10, 1984, the Licensee voluntarily entered Action Statement (a) of Technical Specification 3.7.10, " Fire Rated Assemblies," by opening the fire doorc to the Chilled Water Pump Rooms.

The original Chilled Water Pump installation was of the self-cooling (water) design, and the HVAC to the area was originally installed as non-essential (Non-Nuclear Safety Related).

Chilled Water Pumps "A" and "C" were changed out by a design modification to air cooled pumps. In the preliminary stages of the design change the potential need for additional area cooling to support operation of the replacement pumps was considered; however, the analytical work to fully document the issue was not completed. Further calculations and documentation are now being accomplished with a scheduled completion date of March 30, 1984.

~ Additionally, Nuclear Engineering is reviewing the equipment qualification report for the motors in conjunction with area heat loads to determine the installed qualified life of the motors.

This evaluation is scheduled to be completed by March 30, 1984.

A preliminary engineering evaluation determined that by opening the doors of the rooms to the Intermediate Building -- on loss of HVAC to the room -- enough cross ventilation would occur to ensure adequate cooling from an essential source. This resulted in the establishment of a fire watch in'accordance with Technical Specification 3.7.10.

ACTION TO BE TAKEN A supplementary report will be submitted upon completion of the analysis addressing action taken.

B402140235 840209 PDR ADDCK 05000395 7' S PDR 00 k'

L -

e Lk a

SOUTH CAROLINA ELECTRIC & GAS COMPANY POST OPPICE 764 CotuusiA. south CAROLINA 29218 O. W. DIXON JR.

Vics Pngsr0ENT February 9, 1984 NUCLEAR OranAnONS U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555

Subject:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Special Report (SPR 84-001)

Dear Sir:

Please find attached a Special Report for the Virgil C. Summer Nuclear Station. This Report is required by Technical Specification 6.9.2 as a result of entry into Action Statement (a) of Technical Specification 3.7.10, " Fire Rated Assemblies,"

on January 10, 1984.

Should there be any questions, please call us at your convenience, r trul yours,

. lxon, Jr.

RBJ:OWD/fjc

Attachment:

cc: V. C. Summer D. A. Lavigne T. C. Nichols, Jr./O. W. Dixon, Jr. J. F. Heilman E. H. Crews, Jr. C. L. Ligon (NSRC)

E. C. Roberts K. E. Nodland W. A. Williams, Jr. D. J. Richards D. A. Nauman W. C. Hehl J. P. O'Reilly J. B. Knotts, Jr.

Group Managers INPO Records Center O. S. Bradham NPCF C. A. Price File D

,s