ML20034E205
Text
Health Physics Sample Records ______________________ ~
Sample ID:
142492 Type: RLSSS Type Detail: SAND
==
Description:==
140605BD03 SOUTH LAY DOWN# 4
]Commonl Resp Org: P4000 - PROJECT MANAGEMEr
Contact:
COOPER, TERRY L Reference ID:
Comments: COUNT TO MDA Reviewed: DYNES, WILLIAM J Comments:
Origin I Mat. SizeNolume:
1913 GRAMS
==
Description:==
SOUTH LAY DOWN# 4 IColle~tioriJ Sample Tech: DYNES, WILLIAM J Tritium Req:
No Instructions:
COUNT TO MDA Comments:
COUNT TO MDA I RLS§S Exempt:
No Chem Notification:
No Offsite Analysis:
No Container Surveyed:
No Container Evaluated:
Yes LL_<?~.!~
Status: APPROVED Cross Ref Sample ID:
Survey No:
Accounting Subcode:
Unknown Mat:
NO Date: 06/06/14 07:29 Docmnt/MO/Act #:
Proposed Ship Date: 00/00/00 00:00 Sample Date: 06/05/14 12:15 Sample SizeNolume: 1913 GRAMS Evaluated:
No State Permit:
No Effluent Permit:
No Cleared For Release:
Yes Form 212 Ready:
W' Unit: NON-UNIT RE Stored By:,
Sample Loe:
Area: MS Elev: 100 Room:
Depth:
(in.)
Equip ID:
Date: 00/00/00 00:00 Other: COUNT TO MDA Material Loe:
06/19/2014 09:53 Rasterized: r Priority: N Hazardous Mat:
NO Count Time:
900 (secs.)
Page 1 of 3
Sample ID:
142492 Type: RLSSS Type Detail: SAND
==
Description:==
1406058003 SOUTH LAY DOWN# 4 I Analysis I Geometry B_ 1 L_marinelli_sand_
MCA ID Quant.
Units
--~------
30386 1913 GR Method lsoto.~ l'!_ode_ Activity Activity Uncert.
LLD/MDA 0
K-40 NT 0
TL-208 NT 0
PB-212 NT 0
81-214 NT 0
PB-214 NT 0
BE-7 AP 0
MN-56 AP 0
C0-57 AP 0
C0-58 AP 0
C0-60 AP 0
SB-124 AP 0
SB-125 FP 0
CS-134 FP 0
[_Analysis Review 0.00001204 1.55E-6 4.093E-7 8.88E-8 3.769E-7 1.226E-7 5.365E-7 1.206E-7 5.602E-7 1.525E-7 1.0421E-6 3.2428E-8 9.1097E-8 9.3582E-8 1.0581E-7 1.7561 E-7 1.1698E-7 2.9104E-7 1.1428E-7 3.0386E-8 r r r r;7 r;7
~
~
~
~
Ji1' r;7 Ji1'
~
Health Physics Sample Records Status: APPROVED FP/AP Lab Analys~~r
.000 NEESE, DAVID J
%Abund.
Atom. No.
Comments 86.476%
40 2.940%
208 2.707%
212 3.853%
214 4.024%
214 0.000%
7 0.000%
54 0.000%
56 0.000%
57 0.000%
58 0.000%
60 0.000%
124 0.000%
125 0.000%
134 0.000%
137 Re-Analize:
No Lie Rad Mat Present:
No Reviewed: COOPER, TERRY L HP Notified Name:
Hp Eng Rvw Reqd:
Yes Rad Mat Present:
Yes Comments:
06/19/2014 09:53 Rasterized: r Date Mod ID Mod Date 06/06/14 20:48 Mod Id Mod Date Date: 06/11/14 06:39 Page 2 of 3
Sample ID:
142492 Type: RLSSS Type Detail: SAND
==
Description:==
140605BD03 SOUTH LAY DOWN# 4
[ Review/Approve I Reviewed: COOPER, TERRY L Comments:
Disposition: OTHER Remarks:
Approved: COOPER, TERRY L Comments:
06/19/2014 09:53 Health Physics Sample Records Status: APPROVED Rasterized: r HP Review Date: 06/11/14 06:39 Disposition Result: Sample contains only natural isotopes Final Approval Date: 06/11/14 06:40 Page 3 of 3
SONGS HEALTH PHYSICS REPORT 6-JUN-2014 20:42
- Title
>>>>> SAMPLE PARAMETERS<<<<<
140605BD03 SOUTH LAY DOWN# 4
- ID 30386 Acquisition date: 6-JUN-2014 20:39:10. *
- Start Time:
- Stop Time:
- Quantity
- Geometry 6-JUN-2014 20:39:00.
6-JUN-2014 20:39:00.
Counting System 1.91300E+03 GR IHPS Sample Number:
B lL marinelli_sand_l Analysis Library Operator: DAVID NEEBE U2GSP 142492 HP NATURAL
>>>>> B #42-TP11663A PARAMETERS<<<<<
- Elapsed Live Time
- Elapsed Real Time
- Deadtime
- Activity Mult Factor:
- Half Life Ratio 0 00:03:00.41 0 00:03:00.45 0.0%
l.OOOOOE+OO 8.00000 Calibration Energy Offset Energy Slope Energy Tolerance:
Sensitivity 6-JUN-2014 20:09:
-4.40560E-01 5.00074E-01 1.00000 5.00000 Post-NID Peak Search Report It Energy Area Bkgnd FWHM Channel Left Pw %Err Fit Nuclides 1
238.61 38 30
- 1. 43 478.04 471 11 32.5 2.56E+OO PB-212 1
295.16 21 2
1.17 591.12 586 8 27.2 1.53E+OO PB-214 1
351.81 29 7
- 1. 87 704.40 699 10 25.7 6.llE-01 PB-214 1
583.11 29 5
2.28 1166. 93 1162 9 21. 7 5.22E-01 TL-208 1
609.44 26 2
- 1. 43 1219.60 1216 8 22.5 2.42E+OO BI-214 1
1460.86 69 4
- 1. 99 2922.23 2915 12 12.9 1.15E-01 K-40
Summary of Nuclide Activity Sample ID : 30386 Total number of lines in spectrum Number of unidentified lines Page :
2 Acquisition date 6-JUN-2014 20:39:10 Number of lines tentatively identified by NID 6
0 6
100.00%
Nuclide Type : natural Uncorrected Decay Corr Decay Corr 1-Sigma Nuclide Hlife Decay uCi/GR uCi/GR 1-Sigma Error
%Error Flags K-40 1.28E+09Y
- 1. 00 1.204E-05
- 1. 204E-05 0.155E-05 12.86 A
TL-208 3.05M
- 1. 43 2.854E-07 4.093E-07 0.888E-07
- 21. 70 A
PB-212 10.64H
- 1. 00 3.762E-07 3.769E-07 l.226E-07 32.53 A
BI-214 19.90M
- 1. 06 5.064E-07 5.365E-07 1.206E-07 22.47 A
PB-214 26.80M
- 1. 04 5.366E-07 5.602E-07 1.525E-07 27.23 A
Total Activity 1.375E-05
- 1. 393E-05 Grand Total Activity :
1.375E-05 1.393E-05 Flags: "K" Keyline not found "M"
Manually accepted "E"
Manually edited "A"
Nuclide specific abn. limit
Unidentified Energy Lines Sample ID : 30386 None Flags: "T" Tentatively associated Acquisition date Page :
3 6-JUN-2014 20:39:10
Interference Report Sample ID : 30386 No interference correction performed Acquisition date Page :
4 6-JUN-2014 20:39:10
Nuclide Line Activity Report Sample ID : 30386 Nuclide Type: natural Nuclide Energy Area K-40 1460.83 69 TL-208 72.80 74.97 84.79 ------
252.45 ------
277.28 ------
510.61 ------
583.02 29 763.06 ------
860.30 ------
PB-212 74.81 77.11 ------
87.19 ------
90.13 115. 12 238.58 38 300.03 ------
BI-214 76.86 ------
79.29 ------
609.31 26 665.44 768.35 ------
806.16 ------
934.04 1120. 27 1155.18 1238. 11 ------
1280.95 ------
1377.66 ------
1385.30 ------
1401. 48 1407.97 1509.22 ------
1583.22 ------
1661. 26 1729.58 ------
1764.49 ------
1847.41 ------
PB-214 53.17 74.81 77.11 87.19 ------
90.13 ------
241. 92 258.94 295.09 21 351.87 29 785.83 ------
839.00
%Abn 10.67*
2.14 3.60
- 1. 27 0.80 6.80
- 21. 60 86.00*
- 1. 64 12.00 10.50 17.70 6.27
- 1. 86 0.59 43.60*
3.34 0.58 0.97 46.10*
- 1. 56 4.88
- 1. 23 3.16 15.00
- 1. 69 5.92
- 1. 47 4.02 0.78
- 1. 39 2.48 2.19
- 0. 72 1.15 3.05 15.90 2.12 1.10 6.52
- 11. 00 3.88 1.15 7.46 0.55 19.20*
37.10
- 1. 09 0.59 Page :
5 Acquisition date 6-JUN-2014 20:39:10 Uncorrected Decay Corr 1-Sigma
%Eff uCi/GR uCi/GR
%Error
- 4. 211E-01 l.204E-05
- 1. 204E-05 12.86 1.070E+OO Line Not Found ------
1.156E+OO Line Not Found ------
1.506E+OO Line Not Found ------
1.745E+OO Line Not Found ------
l.645E+OO Line Not Found ------
1.035E+OO Line Not Found ------
9.198E-01 2.854E-07 4.093E-07 21.70 7.126E-01 ------
Line Not Found ------
6.341E-01 ------
Line Not Found ------
1.150E+OO Line Not Found ------
- 1. 239E+OO Line Not Found ------
l.579E+OO Line Not Found ------
1.662E+OO Line Not Found ------
2.085E+OO Line Not Found ------
1.805E+OO 3.762E-07 3.769E-07 32.53 1.562E+OO Line Not Found ------
1.229E+OO Line Not Found ------
1.320E+OO ------
Line Not Found ------
8.831E-01 5.064E-07 5.365E-07 22.47 8.131E-01 Line Not Found ------
7.078E-01 Line Not Found ------
6.754E-01 Line Not Found ------
5.861E-01 Line Not Found ------
4.982E-01 ------
Line Not Found ------
4.860E-01 Line Not Found ------
4.615E-01 Line Not Found ------
4.510E-01 Line Not Found ------
4.323E-01 ------
Line Not Found ------
4.311E-01 ------
Line Not Found ------
4.287E-01 ------
Line Not Found ------
4.277E-01 Line Not Found ------
4.165E-01 Line Not Found ------
4.120E-01 Line Not Found ------
4.103E-01 Line Not Found ------
4.114E-01 Line Not Found ------
4.128E-01 Line Not Found ------
4.187E-01 Line Not Found ------
2.929E-01 Line Not Found ------
1.150E+OO Line Not Found ------
1.239E+OO Line Not Found ------
1.579E+OO ------
Line Not Found ------
1.662E+OO ------
Line Not Found ------
- 1. 7 90E+OO Line Not Found ------
1.718E+OO Line Not Found ------
1.579E+OO 5.366E-07 5.602E-07 27.23 1.395E+OO 4.318E-07 4.507E-07 25.69 6.925E-01 Line Not Found ------
6.497E-01 Line Not Found ------
Nuclide Line Activity Report (continued)
Sample ID : 30386 Acquisition date Flag: "*"
Keyline Page :
6 6-JUN-2014 20:39:10
Minimum Detectable Activity Report Page :
7 Sample ID 30386 Acquisition date 6-JUN-2014 20:39:10 Bckgnd Energy MDA Nuclide Sum (keV)
(uCi/GR)
BE-7
- 7.
477.61 l.0421E-06 MN-54
- 0.
834.83 3.2428E-08 MN-56
- 1.
846.81 9.1097E-08 C0-57
- 17.
122.06 9.3582E-08 C0-58
- 2.
810.79 l.0581E-07 C0-60
- 3.
1173.24 1.7561E-07 SB-124
- 5.
602.73 1.1698E-07 SB-125
- 5.
427.88 2.9104E-07 CS-134
- 5.
604. 71 l.1428E-07 CS-137
- o.
661.66 3.0386E-08