Health Physics Sample Records Sample ID: 142472 Type: RLSSS Type Detail: SAND Status: APPROVED Rasterized: r

Description:

140603BD 1 CULVERT 1

!Comm_<>_!!]

. Resp Org: P4000 - PROJECT MANAGEMEr Cross Ref Sample ID: Priority: N

Contact:

COOPER, TERRY L Survey No:

Reference ID: Accounting Subcode: Unknown Mat: NO Hazardous Mat: NO Comments:

Reviewed: DYNES, WILLIAM J Date: 06/05/14 06:54 Comments:

l ..9!:l9i!l]

Mat. SizeNolume: 1821 GRAMS Docmnt/MO/Act #: Proposed Ship Date: 00/00/00 00:00

Description:

CULVERT 1 1co11ecti~

Sample Tech: DYNES, WILLIAM J Sample Date: 06/03/14 07:57 Count Time: 900 (secs.)

Tritium Req: No Sample SizeNolume: 1821 GRAMS Instructions: COUNT TO MDA Comments: COUNT TO MDA

[__B_LSSS_j Exempt: No Evaluated: No Chem Notification: No State Permit: No Offsite Analysis: No Effluent Permit: No Container Surveyed: No Cleared For Release: Yes Container Evaluated: Yes Form 212 Ready: W" l.,Q_cation~I Unit: NON-UNIT RE Area: MS Elev: 100 Room: Depth: (in.) Equip ID:

Stored By:, Date: 00/00/00 00:00 Sample Loe:

Other:

Material Loe:

06/19/2014 08:02 Page 1 of3

  • - - - - - - - - ~ - - - - - - - - - - - - - H _ e _ a . l t h Physics Sample Records Sample ID: 142472 Type: RLSSS Type Detail: SAND Status: APPROVED Rasterized: r

Description:

140603BD 1 CULVERT 1

[_Analysis]

Geometry____ MCA ID Quant. Units Method FP/AP Lab Analysis By Date Mod ID Mod Date A_ 1 L_marinelli_sand_ 30378 1821 GR _ooo PARK, MICHAEL C 06/05/1416:43 Isotope _ Mode Activity Activity Uncert. LLD/MDA %Abund. Atom. No. Comments Mod Id Mod Date 0 K-40 NT 0.0000153 1.65E-6 89.261% 40 0 PB-212 NT 4.662E-7 9.63E-8 r 2.720% 212 0 Bl-214 NT 3.461E-7 1_046E-7 r 2_019% 214 0 PB-214 NT 3.499E-7 1.264E-7 r 2.041% 214 0 AC-228 NT 6.786E-7 1.5E-7 r 3_959% 228 0 BE-7 AP 7.8081E-7 Iv" 0.000% 7 0 MN-54 AP 1.0074E-7 Iv" 0_000% 54 0 MN-56 AP 1.1917E-7 w 0.000% 56 0 C0-57 AP 7.8151E-8 w 0.000% 57 0 C0-58 AP 4.7226E-8 Iv'" 0.000% 58 0 C0-60 AP 1.3939E-7 Iv 0.000% 60 0 SB-124 AP 5_6474E-8 Iv" 0.000% 124 0 SB-125 FP 2-3502E-7 Iv'" 0.000% 125 0 CS-134 FP 7.1626E-8 Iv'" 0.000% 134 0 CS-137 FP 1.2898E-7 iv 0_000% 137

[_~_!laly.5is Revi~

Re-Analize: No Lie Rad Mat Present: No Reviewed: COOPER, TERRY L Date: 06/10/1414:18 Hp Eng Rvw Reqd: Yes Rad Mat Present: Yes HP Notified Name:

Comments:

06/19/2014 08:02 Page 2 of 3

Health Physics Sample Records Sample ID: 142472 Type: RLSSS Type Detail: SAND Status: APPROVED Rasterized: r

Description:

140603BD 1 CULVERT 1

[Revie'NjApprove~I


~ ------

HP Review Reviewed: COOPER, TERRY L Date: 06/10/1414:25 Comments:

___________________________DJ~osi_ti_o_n_ _ _ _ _ _ _ _ _ _ _ _ _ _ __

Disposition: OTHER Result: Sample contains only natural isotopes Remarks:

Final Aooroval Approved: COOPER, TERRY L Date: 06/10/14 14:25 Comments:

06/19/2014 08:02 Page 3 of 3

  • SONGS HEALTH PHYSICS REPORT 5-JUN-2014 16:34 *
  • >>>>> SAMPLE PARAMETERS<<<<< *
  • Title 140603BD 1 CULVERT 1 *
  • ID 30378 Acquisition date: 5-JUN-2014 16:31:46. *
  • Start Time: 5-JUN-2014 16:31:00. *
  • Stop Time: 5-JUN-2014 16:31:00. Counting System U2GSP *
  • Quantity 1.82100E+03 GR IHPS Sample Number: 142472 *
  • Geometry A 11 marinelli sand 1 Analysis Library HP NATURAL *
  • Operator: MICHAEL PARK *
  • >>>>> A #41-TP11679B PARAMETERS<<<<< *
  • Elapsed Live Time 0 00:03:00.48 Calibration 5-JUN-2014 08:09: *
  • Elapsed Real Time 0 00:03:00.51 Energy Offset 2.12659E-01 *
  • Deadtime 0.0% Energy Slope 4.99528E-01 *
  • Activity Mult Factor: 1.00000E+OO Energy Tolerance: 1. 00000 *
  • Half Life Ratio 8.00000 Sensitivity 5.00000
  • Post-NID Peak Search Report It Energy Area Bkgnd FWHM Channel Left PW %Err Fit Nuclides 1 238.65 51 18 1.14 477.33 472 9 20.7 8.16E-01 PB-212 1 351.94 25 14 1. 53 704.12 698 11 36.1 9.19E-01 PB-214 1 608.99 19 5 2.14 1218.70 1214 10 30.2 8.54E-01 BI-214 1 910.68 18 0 2.07 1822.66 1818 8 22.1 2.22E-01 AC-228 1 1460.69 106 6 1. 80 2923. 73 2917 12 10.8 1.14E+OO K-40

Summary of Nuclide Activity Page : 2 Sample ID : 30378 Acquisition date 5-JUN-2014 16:31:46 Total number of lines in spectrum 5 Number of unidentified lines 0 Number of lines tentatively identified by NID 5 100.00%

Nuclide Type : natural Uncorrected Decay Corr Decay Corr 1-Sigma Nuclide Hlife Decay uCi/GR uCi/GR 1-Sigma Error %Error Flags K-40 l.28E+09Y 1. 00 1.530E-05 l.530E-05 0.165E-05 10.76 A PB-212 10.64H 1. 00 4.650E-07 4.662E-07 0. 963E-07 20.66 A BI-214 19.90M 1. 08 3.198E-07 3.461E-07 1.046E-07 30.21 A PB-214 26. SOM 1. 06 3.298E-07 3.499E-07 1.264E-07 36.13 KA AC-228 6.13H 1. 00 6.756E-07 6.786E-07 l.SOOE-07 22 .11 A Total Activity 1.709E-05 1. 714E-05 Grand Total Activity : l.709E-05 1. 714E-05 Flags: "K" Keyline not found "M" Manually accepted "E" Manually edited "A" Nuclide specific abn. limit

Unidentified Energy Lines Page : 3 Sample ID : 30378 Acquisition date 5-JUN-2014 16:31:46 None Flags: "T" Tentatively associated

Interference Report Page : 4 Sample ID : 30378 Acquisition date 5-JUN-2014 16:31:46 No interference correction performed

Nuclide Line Activity Report Page : 5 Sample ID : 30378 Acquisition date 5-JUN-2014 16:31:46 Nuclide Type: natural Uncorrected Decay Corr 1-Sigma Nuclide Energy Area %Abn %Eff uCi/GR uCi/GR %Error K-40 1460.83 106 10.67* 5.314E-01 l.530E-05 1.530E-05 10.76 PB-212 74.81 ------ 10.50 1. 685E+OO ------ Line Not Found ------

77 .11 ------ 17.70 1. 782E+OO ------ Line Not Found ------

87.19 ------ 6.27 2.129E+OO ------ Line Not Found ------

90.13 ------ 1. 86 2.206E+OO ------ Line Not Found ------

115 .12 ------ 0.59 2.535E+OO ------ Line Not Found ------

238.58 51 43.60* 2.082E+OO 4.650E-07 4.662E-07 20.66 300.03 ------ 3.34 l.834E+OO ------ Line Not Found ------

BI-214 76.86 ------ 0.58 1. 772E+OO ------ Line Not Found ------

79.29 ------ 0.97 l.869E+OO ------ Line Not Found ------

609.31 19 46.10* 1.085E+OO 3.198E-07 3.461E-07 30.21 665.44 ------ 1. 56 9.985E-01 ------ Line Not Found ------

768.35 ------ 4. 88 8.685E-01 ------ Line Not Found ------

806.16 ------ 1. 23 8.283E-01 ------ Line Not Found ------

934.04 ------ 3.16 7. l 77E-01 ------ Line Not Found ------

1120.27 ------ 15.00 6 .114E-Ol ------ Line Not Found ------

1155.18 ------ 1. 69 5.973E-01 ------ Line Not Found ------

1238 .11 ------ 5.92 5.697E-01 ------ Line Not Found ------

1280.95 ------ 1. 4 7 5.585E-01 ------ Line Not Found ------

1377.66 ------ 4.02 5.401E-Ol ------ Line Not Found ------

1385.30 ------ 0.78 5.391E-01 ------ Line Not Found ------

1401.48 ------ 1. 39 5.370E-01 ------ Line Not Found ------

1407.97 ------ 2.48 5.362E-01 ------ Line Not Found ------

1509.22 ------ 2.19 5.292E-01 ------ Line Not Found ------

1583.22 ------ 0. 72 5. 296E-01 ------ Line Not Found ------

1661. 26 ------ 1.15 5.351E-01 ------ Line Not Found ------

1729.58 ------ 3.05 5.442E-01 ------ Line Not Found ------

1764.49 ------ 15.90 5.503E-01 ------ Line Not Found ------

1847.41 ------ 2.12 5.694E-01 ------ Line Not Found ------

PB-214 53.17 ------ 1.10 5.543E-01 ------ Line Not Found ------

74.81 ------ 6.52 1.685E+OO ------ Line Not Found ------

77 .11 ------ 11. 00 1. 782E+OO ------ Line Not Found ------

87.19 ------ 3.88 2.129E+OO ------ Line Not Found ------

90.13 ------ 1.15 2.206E+OO ------ Line Not Found ------

241. 92 ------ 7.46 2.067E+OO ------ Line Not Found ------

258.94 ------ 0.55 l.994E+OO ------ Line Not Found ------

295.09 ------ 19.20* l.852E+OO ------ Line Not Found ------

351. 87 25 37.10 1.662E+OO 3.298E-07 3.499E-07 36.13 785.83 --*---- 1. 09 8.495E-01 ------ Line Not Found ------

839.00 ------ 0.59 7. 964E-01 ------ Line Not Found ------

AC-228 89. 96 ------ 3.40 2.201E+OO ------ Line Not Found ------

93.35 ------ 5.60 2.279E+OO ------ Line Not Found ------

99.55 ------ 1. 30 2.389E+OO ------ Line Not Found ------

105.36 ------ 2.00 2.463E+OO ------ Line Not Found ------

108.99 ------ 0.67 2.496E+OO ------ Line Not Found ------

129.03 ------ 2.90 2.562E+OO ------ Line Not Found ------

153.89 ------ 0.84 2. 4 96E+OO ------ Line Not Found ------

209.39 ------ 4.10 2.221E+OO ------ Line Not Found ------

216.24 ------ 0.80 2.187E+OO ------ Line Not Found ------

Nuclide Line Activity Report (continued) Page : 6 Sample ID : 30378 Acquisition date 5-JUN-2014 16:31:46 Nuclide Type: natural Uncorrected Decay Corr 1-Sigma Nuclide Energy Area %Abn %Eff uCi/GR uCi/GR %Error 270.26 ------ 3.80 1.948E+OO ------ Line Not Found ------

328.07 ------ 3.50 1.738E+OO ------ Line Not Found ------

338.42 ------ 12.40 1.704E+OO ------ Line Not Found ------

340.94 ------ 0.52 1. 696E+OO ------ Line Not Found ------

409.62 ------ 2.20 l.499E+OO ------ Line Not Found ------

463.10 ------ 4. 60 l.368E+OO ------ Line Not Found ------

562.65 ------ 1. 01 1.164E+OO ------ Line Not Found ------

581. 52 ------ :Loo 1.131E+OO ------ Line Not Found ------

72 6. 63 ------ 0.87 9.173E-01 ------ Line Not Found ------

755.28 ------ 1. 32 8.833E-01 ------* Line Not Found ------

772. 28 ------ 1. 09 8.641E-01 ------ Line Not Found ------

782.12 ------ 0.59 8.534E-01 ------ Line Not Found ------

794.79 ------ 4.60 8.400E-01 ------ Line Not Found ------

830.59 ------ 0.63 8.043E-01 ------ Line Not Found ------

835.60 ------ 1. 71 7.996E-01 ------ Line Not Found ------

840.44 ------ 0.94 7.951E-01 ------ Line Not Found ------

904.29 ------ 0.89 7.403E-Ol ------ Line Not Found ------

911.16 18 29.00* 7.353E-01 6.756E-07 6.786E-07 22 .11 964.64 ------ 5.80 6.962E-01 ------ Line Not Found ------

968.97 ------ 17.40 6.933E-01 ------ Line Not Found ------

1246.60 ------ 0.57 5.673E-01 ------ Line Not Found ------

1459.19 ------ 1. 06 5.315E-01 ------ Line Not Found ------

1496.00 ------ 1. 05 5.296E-01 ------ Line Not Found ------

1501. 44 ------ 0.58 5.294E-01 ------ Line Not Found ------

1580.30 ------ 0. 71 5.295E-01 ------ Line Not Found ------

1588.23 ------ 3.60 5.298E-Ol ------ Line Not Found ------

1630.47 ------ 1. 95 5.324E-01 ------ Line Not Found ------

1638.10 ------ 0.54 5.330E-01 ------ Line Not Found ------

Flag: "*" = Keyline

  • , \

Minimum Detectable Activity Report Page : 7 Sample ID 30378 Acquisition date 5-JUN-2014 16:31:46 Bckgnd Energy MDA Nuclide Sum (keV) (uCi/GR)

BE-7 5. 477.61 7.8081E-07 MN-54 2. 834.83 1.0074E-07 MN-56 3. 846.81 l.1917E-07 C0-57 15. 122.06 7.8151E-08 C0-58 0. 810.79 4. 7226E*-08 C0-60 2. 1332.50 l.3939E-07 SB-124 1. 602.73 5.6474E-08 SB-125 4. 427.88 2.3502E-07 CS-134 2. 604. 71 7.1626E-08 CS-137 5. 661. 66 1. 2898E-07