ML20034E193
Text
Health Physics Sample Records Sample ID:
142505 Type: RLSSS Type Detail: SAND
==
Description:==
140606148D 05 NORTH LAYDOWN # 9
[Common Resp Org: P4000 - PROJECT MANAGEMEr
Contact:
COOPER, TERRY L Reference ID:
Comments: COUNT TO MDA Reviewed: DYNES, WILLIAM J Comments: COUNT TO MDA LQ.r:igin l Status: APPROVED Cross Ref Sample ID:
Survey No:
Accounting Subcode:
Date: 06/09/14 08:27 Unknown Mat:
NO Mat. SizeNolume:
2041 GRAMS Docmnt/MO/Act #:
Proposed Ship Date: 00/00/00 00:00
==
Description:==
NORTH LAYDOWN #9
[Collecti~~
Sample Tech:
DYNES, WILLIAM J Tritium Req:
No Instructions:
COUNT TO MDA Comments:
COUNT TO MDA RLSSS I Exempt:
No Chem Notification:
No Offsite Analysis:
No Container Surveyed:
No Container Evaluated:
Yes I Locationl Unit: NON-UNIT RE Stored By:,
Sample Loe:
Area: MS Other: COUNT TO MDA Material Loe:
06/19/2014 09:03 Sample Date: 06/06/1410:00 Sample SizeNolume: 2041 GRAMS Evaluated:
No State Permit:
No Effluent Permit:
No Cleared For Release:
Yes Form 212 Ready:
1'i" Elev: 100 Room:
Depth:
(in.)
Equip ID:
Date: 00/00/00 00:00 Rasterized: r Priority: N Hazardous Mat:
NO Count Time:
900 (secs.)
Page 1 of 3
Sample ID:
142505 Type: RLSSS Type Detail: SAND
==
Description:==
14060614BD 05 NORTH LAYDOWN # 9 IAnalysisl Geometry C_ 1 L_marinelli_sand_
MCA ID Quant.
Units 30425 2041 GR Method
_lsotop~ _ Mod~_ Activity Activity Uncert.
LLD/MDA 0
K-40 NT 8.416E-6 0
TL-208 NT 1.965E-7 0
PB-212 NT 7.808E-7 0
Bl-214 NT 3.825E-7 0
PB-214 NT 7.435E-7 0
RA-226 NT 2.861 E-6 0
AC-228 NT 4.851E-7 0
U-235 NT 1.77E-7 0
BE-7 AP 5.4378E-7 0
MN-56 AP 2.517E-8 0
C0-57 AP 8.0595E-8 0
C0-58 AP 8.7156E-8 0
C0-60 AP 8.9426E-8 0
SB-124 AP 6.5107E-8 0
SB-125 FP 9.8885E-8 0
CS-134 FP 6.7602E-8 0
[Analysis Review I 1.028E-6 6.11 E-8 9.71E-8 8.18E-8 1.821 E-7 1.147E-6 1.735E-7 7.1 E-8 r
Iv w w
Iv Iv Iv Iv Iv Iv Iv Health Physics Sample Records Status: APPROVED FP/AP Lab Analy~i~_}'
.000 NEEBE, DAVID J
%Abund.
Atom. No.
Comments 59.933%
40 1.399%
208 5.560%
212 2.724%
214 5.295%
214 20.374%
226 3.455%
228 1.260%
235 0.000%
7 0.000%
54 0.000%
56 0.000%
57 0.000%
58 0.000%
60 0.000%
124 0.000%
125 0.000%
134 0.000%
137 Re-Analize:
No Lie Rad Mat Present:
No Reviewed: COOPER. TERRY L HP Notified Name:
Hp Eng Rvw Reqd:
Yes Comments:
06/19/2014 09:03 Rad Mat Present:
Yes Rasterized: r Date Mod ID Mod Date 06/09/14 20:43 Mod Id Mod Date Date: 06/11/14 08:01 Page 2 of 3
Health Physics Sample Records Sample ID:
142505 Type: RLSSS Type Detail: SAND Status: APPROVED
==
Description:==
14060614BD 05 NORTH LAYDOWN # 9 I __ Re~ew/Ap_p_rove I HP Eng Review Reviewed: COOPER, TERRY L Date: 06/11/14 08:02 Comments: U-235 is likely mis-lD'd off the Ra-226 energy peak Disposition: OTHER Remarks:
Approved: COOPER, TERRY L Comments:
06/19/2014 09:03 Disposition Result: Sample contains only natural isotopes
~~~~~~~~-F_i_n_al~Appro~v~a~I~~~~~~~~~~~~--~~~~~~~~~
Date: 06/11/14 08:02 Rasterized: r Page 3 of 3
SONGS HEALTH PHYSICS REPORT 9-JUN-2014 20:39
- Title
>>>>> SAMPLE PARAMETERS<<<<<
14060614BD 05 NORTH LAYDOWN # 9
- ID 30425 Acquisition date: 9-JUN-2014 20:36:41. *
- Start Time:
- Stop Time:
- Quantity
- Geometry 9-JUN-2014 20:36:00.
9-JUN-2014 20:36:00.
Counting System 2.04100E+03 GR IHPS Sample Number:
C lL marinelli_sand_l Analysis Library Operator: DAVID NEEBE U2GSP 142505 HP NATURAL
>>>>> C #41-TP11750A PARAMETERS<<<<<
- Elapsed Live Time
- Elapsed Real Time
- Deadtime
- Activity Mult Factor:
- Half Life Ratio 0 00:03:00.43 0 00:03:00.48 0.0%
1.00000E+OO 8.00000 Calibration Energy Offset Energy Slope Energy Tolerance:
Sensitivity 9-JUN-2014 19:38:
-1.08890E-01 4.99807E-01 1.00000 5.00000 Post-NID Peak Search Report It Energy Area Bkgnd FWHM Channel Left PW %Err Fit Nuclides PB-214 1
186.32 29 31
238.49 95 17 1.17 477.36 474 8 12.4 7.98E-01 PB-212 1
295.07 34 10
- 1. 33 590.55 586 10 24.5 7.29E-01 PB-214 1
351.91 47 11
- 1. 73 704.26 700 9 19.2 3.29E-01 PB-214 1
583.37 16 2
- 1. 40 1167.26 1162 10 31.1 8.84E-01 TL-208 1
609.62 25 0
- 1. 51 1219.76 1215 9 21. 4 1. 30E+OO BI-214 1
911. 21 14 4
- 1. 99 1822.97 1818 9 35.8 1.45E+OO AC-228 1
1461.06 68 0
- 1. 75 2922.52 2917 12 12.2 3.16E-01 K-40
Surrunary of Nuclide Activity Sample ID : 30425 Total number of lines in spectrum Number of unidentified lines Page :
2 Acquisition date 9-JON-2014 20:36:41 Number of lines tentatively identified by NID 9
0 9
100.00%
Nuclide Type : natural Uncorrected Decay Corr Decay Corr 1-Sigma Nuclide Hlife Decay uCi/GR uCi/GR 1-Sigma Error
%Error Flags K-40 l.28E+09Y
- 1. 00 8.416E-06 B.416E-06
- 1. 028E-06 12.21 A
TL-208 3.05M
- 1. 62
- 1. 216E-07 l.965E-07
- 0. 611E-07
- 31. OB A
PB-212 10.64H
- 1. 00 7.789E-07 7.BOBE-07 0.971E-07 12.44 A
BI-214 19.90M
- 1. OB 3.545E-07 3.825E-07
- 0. BlBE-07
- 21. 38 A
PB-214 26.BOM
- 1. 06 7.026E-07 7.435E-07 l.821E-07 24.49 A
RA-226 1600.00Y
- 1. 00 2.861E-06 2.861E-06 1.147E-06 40.10 A
AC-228 6.13H
- 1. 00 4.830E-07 4.851E-07
- 1. 735E-07 35.77 A
0-235 7.04E+08Y
- 1. 00 1.770E-07 l.770E-07
- 0. 710E-07 40.10 A
Total Activity 1.389E-05 1.404E-05 Grand Total Activity :
1.389E-05 l.404E-05 Flags: "K" Keyline not found "M"
Manually accepted "E"
Manually edited "A"
Nuclide specific abn. limit
Unidentified Energy Lines Sample ID : 30425 None Flags: "T" Tentatively associated Page :
3 Acquisition date 9-JUN-2014 20:36:41
Interference Report Sample ID : 30425 No interference correction performed Acquisition date Page :
4 9-JUN-2014 20:36:41
Nuclide Line Activity Report Page :
5 Sample ID : 30425 Acquisition date 9-JUN-2014 20:36:41 Nuclide Type: natural Uncorrected Decay Corr 1-Sigma Nuclide Energy Area
%Abn
%Eff uCi/GR uCi/GR
%Error K-40 1460.83 68 10.67*
5.560E-01 8.416E-06 8.416E-06 12.21 TL-208
- 72. 80 ------
2.14 1.486E+OO ------
Line Not Found ------
74.97 3.60 l.577E+OO Line Not Found ------
84.79 ------
- 1. 27 1.917E+OO Line Not Found ------
252.45 ------
0.80 2.004E+OO Line Not Found ------
277.28 ------
6.80 l.917E+OO Line Not Found ------
510.61 ------
- 21. 60 l.298E+OO ------
Line Not Found ------
583.02 16 86.00*
1.157E+OO l.216E-07
- 1. 965E-07 31.08 763.06 ------
- 1. 64 8.934E-01 Line Not Found ------
860.30 ------
12.00 7.922E-01 Line Not Found ------
PB-212 74.81 10.50 1.570E+OO Line Not Found ------
77.11 0
17.70 1.690E+OO O.OOOE+OO O.OOOE+OO 0.00 87.19 ------
6.27
- 1. 983E+OO Line Not Found ------
90.13 ------
- 1. 86 2.055E+OO Line Not Found ------
115. 12 0.59 2.376E+OO Line Not Found ------
238.58 95 43.60*
2.055E+OO 7.789E-07 7.808E-07 12.44 300.03 ------
3.34 l.843E+OO ------
Line Not Found ------
BI-214 76.86 ------
0.58 1.651E+OO ------
Line Not Found ------
79.29 ------
0.97 1.741E+OO Line.Not Found ------
609.31 25 46.10*
- 1. lllE+OO 3.545E-07 3.825E-07
- 21. 38 665.44
- 1. 56 1.023E+OO Line Not Found ------
768.35 ------
4.88 8.873E-01 ------
Line Not Found ------
806.16 ------
- 1. 23 8.454E-01 ------
Line Not Found ------
934.04 3.16 7.310E-01 ------
Line Not Found ------
1120.27 15.00 6.242E-01 ------
Line Not Found ------
1155. 18
- 1. 69 6.105E-01 ------
Line Not Found ------
1238.11 ------
5.92 5.846E-01 ------
Line Not Found ------
1280.95 ------
- 1. 4 7 5.747E-01 ------
Line Not Found ------
1377.66 ------
4.02 5.602E-01 Line Not Found ------
1385.30 ------
0.78 5.595E-01 Line Not Found ------
1401.48 ------
- 1. 39 5.583E-01 Line Not Found ------
1407.97 ------
2.48 5.578E-01 Line Not Found ------
1509.22 ------
2.19 5.568E-01 ------
Line Not Found ------
1583.22 ------
- 0. 72 5.628E-01 ------
Line Not Found ------
1661. 26 ------
1.15 5.753E-01 ------
Line Not Found ------
1729.58 ------
3.05
- 5. 918E-01 Line Not Found ------
1764.49 ------
15.90 6.023E-01 ------
Line Not Found ------
1847.41 ------
2.12 6.331E-01 ------
Line Not Found ------
PB-214 53.17 ------
1.10 5.203E-01 ------
Line Not Found ------
74.81 ------
6.52 1.570E+OO Line Not Found ------
77.11 0
- 11. 00 1.690E+OO O.OOOE+OO O.OOOE+OO 0.00 87.19 ------
3.88 l.983E+OO Line Not Found ------
90.13 ------
1.15 2.055E+OO Line Not Found ------
241. 92 7.46 2.043E+OO Line Not Found ------
258.94 0.55 1.981E+OO Line Not Found ------
295.09 34 19.20*
l.859E+OO 7.026E-07 7.435E-07 24.49 351.87 47 37.10
'1.686E+OO 5.481E-07 5.800E-07 19.19 785.83 ------
- 1. 09 8.674E-01 ------
Line Not Found ------
839.00 ------
0.59 8.122E-01 ------
Line Not Found ------
Nuclide Line Activity Report (continued)
Page :
6 Sample ID : 30425 Acquisition date 9-JUN-2014 20:36:41 Nuclide Type: natural Uncorrected Decay Corr 1-Sigma Nuclide Energy Area
%Abn
%Eff uCi/GR uCi/GR
%Error RA-226
- 81. 07 ------
0.18 1.802E+OO Line Not Found ------
186.11 29 3.28*
2.260E+OO 2.861E-06 2.861E-06 40.10 AC-228 89.96 ------
3.40 2.051E+OO Line Not Found ------
93.35 ------
5.60 2.124E+OO Line Not Found ------
99.55 ------
- 1. 30 2.229E+OO Line Not Found ------
105.36 2.00 2.301E+OO Line Not Found ------
108.99 ------
0.67 2.335E+OO Line Not Found ------
129.03 ------
2.90 2.414E+OO Line Not Found ------
153.89 ------
0.84 2.377E+OO Line Not Found ------
209.39 ------
4.10 2.168E+OO Line Not Found ------
216.24 0.80 2.141E+OO Line Not Found ------
270.26 ------
3.80 1.941E+OO ------
Line Not Found ------
328.07 ------
3.50 1.756E+OO Line Not Found ------
338.42 12.40 1.725E+OO Line Not Found ------
340.94 ------
0.52 1.718E+OO Line Not Found ------
409.62 2.20 1.531E+OO Line Not Found ------
463.10
- 4. 60 1.401E+OO ------
Line Not Found ------
562.65 ------
- 1. 01 1.195E+OO Line Not Found ------
581. 52 3.00 l.160E+OO Line Not Found ------
726.63 0.87 9.382E-01 ------
Line Not Found ------
755.28 ------
- 1. 32 9.027E-Ol ------
Line Not Found ------
772. 28
- 1. 09 8.827E-01 ------
Line Not Found ------
782.12 0.59 8, 716E-01 Line Not Found ------
794.79
- 4. 60 8.576E-01 ------
Line Not Found ------
830.59 0.63 8.205E-01 ------
Line Not Found ------
835.60 ------
- 1. 71 8.155E-01 ------
Line Not Found ------
840.44 ------
0.94 8.108E-01 ------
Line Not Found ------
904.29 ------
0.89 7.542E-01 ------
Line Not Found ------
911.16 14 29.00*
7.486E-01 4.830E-07 4.851E-07 35.77 964.64 5.80 7.091E-01 ------
Line Not Found ------
968. 97 17.40 7.061E-01 ------
Line Not Found ------
1246.60 ------
0.57 5.825E-01 ------
Line Not Found ------
1459.19 ------
- 1. 06 5.560E-01 ------
Line Not Found ------
1496. 00
- 1. 05 5.563E-01 ------
Line Not Found ------
1501. 44 0.58 5.565E-01 ------
Line Not Found ------
1580.30 ------
0.71 5.624E-01 ------
Line Not Found ------
1588.23 3.60 5.634E-01 ------
Line Not Found ------
1630.47 ------
- 1. 95
- 5. 696E-01 Line Not Found ------
1638.10 0.54 5.709E-01 ------
Line Not Found ------
- 89. 96 3.36 2.051E+OO Line Not Found ------
93.35 ------
5.50 2.124E+OO Line Not Found ------
105.36 ------
- 1. 98 2.301E+OO Line Not Found ------
109.18 ------
- 1. 50 2.336E+OO Line Not Found ------
143.79 ------
10.50 2.402E+OO Line Not Found ------
163.38 ------
4.70 2.347E+OO Line Not Found ------
185.74 29 53.00*
2.260E+OO 1.770E-07 1.770E-07 40.10 194. 96 0.59 2.226E+OO ------
Line Not Found ------
202.13 ------
- 1. 00 2.197E+OO Line Not Found ------
205.33 4.70 2.184E+OO Line Not Found ------
Nuclide Line Activity Report (continued)
Sample ID : 30425 Acquisition date Flag: "*"
Keyline Page :
7 9-JUN-2014 20:36:41
Minimum Detectable Activity Report Page :
8 Sample ID 30425 Acquisition date 9-JON-2014 20:36:41 Bckgnd Energy MDA Nuclide Sum (keV)
(uCi/GR)
BE-7
- 3.
477.61 5.4378E-07 MN-54
- 0.
834.83 4.9818E-08 MN-56
- 0.
846.81 2.5170E-08 C0-57
- 18.
122.06 8.0595E-08 C0-58
- 2.
810.79
- 8. 7156E-08 C0-60
- 1.
1173.24 8.9426E-08 SB-124
- 2.
602.73 6.5107E-08 SB-125
- 0.
600.50 9.8885E-08 CS-134
- 3.
604. 71 6.7602E-08 CS-137
- 3.
661.66 9.0076E-08